Bussmann®
LOW-PEAK®LPS-RK
Dual-Element, Time-Delay Fuses 70-600A
Class RK1 –– 600 Vac/300 Vdc
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Form No. LPS-RK 70-600
Page 3 of 3
Data Sheet: 1002
Current-Limitation Curves
Current-Limiting Effects
Prosp. Let-Through Current (Apparent RMS
S.C.C. Symmetrical) Versus Fuse Rating
100A 200A 400A 600A
5,000 2,200 3,250 5,000 5,000
10,000 2,700 4,100 7,150 9,600
15,000 3,050 4,650 7,950 10,650
20,000 3,300 5,100 8,650 11,500
25,000 3,500 5,500 9,200 12,200
30,000 3,700 5,800 9,650 12,750
35,000 3,900 6,100 10,100 13,300
40,000 4,050 6,400 10,450 13,750
50,000 4,300 6,850 11,100 14,600
60,000 4,550 7,250 11,700 15,300
80,000 4,950 7,950 12,650 16,450
100,000 5,250 8,550 13,450 17,450
150,000 5,900 9,750 15,050 19,400
200,000 6,450 10,700 16,300 20,900
250,000 6,850 11,500 17,350 22,100
300,000 7,250 12,200 18,250 23,200
*Values derived from curve data.
10-2-02 SB02295