Solid-state timer
H3RN
Ultra-slim Timer for G2R Relay Socket
Pin configuration compatible with G2R Relay and mounts to the
P2R/P2RF Socket.
Standard multiple time ranges and multiple operating modes.
Conforms to EN61812-1 and IEC60664-1 4 kV/2 for Low Volt-
age, and EMC Directives.
Model Number Structure
Model Number Legend
1. Output
1: SPDT
2: DPST-NO
2. Time Range
None: Short-time range (0.1 s to 10 min)
1: Long-time range (0.1 min to 10 hrs)
Ordering Information
List of Models
Accessories (Order Separately)
Connecting Socket
H3RN-@@
1 2
Supply voltage Time-limit contact Short-time range model
(0.1 s to 10 min)
Long-time range model
(0.1 min to 10 h)
24 VAC;
12, 24 VDC
SPDT H3RN-1 H3RN-11
DPST-NO H3RN-2 H3RN-21
Note: Specify both the model number and supply voltage when ordering.
Example: H3RN-1 24 VAC
Supply voltage
Timer Track mounting/Front connecting socket Back connecting socket
H3RN-1/-11 P2RF-05-E P2R-057P
H3RN-2/-21 P2RF-08-E P2R-087P
http://www.ia.omron.com/ 2
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
Specifications
Ratings
Note: 1. When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages
(12 VDC: 95% to 110% of the rated voltage).
2. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
Characteristics
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Time ranges 0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max.
selectable)
0.1 min to 10 h (1 min, 10 min, 1 h, or 10 hrs max.
selectable)
Rated supply voltage (See note 2.) 24 VAC (50/60 Hz); 12, 24 VDC
Pin type Plug-in
Operating mode ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch
Operating voltage range 85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)
(See note 1.)
Reset voltage 10% max. of rated supply voltage
Power consumption 24 VAC: Relay ON: approx. 0.8 VA (0.6 W) at 24 VAC, 60 Hz
Relay OFF: approx. 0.6 VA (0.4 W) at 24 VAC, 60 Hz
12 VDC: Relay ON: approx. 0.5 W at 12 VDC
Relay OFF: approx. 0.2 W at 12 VDC
24 VDC: Relay ON: approx. 0.6 W at 24 VDC
Relay OFF: approx. 0.3 W at 24 VDC
Control outputs 3 A at 250 VAC, resistive load (cosφ = 1) (G6B-2@14P-FD-US used)
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Item H3RN-1/H3RN-2 H3RN-11/H3RN-21
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±15%±50 ms FS max.
Reset time Min. power-opening time: 12, 24 VDC: 0.1 s max. (including halfway reset)
24 VAC: 0.5 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different
poles)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 1 h each in 3 directions
Malfunction: 10 to 55 Hz, 0.5-mm single amplitude for 10 min each in 3 directions
Shock resistance Destruction: 300 m/s2
Malfunction: 100 m/s2
Ambient temperature Operating: 10°C to 55°C (with no icing)
Storage: 25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load at 1,800 operations/h)
Impulse withstand voltage Between power terminals: 1 kV
Noise immunity ±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity Destruction: 8 kV
Malfunction: 4 kV
Degree of protection IP40 (Terminal screw sections are excluded.)
Weight Approx. 18 g
EMC (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: IEC61000-4-3:10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge: IEC51000-4-5: 1 kV line to line (level 3)
2 kV line to ground (level 3)
Approved standards UL508, CSA C22.2 No. 14
Conforms to EN61812-1, IEC60664-1 4 kV/2.
Output category according to IEC60947-5-1.
http://www.ia.omron.com/ 3
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
Connections
Connection
Pulse Operation
A pulse output for a certain period can be obtained with a random external input signal.
Use the H3RN in interval mode as shown in the following timing charts.
OUT PW
Bottom View
H3RN-1/H3RN-11 H3RN-2/H3RN-21
DIN Indication DIN Indication
OUT PW
Bottom View
Timer
circuit Timer
circuit
H3RN-2/H3RN-21
External input
Power (3-8)
External short circuit (1-4)
External input (1-3)
Timer
circuit
50 ms
min.
Time limit contact
NO (6-5)
Run/Power indicator (PW)
Output indicator (OUT)
Note: t: Set time
Rt: Reset time
!Caution
Be careful when connecting wires.
Mode Terminals
Pulse operation Power supply between 3 and 8
Short-circuit between 4 and 1
Input signal between 3 and 1
Operating mode; interval and all other
modes
Power supply between 1 and 8
http://www.ia.omron.com/ 4
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
Operation
Timing Chart
Note: t: Set time
Rt: Reset time
Operating mode Timing chart
H3RN-1/H3RN-11 H3RN-2/H3RN-21
ON-delay
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Interval
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker OFF-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
Flicker ON-start
Power
Output
Power (1-5)
Time limit contact
NC (4-2)
Time limit contact
NO (4-3)
Run/Power
indicator (PW)
Output indicator
(OUT)
Power (1-8)
Time limit contact
NO (4-3, 5-6)
Run/Power
indicator (PW)
Output indicator
(OUT)
http://www.ia.omron.com/ 5
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
DIP Switch Settings
The 1-s range and ON-delay mode for H3RN-1/-2, 1-min range and ON-delay mode for H3RN-11/-21 are factory-set before shipping.
Time Ranges
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes
Note: The right two DIP switch pins are used to select the operating modes.
Nomenclature
Model Time range Time setting
range
Setting Factory-set
H3RN-1,
H3RN-2
1 s 0.1 to 1 s Yes
10 s 1 to 10 s No
1 min 0.1 to 1 min No
10 min 1 to 10 min No
H3RN-11,
H3RN-21
1 min 0.1 to 1 min Yes
10 min 1 to 10 min No
1 h 0.1 to 1 h No
10 h 1 to 10 h No
Operating mode Setting Factory-set
ON-delay Yes
Interval No
Flicker OFF-start No
Flicker ON-start No
Run/Power Indicator (Green)
(Lit: Power ON)
Output Indicator (Orange)
(Lit: Output ON)
Main Dial
Set the desired time according to time
range selectable by DIP switch.
http://www.ia.omron.com/ 6
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Timers
H3RN-1/H3RN-11 Front Mounting
H3RN-2/H3RN-21 Front Mounting
Mounting Height
P2RF-@-E P2R-@7P
H3RN Series H3RN Series
Use the P2RF-@-E or P2R-@7P to mount the H3RN. When ordering any one of these sockets,
replace "@" with "05" for SPDT or "08" for DPST-NO.
The P2RF-@ cannot be used because the hook is a different shape.
P2RF-@-E
Socket
79.5 (see note 1)
(83.5) (see note 2)
80.9 (see note 1)
(84.9) (see note 2)
P2R-@7P
Socket
Note: 1. The value shown indicates the dimension for the
P2RF-05-E with the PFP-@N Mounting Rail.
The value is 71.5 mm when using the PFP-N@2.
2. The value shown in parentheses indicates the
dimension for the P2RF-08-E with the PFP-@N
Mounting Rail.
The value is 75.5 mm when using the PFP-N@2.
http://www.ia.omron.com/ 7
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
H3RN
Safety Precautions
Correct Use
When using the H3RN in any place where the ambient temperature
is more than 50°C, supply 90% to 110% of the rated voltages (at
12 VDC: 95% to 110%).
Do not leave the H3RN in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts may become dam-
aged. Therefore, the use of the H3RN with a relay as shown in the
following circuit diagram is recommended.
The H3RN must be disconnected from the socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.
Do not connect the H3RN as shown in the following circuit diagram
on the right hand side, otherwise the H3RN’s internal contacts differ-
ent from each other in polarity may become short-circuited.
Use the following safety circuit when building a self-holding circuit
with the H3RN and an auxiliary relay, such as a G2R Relay, in combi-
nation.
In the case of the above circuit, the H3RN will be in pulse operation.
Therefore, if the circuit shown on page 3 is used, no auxiliary relay
will be required.
Do not use the SPDT contact in a circuit which may cause short-cir-
cuiting at three points (otherwise, short-circuiting of the power supply
may occur) because the SPDT contact of H3RN-1/-11 is composed
of an SPST-NC contact.
Do not set to the minimum setting in the flicker modes, otherwise the
contact may be damaged.
Do not use the H3RN in places where there is excessive dust, corro-
sive gas, or direct sunlight.
Make sure that there is a space of 3 mm or more between any H3RN
Models next to each other. (When using the P2RF-@-E Socket, a
space of 3 mm or more will be secured.) If a space of 3 mm or more
is not secured, the ambient temperature must be less than 50°C.
The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3RN.
Precautions for EN61812-1
Conformance
The H3RN as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied.
Handling
Do not touch the DIP switch while power is supplied to the H3RN.
Before dismounting the H3RN from the socket, make sure that no
voltage is imposed on any terminal of the H3RN.
Wiring
Basic insulation is ensured between the H3RN’s operating circuit and
control output.
Basic insulation: Overvoltage category III,
pollution degree 2
(with a clearance of 3.0 mm and a creepage
distance of 3.0 mm at 240 VAC)
The clearance from the edge of the P2R-087P Socket to internal,
current-carrying metal parts is 1.3 mm. Position the H3RN to provide
the necessary clearance for the voltage used.
When using the P2RF-@-E or P2R-057P Socket, basic insulation is
ensured in the mounted condition for a voltage of 250 VAC max.
X1T X2
X2/b T/a X1/a X1/a
X:
Auxiliary relay such as G2R Relay
L2L1
L2
L1
Correct Incorrect
G2R Relay
3
4
2
15
Short-circuit current
Power supply
for load
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
http://www.ia.omron.com/ C-1
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Safety Precautions for All Timers
Refer to the Safety Precautions for individual Timers for precautions specific to each Timer.
!WARNING
!CAUTION
Precautions for Safe Use
Operating Environment
Use the Timer within the ratings specified for ambient operating
temperature and ambient operating humidity for each model.
Store the Timer with the specified temperature range for each
model. If the Timer has been stored at a temperature of less than
10°C, allow the Timer to stand at room temperature for at least 3
hours before using it.
Use the Timer within the performance specified for water and oil
exposure for each model.
Do not use the Timer in locations subject to shock and vibration.
Long-term usage in such locations may damage the Timer due to
stress.
Magnetic contactors generate a shock of 1,000 to 2,000 m/s2 when
switching a load. When mounting to DIN Track, separate magnetic
contactors from the Timer so that the Timer is not subjected to
vibration and shock. Use anti-vibration rubber.
Do not use the Timer in locations subject to excessive dust,
corrosive gases, or direct sunlight.
Do not use organic solvents (such as paint thinner or benzine),
strong alkalis, or strong acids because they will damage the
external finish of the Timer.
Separate the input devices, input wiring, and Timer as far as
possible from sources of noise and power lines carrying noise.
When using the Timer in environments subject to large amounts of
static electricity (e.g., pipes carrying molding materials, powders, or
fluid materials), separate the Timer as far as possible from the
sources of static electricity.
Do not remove the external case from the Timer.
Do not use the Timer in locations where condensation may occur
due to high humidity or sudden temperature changes.
Condensation inside the Timer may result in malfunction or
damage to Timer elements.
The life of internal parts may be reduced if Timers are mounted in
close proximity to each other.
Resin and rubber parts (e.g., rubber packing) may deteriorate,
shrink, or harden depending on the operating environment (e.g.,
subjected to corrosive gases, ultraviolet light, or high
temperatures). We recommend periodic inspection and
replacement.
Normal operation may not be possible in locations subject to
sulfidizing gas, such as in sewer systems or waste incinerators.
OMRON does not market any Timers or other control devices for
operation in atmospheres containing sulfidizing gas. Seal the Timer
so that sulfidizing gas will not enter it. If sealing is not possible,
OMRON does provide special Timers with improved resistance to
sulfidizing gas. Ask your OMRON representative for details.
Power Supply
Be sure that the voltage applied is within the specified range,
otherwise the internal elements of the Timer may be damaged.
Install a switch or circuit breaker that allows the operator to
immediately turn OFF the power, and label it to clearly indicate its
function.
Maintain voltage fluctuations
in the power supply within
the specified range.
Use a commercial power supply for the power supply voltage input
to models with AC inputs.
Inverters with an output frequency of 50/60 Hz are available, but
the rise in the internal temperature of the Timer may result in
ignition or burning. Do not use an inverter output for the power
supply of the Timer.
The Timers listed below cannot be directly turned ON and OFF by
using an AC 2-wire proximity sensor to turn the Timer's power
supply ON and OFF.
Use the following countermeasure when using an AC 2-wire
proximity sensor with the Timer. (The power supply circuit in the
Timer uses half-wave rectification. Only a half AC wave is supplied
to the proximity sensor, which may cause operation to be unstable.)
Applicable Models
H3Y, H3YN, H3RN, H3CA-8, RD2P, and H3CR(-A, -A8, -AP, -F, and
-G)
Countermeasure
Wire through a relay and use the relay contacts to turn the power
supply ON and OFF.
Confirm the stability of operation after making the connections.
Install protective measures (such as earth leakage breakers, wiring
breakers, or fuses) on the power supply side according to any
applicable laws or regulations.
The following Timers contain lithium batteries that are
not explosion proof.
1. Timers with Built-in Batteries: H5L
The Timer contains a lithium battery, which may occasionally
ignite or rupture. Do not disassemble, deform under pressure,
heat to 100°C or higher, or incinerate the Timer.
2. Timers with Replaceable Batteries: Y92S-20 (for H5CN-M)
The battery may occasionally rupture, ignite, or leak fluid. Do
not short the positive and negative terminals. Do not charge,
disassemble, deform under pressure, or throw the battery into a
fire. If a non-specified battery is used, the battery may leak fluid
or rupture, occasionally resulting in equipment failure or minor
injury. Use only the specified battery.
The following Timers contain lithium batteries that are
explosion proof.
Timers with Built-in Batteries: H5BR, H5AN-4DM, H5S, H5F, and
H4KV
The Timer contains a lithium battery, which may occasionally
ignite or rupture. Do not disassemble, deform under pressure,
heat to 100°C or higher, or incinerate the Timer.
Allowable
Voltage Range
http://www.ia.omron.com/ C-2
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Correctly Handling Input Signals
Malfunction due to noise may occur if input wiring is placed in the
same duct or conduit as power lines or high-voltage lines. Separate
input wiring from power lines and wire them in a separate system.
Also, use shielded cables, use metal conduits, and keep wiring
distances as short as possible.
Timers with Relays
Do not connect a load that exceeds contact ratings, such as the
switching capacity (contact voltage or contact current). Insulation
faults, contact welding, contact faults, and other failures to achieve
specified performance may occur and the relay may be damaged or
may burn.
Continued use with deteriorated performance may ultimately result
in insulation breakdown between circuits or relay burning. The life
of the built-in relay is greatly affected by switching conditions.
Before using the Timer, test operation under actual application
conditions and confirm that the switching frequency presents no
problems in performance.
Electrical life depends on the type of load, switching frequency, and
ambient environment. Observe the following precautions when
using the Timer. When switching a DC load, contact transfer may
cause the contacts to stick or may cause contact failure. Confirm
applicability and consider using a surge absorbing element. When
switching at high frequencies, heat generated by arcing may cause
contacts to melt or may cause metal corrosion. Consider
connecting an arc absorbing element, reducing the switching
frequency, or lowering the humidity.
The surge current depends on the type of load, which also affects
contact switching frequency and the number of operations. Check
the rated current and the surge current, and design the circuits with
sufficient margin.
Arcing when switching and relay heating may result in ignition or
explosion. Do not use the Timer in atmospheres subject to
inflammable or explosive gases.
Contact faults may occur. Do not use the Timer in atmospheres
subject to sulfidizing gas, chloride gas, or silicon gas.
The switching capacity for DC voltage loads is lower than that for
AC voltage loads.
Timers with Non-contact Outputs
Short faults or open faults may occur due to destruction of the
output element. Do not use the Timer for a load that exceeds the
rated output current.
Short faults or open faults may occur due to destruction of the
output element from reverse electromotive force. When using the
Timer for a DC inductive load, always connect a diode as a
countermeasure against reverse electromotive force.
Other Precautions
Confirm that you have the correct model before using it.
Be sure that all terminals are wired correctly.
Always test the output status with a tester before using a Timer with
a built-in keep relay (e.g., the H3CR-H and H3DE-H). Shock
resulting from dropping the Timer during transport or handling may
cause the output contacts to reverse or to be in a neutral status.
Leaving the Timer with outputs ON at a high temperature for a long
time may hasten the degradation of internal parts (such as
electrolytic capacitors). Use the Timer in combination with relays
and avoid leaving the Timer with the output turned ON for an
extended period of time (e.g., for more than a month).
Reference Example (Use the Timer as shown below.)
Be sure that only a qualified worker (e.g., an electrical engineer)
performs electrical work for the Timer.
Resistive load Solenoid load Motor load Incandescent
lamp load
Rated current 10 to 20 times
the rated
current
5 to 10 times
the rated
current
10 to 20 times
the rated
current
Sodium light
loads
Capacitor
loads
Transformer
loads
Mercury light
loads
1 to 3 times the
rated load
20 to 40 times
the rated load
5 to 15 times
the rated load
1 to 3 times the
rated load
X
X1T X2
X2/b T/a X1/a X1/a
Auxiliary relay
(e.g., MY Relays)
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
2007.3
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2007 All Rights Reserved.
In the interest of product improvement, specifications are subject to change without notice.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specifi ed) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL
LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR
STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the product.
At the customer's request, OMRON will provide applicable third party certi cation documents identifying ratings and limitations of use that apply to the
products. This information by itself is not suf cient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifi cations and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when signi cant construction changes are made.
However, some specifi cations of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fi x
or establish key specifi cations for your application on your request. Please consult with your OMRON representative at any time to confi rm actual
specifi cations of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent
the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This catalog shall not be copied for sales or promotions without permission.
This catalog is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this
catalog in any manner, for any other purpose. If copying or transmitting this catalog to another, please copy or transmit it in its entirety.