Supply Specifications (cont.)
Fail polarity state delay
Upon loss of Dupline®carrier ≤20 ms
Power ON delay typ. 2s
Indication for:
Supply ON LED, Green
Dupline®carrier LED, Yellow
Output ON
LED, red (one per output)
Environment
Degree of protection IP 20
Pollution degree 3 (IEC 60664)
Operating temperature
-5 to +50°C (+23° to +122°F)
Storage temperature
-50 to +85°C (-58° to +185°F)
Humidity (non-condensing) 20 to 80%
Mechanical resistance
Shock 5 G (11ms)
Vibration 2 G (6 to 55Hz)
Housing H4-housing
Weight 400 g
Specifications are subject to change without notice (29.09.2005) 1
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description Ordering Key
Type: Dupline®
H4-housing
Receiver
Number of channels
Output type
Power supply
Output Module
Type G 3430 5545
• 8-channel receiver
• Relay load: 16A
• Module load: 32A (16 A per relay)
• Galvanically separated SPST relay outputs
• H4-housing
• For mounting on DIN-rail (EN 50022)
• LED-indications for supply, Dupline®carrier and outputs
• AC power supply
• Address coding by GAP 1605
Dupline receiver®designed to
be a part of the Dupline®
concept for Building Automa-
tion. SPST relay outputs for
Type Selection
Supply Ordering no.
24 VAC G3430 5545 024
115 VAC G3430 5545 115
230 VAC G3430 5545 230
control of 8 loads of up to
250 VAC/16 A.
Output Specifications
Outputs 8 SPST relays
Contact ratings (AgSn02) µ (micro gap)
Resistive loads AC1 16 A
Mechanical lifetime 5x106operations
Electrical lifetime
1x105operations/250 V, 12 A
Minimum load 100 mA/12 V
Operating frequency 60 operations/min.
Dielectric voltage
Outputs – Dupline®≥4 kVAC (rms)
Response time ≤1 pulse train
G 3430 5545 024
Supply Specifications
Power Supply Overvoltage cat. III
(IEC 60664)
Rated operational voltage
Through term. 21 & 22 230 VAC, +/- 10%
(IEC 60038)
115 VAC, +/- 10% (IEC 60038)
24 VAC, +/- 10%
Frequency 45 to 65 Hz
Rated operational power Typ. 2,5 VA
Power dissipation ≤4 W
Rated impulse withstand
voltage 230 4 kV
115 2,5 kV
024 800 V
Dielectric voltage
Supply – Dupline®≥4 kVAC (rms)
Supply – Outputs ≥2 kVAC (rms)
Mode of Operation
8-channel receiver with 8
normally open contact out-
puts. Each output is coded
by means of the code pro-
grammer GAP 1605. For
changing the default setting,
please refer to the datasheet
on GAP 1605.
The outputs are normally
OFF. When a transmitter
coded to the selected chan-
nel is activated, the output
turns ON and remains ON
until the respective channel
becomes deactivated. The
default setting is such that
upon loss of Dupline® carrier
all the outputs go OFF.
Note: At delivery some of the
relays might be ON due to
transportation bumps. To be
sure that the relays are OFF,
connect the module to power
and Dupline and transmit on
channels A1-8 once.
Note: Due to the construc-
tion with bistable relays, the
module is intended for heat-
ing and light control only.