43ZX1012-0VL21-1EA1
Table of Values
Table de valeur
Tabla de valores
Tabella dei valori
Screen Value Range Factory settings
Rated current - I N [A] 63 – 1600 fixed as per type
Continuous Amps - I r [A] 0.4 – 1.0 x IN1.0 x IN
Long Time Delay - t r [s] 2.5; 4; 6; 8; 10; 14; 17; 20; 25; 30 2.5
Short Time Pickup - I sd [A] 1.5 – 10 x Ir 10 x Ir
Short Time Delay - I sd [s] 0.1; 0.2 ; 0.3; 0.4; 0.5 0.1
IOC Amps - I i [A] 1.25 – 8...11 x IN3xIN
Prealarm - [A] 0.8 – 1.0 x Ir 1.0 x Ir
Neutral Ratio - I n [A] 0.5; 0.55; 0.6; ..... 1.0 x Ir1.0 x Ir
GF Pickup - I g [A] 0.4 – 1.0 x IN(≤ 1200 A) 1.0 x IN
GF Delay - [s] 0.1; 0.2; 0.3; 0.4; 0.5 0.4
Ecran Valeur Plage Réglage usine
Courant assigné - I N [A] 63 – 1600 fixe selon type
Courant permanent - I r [A] 0,4 – 1,0 x IN1,0 x IN
Retard de déclenchement longue durée - t r [s] 2,5; 4; 6; 8; 10; 14; 17; 20; 25; 30 2,5
Seuil de fonctionnement courte durée - I sd [A] 1,5 – 10 x Ir 10 x Ir
Retard de déclenchement courte durée - I sd [s] 0,1; 0,2 ; 0,3; 0,4; 0,5 0,1
Surintensité - I i [A] 1,25 – 8...11 x IN3xIN
Pré-alarme - [A] 0,8 – 1,0 x Ir 1,0 x Ir
Courant ininterrompu admissible (neutre) - I n [A] 0,5; 0,55; 0,6; ..... 1,0 x Ir1,0 x Ir
Seuil de fonctionnement sur défaut de terre - I g [A] 0,4 – 1,0 x IN (≤ 1200 A) 1,0 x IN
Retard sur défaut de terre - [s] 0,1; 0,2; 0,3; 0,4; 0,5 0,4
Pantalla Val. Rango Ajuste de fábrica
Corriente asignada - I N [A] 63 – 1600 fijo según tipo
Intensidad ininterrumpida - I r [A] 0,4 – 1,0 x IN1,0 x IN
Retardo disparo, largo plazo - t r [s] 2,5; 4; 6; 8; 10; 14; 17; 20; 25; 30 2,5
Valor de respuesta, corto plazo - I sd [A] 1,5 – 10 x Ir 10 x Ir
Retardo disparo, corto plazo - I sd [s] 0,1; 0,2 ; 0,3; 0,4; 0,5 0,1
Sobreintensidad - I i [A] 1,25 – 8...11 x IN3xIN
Prealarma - [A] 0,8 – 1,0 x Ir 1,0 x Ir
Intensidad interrumpida permitida (neutro) - I n [A] 0,5; 0,55; 0,6; ..... 1,0 x Ir1,0 x Ir
Valor de respuesta de efecto a tierra - I g [A] 0,4 – 1,0 x IN (≤ 1200 A) 1,0 x IN
Retardo de efecto a tierra - [s] 0,1; 0,2; 0,3; 0,4; 0,5 0,4
Maschera Valore Campo Impostazione di fabbrica
Corrente nominale - I N [A] 63 – 1600 fissa secondo il tipo
Cont. A - I r [A] 0,4 – 1,0 x IN1,0 x IN
Ritardo di sgancio di lunga durata - t r [s] 2,5; 4; 6; 8; 10; 14; 17; 20; 25; 30 2,5
Valore di risposta di breve durata - I sd [A] 1,5 – 10 x Ir10 x Ir
Ritardo di sgancio di breve durata - I sd [s] 0,1; 0,2 ; 0,3; 0,4; 0,5 0,1
IOC A- I i [A] 1,25 – 8...11 x IN3xIN
Preallarme - [A] 0,8 – 1,0 x Ir1,0 x Ir
Corrente permanente amm. (conduttore neutro) - I n [A] 0,5; 0,55; 0,6; ..... 1,0 x Ir1,0 x Ir
Valore di risposta su dispersione a terra - I g [A] 0,4 – 1,0 x IN (≤ 1200 A) 1,0 x IN
Ritardo su dispersione a terra - [s] 0,1; 0,2; 0,3; 0,4; 0,5 0,4