Page 1 of 4 DATA SHEET S85001-0557
Not to be used for installation purposes. Issue 7
Edwards Signaling Catalog u Strobes, Horns, Bells, Chimes
06-27-13
Standard Features
Field configurable – no need to remove the device!
15/30/75/95 cd and 95/115/150/177 cd clear strobe lens
models available
Switch settings remain visible even after the unit is installed
Unique low-profile design
30 per cent slimmer profile than comparable signals
Attractive appearance
No visible mounting screws
Available with white or red housings
Easy to install
Fits all standard 4” square electrical boxes with plenty of
room behind the signal for extra wire – no extension ring or
trim plate needed
#18 to #12 AWG terminals ideal for long runs or existing wiring
Unparalleled performance
Exclusive FullLight strobe technology produces the industry’s
most even light distribution
Precision timing electronics meet tough synchronizing
standards for strobes
Low current draw minimizes system overhead
Approved for public and private mode applications
UL 1971-listed as signaling devices for the hearing impaired
UL 1638-listed as protective visual signaling appliances
UL/ULC listed for ceiling or wall use
Overview
Genesis life safety ceiling strobes are small, compact, and attrac-
tive visible emergency signaling devices. Protruding no more than
1.6” (41 mm) from the ceiling, Genesis strobes blend with any
decor.
Thanks to patented breakthrough technology, Edwards Gen-
esis strobes do not require bulky specular reflectors and lenses.
Instead, an exclusive cavity design conditions light to produce
a highly controlled distribution pattern. Significant development
efforts employing this new technology have given rise to a new
benchmark in strobe performance – FullLight technology.
FullLight strobe technology produces a smooth light distribution
pattern without the spikes and voids characteristic of specular
reflectors. This ensures the entire coverage area receives consis-
tent illumination from the strobe flash. As a result, Genesis strobes
with FullLight technology go well beyond the minimum UL-required
“cross” pattern, significantly exceeding UL-1971 and ULC-S526
light distribution requirements.
Depending on the model, clear lens Genesis ceiling strobes fea-
ture 15 to 95, or 95 to 177 candela output (see ordering informa-
tion), which is selectable with a conveniently-located switch. The
candela output setting remains clearly visible even after final instal-
lation, yet it is locked in place to prevent unauthorized movement
after installation.
Genesis appliances offer emergency signaling with clear or amber
lenses and with optional ALERT housing labels. They are ideal
for applications that require differentiation between life safety and
mass notification alerts.
Field Configurable
Ceiling Strobes
Genesis Series
One or more patents pending.
MEA
Pending
Page 2 of 4 DATA SHEET S85001-0557
Not to be used for installation purposes. Issue 7
Application
Genesis strobes are UL 1971 or 1638 listed for indoor use. Prevailing
codes require strobes to be used where ambient noise conditions
exceed specified levels, where occupants use hearing protection,
and in areas of public accommodation. Consult with your Authority
Having Jurisdiction for details.
All Genesis strobes exceed UL synchronization requirements
(within 10 milliseconds over a two-hour period) when used with a
synchronization source. Synchronization for multiple strobe lights
in a single field of view is required.
Light output (effective cd)
Percent of UL rating versus angle
0 10 20 30 40 50 60 70 80 90 100 110 120102030405060708090100110120
0°15°
30°
45°
60°
75°
90°
-15°
-30°
-45°
-60°
-75°
Angle
Percentage of rated output
Horizontal and vertical outputs reflect the same pattern.
1.0"
(25 mm)
6.8" dia.
(173 mm)
0.60"(15 mm)
Dimensions
Installation
All models are intended for indoor applications only. Strobes
mount to any flush North-American 4” square electrical box, 21/8
(54 mm) deep.
Genesis ceiling strobes simply unlatch and twist to open. This
gains access to mounting screws and the selectable candela
switch. The shallow depth of Genesis devices leaves ample room
behind the signal for extra wiring. Once installed with the cover in
place, no mounting screws are visible.
95
75
15
30
Candela switch
Indicator
Field Configuration
Depending on the model, Genesis ceiling
speaker-strobes have multi-candela output
(see ordering information). The output
setting is changed by simply opening the
device and sliding the switch to the desired
setting. The strobe does not have to be
removed to change the output setting.
The setting remains visible through a small
window on the front of the device after the
cover is closed.
WARNING: These devices will not operate without electrical power. As fires frequently
cause power interruptions, we suggest you discuss further safeguards with your
local fire protection specialist.
Wiring
Field wiring terminals accommodate #18 to #12 AWG (0.75 mm²
to 2.5 mm²) wiring. Strobes are interconnected with a single pair of
wires as shown below.
Page 3 of 4 DATA SHEET S85001-0557
Not to be used for installation purposes. Issue 7
Current Draw
Current values are shown in mA.
Light output setting, standard models Light output setting, high output models
UL
Rating
15 cd 30 cd 75 cd 95 cd 95 cd 115 cd 150 cd 177 cd
RMS RMS RMS RMS RMS RMS RMS RMS
16 Vdc 109 151 281 318 330 392 502 565
16 Vfwr 131 194 379 437 432 518 643 693
Light output setting, standard models Light output setting, high output models
Typical
Current
15 cd 30 cd 75 cd 95 cd 95 cd 115 cd 150 cd 177 cd
RMS RMS RMS RMS RMS RMS RMS RMS
16 Vdc 94 140 273 325 333 392 499 551
20 Vdc 74 108 205 244 259 303 378 429
24 Vdc 63 90 168 194 212 245 306 342
33 Vdc 48 70 124 139 155 180 211 236
16 Vfwr 126 187 368 403 484 570 673 724
20 Vfwr 108 156 281 333 380 438 537 604
24 Vfwr 97 139 240 270 318 361 434 484
33 Vfwr 89 119 197 214 245 269 308 338
Specifications
Housing Textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Red and white models
available.
Lens Optical grade polycarbonate (clear).
Mounting Flush mount to North American 4-inch square electrical box, 2-1/8 (54 mm) inches deep. No extension ring required.
Suitable for indoor wall or ceiling applications.
Wire Connections Screw terminals: #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size.
Operating Voltage Regulated 16 to 33 Vdc, 16 to 33 Vfwr.
Operating environment Indoor: 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
Agency listings/approvals
Meets or exceeds year 2004 UL requirements for standards UL1638 and UL1971 and Canadian requirements for
standards CAN/ULC S526-02 and CAN/ULC S524-01. All models comply with ADA Code of Federal Regulation Chapter
28 Part 36 Final Rule. CSFM, MEA. FM pending.
Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15/30/75/95 cd (EGC-VM) and 95/115/150/177 cd (EGC-VMH)
Strobe operating voltage EGC-VM series strobes: non-coded, filtered 16-33 Vdc
or unfiltered 16-33 Vdc FWR.
Strobe flash rate
EGC-VM series strobes: one flash per second synchronized with optional EG1M Genesis Signal Master indefinitely within
10 milliseconds. Temporal setting (private mode only): synchronized to temporal output of Genesis audible signals on same
circuit.
Synchronization
Meets or exceeds UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ohms. Refer
to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire
resistance.
Synchronization Sources EG1M-RM, EBPS6A, EBPS10A, E-NAC, E-FSC, E-FSA
Page 4 of 4 DATA SHEET S85001-0557
Not to be used for installation purposes. Issue 7
06-27-13
Contact us...
Phone: 1-800-336-4206
Web: www.edwardssignaling.com
Edwards Signaling is
an EDWARDS brand.
3 Farm Glen Boulevard
Farmington, CT 06032
In Canada, contact Chubb Edwards...
Email: inquiries@chubbedwards.com
Web: www.chubbedwards.com
© 2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
Ordering Information
Model Housing Marking Lens Strobe Ship Wt.
Life safety Appliances (c/w running man icon screen printed on housing)
EGC-VM White None
Clear
Selectable
15, 30, 75, or 95 cd 1.8 lb.
(0.82 kg.)
EGCF-VM White “FIRE”
EGCFR-VM Red “FIRE”
EGC-VMH White None Selectable high output
95, 115, 150, or 177 cd
EGCF-VMH White “FIRE”