Electrical data
Primary nominal Primary current Type
DC current measuring range
IPN (A) IP (A)
50 0 .. ± 75 HNC - 050P
100 0 .. ± 140 HNC - 100P
HNC - 050P HNC - 100P
RMMeasuing resistance 60 .. 90 60 .. 80 Ω
ISN Second nominal current 50 50 mA
KNTurns ratio 1 : 1000 1 : 2000
VCSupply voltage (± 5 %) ± 15 V
ICCurrent consumpution 15 + ISN mA
VdR.m.s. voltage for AC isolation test, 50/60Hz, 1 min 2.5 kV
Accuracy-Dynamic performance data
XAccuracy @ TA = 25°C ± 1 % of IPN
εεLLinearity (0 .. ± IPN)< ± 0.5 %
IOElectrical offset current @IP = 0, @TA = 25°C ± 0.2 mA
IHC Hysteresis offset current @ IP = 0,
after an excursion of IPN ± 0.15 mA
IOT Thermal drift of IO 0°C .. +70°C ± 0.005 ms/°C
t rResponse time @ 90% of IP <1 µs
TCεεGThermal drift of the gain (% of reading) < ± 0.004 %/°C
General data
TAAmbient operating temperature - 10 .. + 80 °C
TSAmbient storage temperature - 15 .. + 85 °C
HNC - 200P HNC - 300P
RSSecondary coil Resistance
@TA = 25°C 75 95 Ω
mMass 30 g
Current Transducer HNC- 050 .. 100P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 100 A
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500 V
• Low power consumption
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external interference
Applications
• DC motor drives
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Battery supplied applications
• Inverters
www.nanalem.co.jp
010301/1