Page 1 of 4 DATA SHEET S85001-0557
Not to be used for installation purposes. Issue 7
Edwards Signaling Catalog u Strobes, Horns, Bells, Chimes
06-27-13
Standard Features
• Field configurable – no need to remove the device!
– 15/30/75/95 cd and 95/115/150/177 cd clear strobe lens
models available
– Switch settings remain visible even after the unit is installed
• Unique low-profile design
– 30 per cent slimmer profile than comparable signals
– Attractive appearance
– No visible mounting screws
– Available with white or red housings
• Easy to install
– Fits all standard 4” square electrical boxes with plenty of
room behind the signal for extra wire – no extension ring or
trim plate needed
– #18 to #12 AWG terminals – ideal for long runs or existing wiring
• Unparalleled performance
– Exclusive FullLight strobe technology produces the industry’s
most even light distribution
– Precision timing electronics meet tough synchronizing
standards for strobes
– Low current draw minimizes system overhead
• Approved for public and private mode applications
– UL 1971-listed as signaling devices for the hearing impaired
– UL 1638-listed as protective visual signaling appliances
– UL/ULC listed for ceiling or wall use
Overview
Genesis life safety ceiling strobes are small, compact, and attrac-
tive visible emergency signaling devices. Protruding no more than
1.6” (41 mm) from the ceiling, Genesis strobes blend with any
decor.
Thanks to patented breakthrough technology, Edwards Gen-
esis strobes do not require bulky specular reflectors and lenses.
Instead, an exclusive cavity design conditions light to produce
a highly controlled distribution pattern. Significant development
efforts employing this new technology have given rise to a new
benchmark in strobe performance – FullLight technology.
FullLight strobe technology produces a smooth light distribution
pattern without the spikes and voids characteristic of specular
reflectors. This ensures the entire coverage area receives consis-
tent illumination from the strobe flash. As a result, Genesis strobes
with FullLight technology go well beyond the minimum UL-required
“cross” pattern, significantly exceeding UL-1971 and ULC-S526
light distribution requirements.
Depending on the model, clear lens Genesis ceiling strobes fea-
ture 15 to 95, or 95 to 177 candela output (see ordering informa-
tion), which is selectable with a conveniently-located switch. The
candela output setting remains clearly visible even after final instal-
lation, yet it is locked in place to prevent unauthorized movement
after installation.
Genesis appliances offer emergency signaling with clear or amber
lenses and with optional ALERT housing labels. They are ideal
for applications that require differentiation between life safety and
mass notification alerts.
Field Configurable
Ceiling Strobes
Genesis Series
One or more patents pending.
MEA
Pending