09.10.2001 04.10.2001 Contents SIMATIC Process Control System PCS 7 Driver Blocks Notes 1 Signal blocks and diagnostic drivers 2 PROFIBUS PA - Blocks 3 Appendix Appendix Index Reference Manual Edition 10/2001 A5E00127662-01 A 09.10.2001 04.10.2001 Safety Guidelines This manual contains notices which you should observe to ensure your own personal safety, as well as to protect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: ! Danger indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. ! Warning ! Caution indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. indicates that minor personal injury or property damage can result if proper precautions are not taken. Note draws your attention to particularly important information on the product, handling the product, or to a particular part of the documentation. Qualified Personnel Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defined as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in accordance with established safety practices and standards. Correct Usage Note the following: ! Warning This device and its components may only be used for the applications described in the catalog or the technical descriptions, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. Trademarks SIMATIC(R), SIMATIC HMI(R) and SIMATIC NET(R) are registered trademarks of SIEMENS AG. Some of other designations used in these documents are also registered trademarks; the owner's rights may be violated if they are used by third parties for their own purposes. Copyright (c) Siemens AG 2001 All rights reserved Disclaimer of Liability The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. We have checked the contents of this manual for agreement with the hardware and software described. Since deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement are welcomed. Siemens AG Bereich Automatisierungs- und Antriebstechnik Geschaeftsgebiet Industrie-Automatisierungssysteme Postfach 4848, D- 90327 Nuernberg Siemens Aktiengesellschaft (c)Siemens AG 2001 Technical data subject to change. A5E00127662 09.10.2001 04.10.2001 Contents 1 Notes 1.1 1.2 2 Notes on Using Driver Blocks ...........................................................................1-1 General information on the block description....................................................1-2 Signal blocks and diagnostic drivers 2.1 2.1.1 2.1.2 2.2 2.2.1 2.3 2.3.1 2.4 2.4.1 2.4.2 2.4.3 2.5 2.5.1 2.5.2 2.5.3 2.6 2.7 2.7.1 2.7.2 2.7.3 2.8 2.8.1 2.8.2 2.8.3 2.9 2.9.1 2.10 2.10.1 2.10.2 2.10.3 OB_BEGIN: CPU diagnostics and AS connection diagnostics.........................2-1 Connections of OB_BEGIN...............................................................................2-5 Assignment of the control system messages of the OB_BEGIN ......................2-6 OB_END: Reset stack pointer of the OB_BEGIN ...........................................2-10 Connections of OB_END ................................................................................2-11 OB_DIAG: OB diagnostics to avoid CPU stop................................................2-12 Connections of OB_DIAG ...............................................................................2-14 SUBNET: Runtime group control for driver blocks .........................................2-16 SUBNET: DP Master system monitoring ........................................................2-16 Connections of SUBNET.................................................................................2-19 Message texts and auxiliary process values of SUBNET...............................2-20 RACK: Signal rack failure................................................................................2-20 RACK: Rack monitoring ..................................................................................2-20 Connections of RACK .....................................................................................2-24 Message texts and auxiliary process values of RACK ...................................2-24 PO_UPDAT: Update process image...............................................................2-25 IM_DRV: Transferring time-stamped process signal changes .......................2-26 Connections of IM_DRV..................................................................................2-31 Message texts and auxiliary process values of the IM_DRV..........................2-31 Interface IM .....................................................................................................2-33 MOD_1: Diagnostic driver for S7-300/400 SM modules which cannot be diagnosed with 16 channels............................................................................2-36 MOD_1: Monitoring of S7-300/400 SM modules which cannot be diagnosed with 16 channels maximum ......................................................2-36 Connections of MOD_1 / MOD_2 ...................................................................2-39 Message texts and auxiliary process values of MOD_1 / MOD_2..................2-40 MOD_2: Diagnostic driver for S7-300/400 SM modules which cannot be diagnosed with 32 channels.......................................................................2-41 MOD_2: Monitoring of S7-300/400 SM modules which cannot be diagnosed with 32 channels.......................................................................2-41 MOD_D1: Diagnostic driver for S7-300/400 SM modules which can be diagnosed with 16 channels............................................................................2-45 MOD_D1: Monitoring of S7-300/400 SM modules which can be diagnosed with 16 channels maximum ...........................................................2-45 Connections of MOD_D1 / MOD_D2 ..............................................................2-51 Message texts and auxiliary process values of MOD_D1 ..............................2-52 Process Control System PCS 7, Driver Blocks A5E00127662-01 iii 09.10.2001 04.10.2001 Contents 2.11 2.11.1 2.11.2 2.12 2.12.1 2.13 2.13.1 2.14 2.14.1 2.15 2.15.1 2.16 2.16.1 2.17 2.17.1 2.18 2.18.1 2.19 2.19.1 3 PROFIBUS PA blocks 3.1 3.1.1 3.1.2 3.1.3 3.2 3.2.1 3.2.2 3.2.3 3.3 3.3.1 3.3.2 3.3.3 3.4 3.4.1 3.4.2 3.4.3 3.5 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 3.5.6 3.5.7 3.6 3.6.1 3.6.2 3.6.3 3.7 3.7.1 3.7.2 iv MOD_D2: Diagnostic driver for S7-300/400 SM modules which can be diagnosed with 32 channels............................................................................2-53 MOD_D2: Monitoring of S7-300/400 SM modules which can be diagnosed with 32 channels............................................................................2-53 Message texts and auxiliary process values of MOD_D2...............................2-59 CH_AI: Analog value input ..............................................................................2-61 Connections of CH_AI.....................................................................................2-64 CH_AO: Analog value output ..........................................................................2-66 Connections of CH_AO ...................................................................................2-69 CH_DI: Digital value input ...............................................................................2-70 Connections of CH_DI ....................................................................................2-72 CH_DO: Digital value output ...........................................................................2-73 Connections of CH_DO...................................................................................2-75 CH_U_AI: Analog value input (Universal) .......................................................2-76 Connections of CH_U_AI ................................................................................2-80 CH_U_AO: Analog value output (Universal)...................................................2-82 Connections of CH_U_AO ..............................................................................2-85 CH_U_DI: Digital value input (Universal) ........................................................2-86 Connections of CH_U_DI................................................................................2-89 CH_U_DO Digital value output (Universal).....................................................2-90 Connections of CH_U_DO ..............................................................................2-93 PA_AI: Analog value input PROFIBUS PA .......................................................3-1 PA_AI: Analog Input PROFIBUS PA.................................................................3-1 Connections of PA_AI .......................................................................................3-4 Message texts and auxiliary process values of PA_AI .....................................3-6 PA_AO: Analog value output PROFIBUS PA ...................................................3-6 PA_AO: Analog Output PROFIBUS PA............................................................3-6 Connections of PA_AO .....................................................................................3-9 Message texts and auxiliary process values of PA_AO..................................3-12 PA_DI: Digital value input PROFIBUS PA ......................................................3-13 PA_DI: Discrete Input PROFIBUS PA ............................................................3-13 Connections of PA_DI.....................................................................................3-15 Message texts and auxiliary process values of PA_DI ...................................3-17 PA_DO: Digital value output PROFIBUS PA ..................................................3-17 PA_DO: Discrete Output PROFIBUS PA........................................................3-17 Connections of PA_DO ...................................................................................3-20 Message texts and auxiliary process values of PA_DO .................................3-22 PADP_L0x: Monitoring of DP/PA slaves.........................................................3-23 PADP_L00: Monitoring of DP/PA slaves with up to 7 slots ............................3-23 Message texts and auxiliary process values of PADP_L00............................3-27 PADP_L01: Monitoring of DP/PA slaves with up to 16 slots ..........................3-27 Message texts and auxiliary process values of PADP_L01............................3-31 PADP_L02: Monitoring of DP/PA slaves with up to 32 slots ..........................3-32 Message texts and auxiliary process values of PADP_L02............................3-36 Connections of PADP_L0x..............................................................................3-38 DPAY_V0: Monitoring of DP/PA-Link and Y-Link as V0 slave .......................3-38 DPAY_V0: Monitoring of DP/PA-Link and Y-Link as V0 slave .......................3-38 Connections of DPAY_V0 ...............................................................................3-43 Message texts and auxiliary process values of DPAY_V0 .............................3-44 PA_TOT: Totalizer PROFIBUS PA .................................................................3-45 Connections of PA_TOT .................................................................................3-48 Message texts and auxiliary process values of PA_TOT ...............................3-50 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Contents A Appendix A.1 A.2 A.3 A.4 A.5 A.6 A.7 Addressing ....................................................................................................... A-1 Error information of the MSG_STAT output parameter ................................... A-2 MODE settings for Signal Modules .................................................................. A-2 MODE settings for PA Devices ........................................................................ A-7 Text Library for Signal Modules ....................................................................... A-8 Text Libraries for DP-/PA-Slaves after a PA-/Y-LINK DP V0........................... A-9 Technical data ................................................................................................ A-10 Index Process Control System PCS 7, Driver Blocks A5E00127662-01 v 09.10.2001 04.10.2001 Contents vi Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 1 Notes 1.1 Notes on Using Driver Blocks General * The OBs in which the blocks are installed are given in the description of the driver blocks. Please note that not all OBs listed here are generated in all CPUs. Relevant information can be found in the Online Help of the respective OBs. * In the event that the driver blocks of PCS 7 Driver Blocks V52 are used by the driver generator, a firmware version V3.0 or faster is required in the target system. Signal Processing Blocks Three types of channel blocks for signal processing are available in this library of the driver blocks: 1. Standard Channel Blocks: CH_AI, CH_AO, CH_DI, CH_DO. They are used exclusively for signal processing of S7-300/400 SM modules. Please use these standard blocks if you want to achieve memory and run-time optimization and do not need to process any PA devices. 2. Universal Channel Blocks: CH_U_AI, CH_U_AO, CH_U_DI, CH_U_DO. These blocks are used for signal processing of S7-300/400 SM modules or a PA field device. The advantage of these blocks is that you can create CFC charts regardless of the hardware peripherals to be used later. As a disadvantage, the universal blocks require more memory and run-time. 3. PA Channel Blocks: PA_AI, PA_AO, PA_DI, PA_DO, PA_TOT These blocks are designed especially for use with PA field devices. They are used mainly where the special features of these devices should be used. In contrary to the CH blocks, the PA channel blocks process not only the signal itself, but also all variables according to the desired configuration of the hardware of the device. Process Control System PCS 7, Driver Blocks A5E00127662-01 1-1 09.10.2001 Notes 1.2 General information on the block description The block descriptions always have the same structure. The number of sections may vary depending on the block functions. The most common sections have the following meanings: Heading of the block description Example: RACK: Rack Monitoring The header begins with the type name of the block (RACK). This name is entered in the symbol name and has to be unique within your project. The type name also includes information on the task/function of the block (Rack Monitoring). Object name (Type + Number) FB x The object name for the block type is made up of the realization type Function block = FB, Function = FC and the Block number = x. Command button for the displaying the block connections Example: You can jump directly to the list of block connections of the designated block by clicking on the "Block Connections" command button. The preceding block symbol is used as an eye-catcher in order to find the command button rapidly. Note: The button is not visable in the paper printout. Area of Application You can see here which tasks the block should accept and other information about its use in CFC if necessary. Calling OBs Here you will find information relating to the organization blocks (OBs), in which the described block must be installed. When using the CFC installation is carried out in the cyclic OB (watchdog interrupt) and automatically into the OBs which are listed in the task list of the block (for example in OB100 for restarting). CFC creates the required OBs while compiling. If you use the blocks without CFC, you have to program these OBs and call the instance of the block in them. 1-2 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Notes Use in CFC If it is not already mentioned under "Area of Application", you can find the information here accepted by the driver generator. (the driver generator is called in SIMATIC manager by the selected chart folder and with the menu command Options > Charts > Generate Module Drivers... or as an option in the dialog box of the CFC "Compile Charts as Program"). Function and Operating principle This briefly describes the function of the block. Detailed information is displayed on complex blocks e.g. on the function of individual inputs, operating modes, time sequences etc.. Error handling You will find the error display in the CFC chart at the Boolean block output ENO. The value corresponds to the BIE (Binary result in STEP 7-STL after ending the block) or the OK bit (in SCL notation) and means: ENO=BIE=OK=1 (TRUE) ->The result of the block is OK. ENO=BIE=OK=0 (FALSE) ->The result or the conditions for its calculation (e.g. input values, operating modes, etc.) are not valid. In addition, for FBs, you will find the inverted BIE in output QERR of the instance DB: QERR=NOT ENO The error display arises by two independent routes: The operating system recognizes a processing error (for example: value overflow, called system functions supply an error code with binary input bit=0). This is a system utility and is not mentioned specifically in the individual block description. The block algorithm checks values and operating modes for their functional legality. These error cases are documented in the description of the block. The evaluation of the error indication can be used, for example, to generate messages (refer to the section on alarm blocks) or to utilize substitute values for invalid results. Start-up characteristics A difference is made between: * Initial start The block is called for the first time from the OB, in which it is installed. As a rule this is the OB in which normal, process-specific processing occurs (for example: the watchdog interrupt OB). The block enters the status corresponding to the input parameters. These can be initial values (also refer to the Connections) or values which you have already been configured, for example in CFC. The initial-start behavior is not described separately unless the block deviates from this rule. Process Control System PCS 7, Driver Blocks A5E00127662-01 1-3 09.10.2001 Notes * Start-up The block is executed once during a CPU start-up. This is achieved by calling the block from the start-up OB (where it is additionally installed either automatically via ES or manually by you via STEP 7). In this case the start-up characteristics are described. Time response The block with these characteristics must be installed into a watchdog interrupt OB. Reference is then made to the time characteristic when instructed by the block. Message characteristics The block with these characteristics signals various events to the higher-ranking OS. If they exist, the parameters required to generate messages are documented. Blocks not having message characteristics can be complemented by additional alarm blocks. A reference to the message characteristics in contained in the description of the individual blocks with signaling capabilities. Connections of ... The connections provide the data interface of the block. In addition you can transfer data to the block and fetch results from the block. Connection (parameter) Meaning Data type Default I/O OC&M SUBN1ERR 1=Error in DP master system BOOL 0 O + ..... The "Connections" table lists all the input and outputs of the block type, which the user can access with the configuration tools. They are alphabetically. Elements which can only be accessed from the algorithm of the block are not listed (so-called internal variables). The columns have the following meaning: Connection = Name of parameter, derived from the English designation. Wherever laid down by SIMATIC conventions, the same name rules have been used. The state of delivery of the block display in CFC is identified as follows: Connection name bold = Connection displayed, normal = Not displayed. Meaning = Function (possibly short description) Data type = S7 data type of the parameter (BOOL, REAL, etc.). Initial (Default) = The value of the parameter before the block is executed for the first time (unless changed by configuration). I/O = Type of access of the block algorithm to the parameter. Differentiates between inputs, non-interacting inputs and outputs (see table) 1-4 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Notes Abbreviation I/O I Input. Initialize block with parameters (representation in CFC: left-hand block side). O Output. Output value (representation in CFC: right-hand block side). IO Input/output. Non-interacting input which is written and which can be written back from the block (representation in CFC: left-hand block side). OC&M= Parameters marked with "+" can be operator controlled and monitored via the corresponding OS block. Operator control and monitoring The blocks from this library do not have preconfigured faceplates which control and monitor the OS. If individual faceplates are used for specific diagnostic blocks, the predetermined variables are transferred from the instance block to the OS. This has to be set for the driver generator in the dialog box "Settings - Generate Module Drivers" where the option "Operate C and M capability for diagnostic blocks" can be set. Default: Option is not set. Process Control System PCS 7, Driver Blocks A5E00127662-01 1-5 09.10.2001 Notes 1-6 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 2 2.1 Signal blocks and diagnostic drivers OB_BEGIN: CPU diagnostics and AS connection diagnostics Object name (Type + Number) FB 100 Area of Application The block is used for CPU diagnostics and connection diagnostics of the automation systems (AS). Installing the block in CFC creates all the acyclic priority classes (OBs) in which the blocks of the Driver Blocks library run. If the CFC function "Generate Module Driver" is used, the OB_BEGIN is installed automatically. Calling OBs: OB1 Cyclic processing OB32 Watchdog interrupt (connection diagnostics with SFC 87) *) OB70 I/O redundancy error OB72 CPU redundancy error OB80 Timeout OB81 Power failure fault OB82 Diagnostic interrupt OB83 Withdrawn/plugged alarm OB84 CPU hardware error OB85 Program execution error OB86 Rack failure OB100 Restart: OB121 Programming error OB122 I/O access error *) If you do not position the OB_BEGIN with the function "Create Module Driver" in the CFC chart, but insert it manually into a CFC chart, it is installed in the OB specified by "Predecessor for Installation". This may not be the OB32. Please note that only one watchdog interrupt OB is allowed. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-1 09.10.2001 Signal blocks and diagnostic drivers Function and Operating principle The block is used to signal and display CPU events and states. It reads the starting information of the priority classes (OBs), the diagnostic data of the I/O devices and enables the respective blocks on the basis of the start events. From the starting information of the SFC6 (RD_SINFO) or SFB 54 (RALRM) the OB_BEGIN determines the current OB in which it is running. In as far as it does not exist, it converts the logical basic address from the starting information into the geographic address. It is contained in the respective OBs of the output structure CPU_DIAG, which the downstream blocks can access. On the basis of the geographic address it enables the respective SUBNET blocks for further evaluation of the starting information. With the SFB 54 the diagnostic data are saved synchronously with the starting information in the CPU_DIAG.OB82 structure in a diagnostic case (OB82). Diagnostic (alarm) information longer than 59 bytes have to call the respective driver blocks themselves. The OB_BEGIN generates messages which are emitted with ALARM_8P to WinCC (see message characteristics). The SFC 87 C_DIAG is called in a watchdog interrupt OB (OB32) after 10 cycles have expired for connection diagnosis. Up to 64 connections are monitored. In the case of H systems the current state of the two H-CPUs is determined in the same watchdog interrupt OB by reading the system state list 71 (SSL71). For a detailed description of the meaning of the SSL71 please refer to the reference manual "System Software for S7-300/400 System and Standard Functions". Note The messages "Failure or redundancy loss connection ID" are generated at every CPU of the two connected AS. Exception at the failure of the CPU (or both H-CPUs) of an AS. Error handling The block evaluates the error information of ALARM_8P and writes it to the corresponding output parameters. See Error information of the MSG_STAT output parameter. The block may only be installed in a watchdog interrupt OB. Otherwise QERR = TRUE is set and operation is continued with the watchdog interrupt OB which first called the block after the restart/initial start. If the block installation sequence OB_BEGIN, xx blocks, ..., OB_END is not observed, the message "Incorrect installation OB_END, no OB8x processing" is output and QERR = TRUE is set. In this case no evaluation is carried out in the acyclic OBs. The downstream blocks are not enabled. 2-2 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Start-up characteristics The OB_BEGIN initializes the messages of ALARM_8P. In the case of H systems (CPU_DIAG.H_MODE = TRUE) the current state of the two H-CPUs is determined by reading the SSL71 (see Function). In as far as a CPU with SFC 87 exists, the connection diagnosis is initialized. The system then waits for 120 cycles in the watchdog interrupt OB until the connection diagnosis messages are generated. Initial-start behavior The starting information is read with SFC 6. Time response The block is installed into the required OBs (refer to the Function section) automatically during structuring by the ES, including into the watchdog interrupt OB32. The latter OB installations can be changed as required. Message characteristics The ALARM_8P multiple-instances are only called when a message of the OB_BEGIN is to be emitted. Effected acknowledgments of preceding messages are not updated by the respective ALARM block until this moment. If the connection to WinCC is interrupted, each ALARM_8P can save a maximum of two message states of an Event-ID. A programming error (OB121) is only generated by the CPU as a coming event. In the OB1 the respective generated coming message "Programming error" is reset as going. In order to avoid an overload of programming error messages these are counted within an interval of 1 minute. If more than 5 programming errors are noted within one minute, the subsequent ones are rejected. The maximum of 5 "Programming error" messages are then not generated until at least one minute has passed. Messages of the OB_DIAG block The OB-DIAG blocks are connected to the system structure OB_LOCK. If the OB82 is blocked by the OB_DIAG block, a message "OB82 failure SUBNET:xx RACK:yy SLOT:zz" is generated. If the OB86 is blocked by the OB_DIAG block, a message "OB86 failure SUBNET:xx RACK:yy SLOT:zz" is generated. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-3 09.10.2001 Signal blocks and diagnostic drivers The block generates the following messages in the OBs listed below: OB Starting event Message OB1 Cyclic processing Going message: Timeout Program execution error Programming error OB32 1 sec. watchdog interrupt or alternative watchdog interrupt OB Failure connection ID: xx coming/going Redundancy loss connection ID: xx coming/going OB72 CPU redundancy loss CPU redundancy loss/return OB80 Timeout OB81 Power failure fault Coming message at timeout: Cycle time exceeded OB request: OBxx still being processed OB request: Overflow PRIOxx Time interrupt xx expired Central controller battery failure coming/going Central controller backup voltage failure coming/going Central controller 24 V supply failure coming/going Redundant central controller battery failure coming/going Redundant central controller backup voltage failure coming/going Redundant central controller 24 V supply failure coming/going OB84 CPU hardware error MPSS error coming/going OB85 Program execution error Coming message at program execution error OBxx not loaded Access-error error xx: ... OB100 Restart: Initializing ALARM_8P OB121 Programming error Programming error coming Operator control and monitoring The block does not have a faceplate (display block). Note: In "Connection of OB_BEGIN" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 2-4 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.1.1 Connections of OB_BEGIN The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O OC &M CPU_DIAG System Structure CPU-Diagnosis STRUCT CPUERR_0 1=CPU Failure in Rack 0 BOOL 0 O + CPUERR_1 1=CPU Failure in Rack 1 BOOL 0 O + EN_SUBx Enable SUBNET x (xx=00 - 14) BOOL 0 O EV_IDx EVENT IDx Message Number ALARM_8P_x (x = 1 - 19) DWORD 0 I MASTER_0 1=Master CPU in Rack 0 BOOL 0 O + MASTER_1 1=Master CPU in Rack 1 BOOL 0 O + MSGSTATx Message Status Output WORD STATUS output of the ALARM_8P_x (x = 1 - 19) 0 O OB_LOCK LOCKED OB STRUCT QERR 1=Error BOOL 1 O QMSGERx Message Error Error output of the ALARM_8P_x (x = 1 - 19) BOOL 0 O Valid values O (is assigned by ES) O SUB0IDxx SUBNET primary ID (xx = 00 - 14) BYTE 255 I SUB1IDxx SUBNET secondary ID (xx=00 - 14) BYTE 255 I SZL_71 System Structure SSL71 STRUCT O The structure of the CPU_DIAG is implemented as OUT in the OB_BEGIN, and in all other blocks with this connection as IN_OUT (column: I/O). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-5 09.10.2001 Signal blocks and diagnostic drivers 2.1.2 Assignment of the control system messages of the OB_BEGIN The control system messages are assigned as follows with ALARM_8P at EV_ID1 Message block ALARM_8P Mess. No. OB No. Default message text Message class 1 OB80 Cycle time exceeded: OB@1%d@ms OB@2%d@ S 2 OB86 OB86 Failure SUBNET:@7%d@ RACK:@8%d@ S EV_ID1 3 OB84 MPI error S 4 - Error installation OB_BEGIN/OB_END: - 5 - Reserve - 6 OB122 Read error I/O device: @4%2s@@5%d@ Addr: @6%d@ S 7 OB122 Write error I/O device: @4%2s@@5%d@ Addr: @6%d@ S 8 OB72 CPU redundancy loss in Rack @3%d@ S No OB@10%d@ Processing Stack @9%d@ Messages 1, 6 and 8 are only coming events. They are reset as "going" during a normal run (OB1) of the block. Auxiliary process values of the EV_ID1 The control system messages are generated via ALARM_8P with EV_ID1 with six auxiliary process values. The table shows the assignment of the auxiliary process values to the block parameters. 2-6 Message block ALARM_8P Auxiliary process value Block parameter Data type EV_ID1 1 OB80_Supplementary_Info 1 WORD 2 OB80_1. Byte supplementary info 2_3 BYTE 3 Rack No. of the CPU BYTE 4 OB122_BLK_TYP WORD 5 OB122_BLK_NUM WORD 6 OB122_MEM_ADDR WORD 7 OB86 Subnet_ID BYTE 8 OB86 RACK_NO BYTE Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers The control system messages are assigned as follows with ALARM_8P at EV_ID2 Message block ALARM_8P Mess. No. OB No. Default message text Message class EV_ID2 1 2 OB81 OB81 Battery failure CPU in Rack 0 Battery failure CPU in Rack 1 S S S 3 4 OB81 OB81 Backup voltage failure Backup voltage failure S S 5 6 OB81 24V supply failure CPU in Rack 0 OB121 24V supply failure CPU in Rack 1 S S 7 OB121 Programming error @1%d@: @2%2s@@5%d@ /@6%d@/@4%d@/@3%d@ S 8 OB82 S CPU in Rack 0 CPU in Rack 1 OB82 Failure SUBNET:@7%d@ RACK:@8%d@ SLOT:@9%@ Message 7 is only a coming event. It is reset as "going" during a normal run (OB1) of the block. It is to be interpreted as follows in accordance with the error code number before the colon: OB121_BLK_TYP/OB121_BLK_NUM/OB121_PRG_ADDR/OB121_FLT_REG/OB121_RES ERVED_1. For a description please refer to the reference manual "System Software for S7300/400 System and Standard Functions". Example: 10.05.00 10:30:45 Programming error 35: FB44/1234/5/9 Auxiliary process values of the EV_ID2 The control system messages are generated via ALARM_8P with EV_ID2 with six auxiliary process values. The table shows the assignment of the auxiliary process values to the block parameters. Message block ALARM_8P Auxiliary process value Block parameter Data type EV_ID2 1 2 OB121_SW_FLT OB121_BLK_TYP BYTE WORD 3 4 OB121_RESERVED_1 OB121_FLT_REG BYTE WORD 5 6 OB121_BLK_NUM OB121_PRG_ADDR WORD WORD 7 8 OB82 SUBNET_ID OB82 RACK_NO BYTE BYTE 9 OB82 SLOT_NO BYTE Process Control System PCS 7, Driver Blocks A5E00127662-01 2-7 09.10.2001 Signal blocks and diagnostic drivers The control system messages are assigned as follows with ALARM_8P at EV_ID3 Message block ALARM_8P Mess. No. OB No. Default message text Message class EV_ID3 1 OB80 S OB request: OB@2%d@ still being processed 2 OB80 OB request: Overflow PRIO@3%d@ S 3 OB80 Time interrupt OB@1%d@ expired S 4 OB85 OB @4%d@ not loaded S 5 OB85 Access-error error @4%d@: @7%2s@@5%d@/@6%d@ S 6 - Reserve - 7 - Reserve - 8 - Reserve - Messages 1, 2, 3, 4 and 5 are only coming events. They are reset as "going" during a normal run (OB1) of the block. Auxiliary process values of EV_ID3 The control system messages are generated via ALARM_8P with EV_ID3 with six auxiliary process values. The table shows the assignment of the auxiliary process values to the block parameters. 2-8 Message block ALARM_8P Auxiliary process value Block parameter Data type EV_ID3 1 OB80_Supplementary_Info 1 WORD 2 OB80_1. Byte supplementary info 2_3 BYTE 3 OB80_2. Byte supplementary info 2_3 BYTE 4 OB85_Supplementary_Info 1 WORD 5 OB85_HW_Supplementary_Info 2_3 WORD 6 OB85_LW_Supplementary_Info 2_3 WORD 7 OB85_DKZ2_3 WORD Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers The control system messages are assigned as follows with ALARM_8 at EV_ID4 to EV_ID19: Message block ALARM_8P Mess. No. Default message text Message class 1 Failure connection ID: @1%d@ S 2 Failure connection ID: @2%d@ S 3 Failure connection ID: @3%d@ S 4 Failure connection ID: @4%d@ S 5 Failure connection ID: @5%d@ S 6 Failure connection ID: @6%d@ S 7 Failure connection ID: @7%d@ S 8 Failure connection ID: @8%d@ S 1 Redundancy loss connection ID: @1%d@ S 2 Redundancy loss connection ID: @2%d@ S 3 Redundancy loss connection ID: @3%d@ S 4 Redundancy loss connection ID: @4%d@ S 5 Redundancy loss connection ID: @5%d@ S 6 Redundancy loss connection ID: @6%d@ S 7 Redundancy loss connection ID: @7%d@ S 8 Redundancy loss connection ID: @8%d@ S EV_ID4 to EV_ID11 EV_ID12 to EV_ID19 Auxiliary process values from EV_ID4 to EV_ID19 The control system messages are generated via ALARM_8P with EV_ID4 to EV_ID19 with eight auxiliary process values. The table shows the assignment of the auxiliary process values to the block parameters. Message block ALARM_8P Auxiliary process value Block parameter Data type EV_ID4... EV_ID19 1 Connection_ID 1+x WORD 2 Connection_ID 2+x WORD 3 Connection_ID 3+x WORD 4 Connection_ID 4+x WORD 5 Connection_ID 5+x WORD 6 Connection_ID 6+x WORD 7 Connection_ID 7+x WORD 8 Connection_ID 8+x WORD x = 0 at EV_ID4, x = 8 at EV_ID5, x = 16 at EV_ID6 etc. to x = 56 at EV_ID12 x = 0 EV_ID13, x = 8 at EV_ID14, x = 16 at EV_ID15 etc. to x = 56 at EV_ID19 Process Control System PCS 7, Driver Blocks A5E00127662-01 2-9 09.10.2001 Signal blocks and diagnostic drivers 2.2 OB_END: Reset stack pointer of the OB_BEGIN Object name (Type + Number) FC 280 Area of Application The block is used to reset the stack pointer of the OB_BEGIN. Calling OBs The OB_END has to be installed at the end of the OB in which an OB_BEGIN is installed. An OB_END may not be installed in OBs in which no OB_BEGIN is installed. If the CFC function "Generate Module Driver" is used, the OB_END is installed automatically in the OBs of the run sequence. OB1 Cyclic processing OB32 Watchdog interrupt (connection diagnostics) *) OB70 I/O redundancy error OB72 CPU redundancy error OB80 Timeout OB81 Power failure fault OB82 Diagnostic interrupt OB83 Withdrawn/plugged alarm OB84 CPU hardware error OB85 Program execution error OB86 Rack failure OB100 Restart: OB121 Programming error OB122 I/O access error *) 2-10 If you do not position the OB_END block with the function "Create Module Driver" in the CFC chart, but insert it manually into a CFC chart, it is installed in the OB specified by "Predecessor for Installation". This may not be the OB32. Ensure that you use the watchdog interrupt OB of the OB_BEGIN. Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Function and Operating Principle The block decrements the stack pointer (NUM_CNT) of the OB_BEGIN. In case of an interruption it enters the last interrupted OB number from the CPU stack into the structure CPU_DIAG. Error handling Does not exist Start-up characteristics Do not exist Initial-start behavior Does not exist Time response Does not exist Message characteristics Do not exist Operator control and monitoring The block does not have a faceplate (display block). 2.2.1 Connections of OB_END Connection (parameter) Meaning Data type I/O CPU_DIAG CPU diagnostics (System Structure) STRUCT I/O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-11 09.10.2001 Signal blocks and diagnostic drivers 2.3 OB_DIAG: OB diagnostics to avoid CPU stop Object name (Type + Number) FC 281 Area of Application The block is used in order to avoid a CPU stop when there is a defective DP slave. It recognizes a DP slave failure. If DP slaves are activated in the H system, it indicates the preferred channel of the DP slave. Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The OB_DIAG block is installed after the SUBNET block. * Configuration of - 2-12 The inputs RACK_NO, DADDR, SUBN1_ID, SUBN2_ID and SUBN_TYP. Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers * Interconnection of - The EN input with the output of an AND block. Its inputs are interconnected to the output EN_SUBx (x = No. of the DP Master System) of the OB BEGIN block and to the output EN_Rxxx (xxx = Rack/Station Number) of the SUBNET block. - The OUT structure CPU_DIAG of the OB_BEGIN and SUB_DIAG of the SUBNET block with the INOUT structures of the same name of the OB_DIAG block. Function and Operating principle The block counts the frequency of the calls of an acyclic OB of a block instance before an OB1 can be executed. OB_DIAG displays higher-level errors of the CPU, DP Master and DP Slave (SUBN1ERR, SUBN2ERR). If DP slaves are activated, it determines the preferred channel (SUBN1ACT, SUBN2ACT). The group error information RACK_ERR displays the failure of the DP Master and the failure of the DP Slave. This means if RACK_ERR = 1, the corresponding DP Slave has failed, if SUBN1ERR or SUBN2ERR = FALSE. The start and diagnostic information is read from the structure CPU_DIAG which is interconnected to the structure CPU_DIAG of the block OB_BEGIN. The block determines the currently active preferred channel (SUBN1ACT, SUBN2ACT) in the case of redundant PROFIBUS DP interfaces by evaluating the error events and, if required, the diagnostic address ADDR of the DP slave. If the DP Slave is connected to a DP Master system which is operated in the DP V1 Mode, V1-MODE = TRUE is set. Overload behavior The OB_DIAG counts the frequency of the calls of the acyclic OB82 and OB86 (exception DP Master system failure, see SUBNET block). If the counter DIAG82_CNT > 5 or DIAG86_CNT > 5, EN_F = FALSE is set (disable function block). The counters are reset in the OB1. In all the other OBs the output EN_F = TRUE (enable function block) is set. If there is a malfunction of the OB82 or of the OB86, the OB_BEGIN block then signals this malfunction with geographic address of the DP Slave in the OB1 or OB82 or OB86 respectively. The event is not evaluated due to the disabling of the OB82 or OB86 respectively at an overload. The outputs cannot correspond to the current state of the DP Slave. After a waiting period of approx. 1 minute the state of the DP Slave is checked and the variable EN_86DIAG is set to TRUE in case of the OB86 failure. Updating of the state of the DP Slave can take several cycles. If there is an OB82 failure, the variable EN_82DIAG is set to TRUE. The interconnected DP Slave block can then fetch the current diagnostic data of the DP Slave. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-13 09.10.2001 Signal blocks and diagnostic drivers Redundancy The block supports the redundancy of the DP Master systems at an H system (only distributed I/O devices). To this purpose the inputs of the OB_DIAG block SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) are to be configured with the numbers of the redundant DP Master systems. If there is no redundancy of the DP Master systems, the remaining input must have the value 16#FF (default) assigned. Start-up characteristics A check whether the DP Slave is available is carried out. In the case of H systems the preferred channel of the DP Slave is determined. Error handling No plausibility checks are carried out with reference to the input parameters. Time response Does not exist. Message characteristics See OB_BEGIN block Operator control and monitoring The block has no faceplate. 2.3.1 Connections of OB_DIAG The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O ACC_ID 1=Accept MODE settings BOOL 0 I/O CPU_DIAG System Structure: CPU diagnostics STRUCT DADDR Diagnostic Address of DP-Slave INT 0 I/O EN_82DIAG 1=Read Diagnosis (OB82) BOOL 0 O EN_86DIAG 1=Read Diagnosis (OB86) BOOL 0 O EN_F 1= Enable Function/Function Block BOOL 0 O LOCK_82 1= Locked OB82 BOOL 0 I/O I/O LOCK_86 1= Locked OB86 BOOL 0 I/O LOCK_82_TM Delay Time Locked OB82 DINT 0 I/O 2-14 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Connection (parameter) Meaning Data type Initial I/O LOCK_86_TM Delay Time Locked OB86 DINT 0 I/O MSTR1ERR Reserve BOOL 0 I/O MSTR2ERR Reserve BOOL 0 I/O OB82_CNT Counter OB82 INT 0 I/O OB86_CNT Counter OB86 INT 0 I/O OB_LOCK System Structure: Locked OB STRUCT PARA Reserved BOOL 0 I/O QRACKF 1=Rack Error BOOL 0 O RACKF Reserve BOOL 0 I/O RACK_NO Rack Number BYTE 0 I/O SL1ERR Reserve BOOL 0 I/O SL2ERR Reserve BOOL 0 I/O SUB_DIAG OB_Start Information STRUCT SUBN_TYP 1=External DP interface BOOL 0 I/O SUBN1_ID ID of Primary DP master system BYTE 255 I/O SUBN1ACT 1=Slave 1 Active BOOL 0 O SUBN1ERR 1= Primary DP master system failure BOOL 0 O SUBN2_ID ID of Redundant DP master system BYTE 255 O SUBN2ACT 1=Slave 2 Active BOOL 0 O SUBN2ERR 1= Redundant DP master system failure BOOL 0 O SSL75 Reserve BOOL 0 I/O SSL92a Reserve BOOL 0 I/O SSL92b Reserve BOOL 0 I/O V1_MODE 1=DPV1-Mode BOOL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 I/O I/O 2-15 09.10.2001 Signal blocks and diagnostic drivers 2.4 2.4.1 SUBNET: Runtime group control for driver blocks SUBNET: DP Master system monitoring Object name (Type + Number) FB 106 Area of Application The block is used to reduce the acyclic OB processing times. Only the blocks actually affected can be called in case of an acyclic event. Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB81 Power failure fault OB82 Diagnostic interrupt OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * Creating runtime groups with driver blocks organized by racks. * Configuration of - 2-16 The inputs SUBN1_ID, SUBN2_ID and SUBN+TYP. Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers * Interconnection of - The outputs EN_Rxxx with the respective blocks (for example RACK). - The INOUT structure CPU_DIAG with the OUT structure of the OB_BEGIN block. - The OUT structure SUB_DIAG with the INOUT structures of the respective blocks (for example RACK). Function and Operating principle The SUBNET block monitors a DP Master system and enables the blocks (for example RACK) for executing the connected DP Slaves (for example ET200M). Corresponding messages are generated and the output variables SUBN1ERR and SUBN2ERR set at a failure or redundancy loss of a DP master system. The output structure SUB_DIAG contains the geographic address of the DP Master system (and DP Master system 2 at H systems) as well as the group area information SUBN0_ERR (for DP Master system 1) and SUBN1_ERR (for DP Master system 2). If SUBN0_ERR = 1 or SUBN1_ERR = 1, the corresponding DP Master system is not available. The SUBNET block is installed per connected DP Master system or once for the centrally plugged I/O devices into the OBs listed above and is enabled by the OB_BEGIN block. The start and diagnostic information is read from the I/O structure CPU_DIAG. It has to be interconnected to the structure CPU_DIAG of the OB_BEGIN block (is implemented automatically with the CFC function "Generate Module Driver"). The SUBNET block has one enable output per connectable rack or DP Master system (per expansion rack in the case of centralized I/O devices). It uses the starting information of the calling OB to determine whether the signaled result has occurred at its DP Master (or at the centrally plugged I/O devices) and then sets the output for the respective rack or for the DP Master system (EN_Rx). If redundant DP Master systems are used (only for H-CPUs), a rack (for example ET200M) is connected to the two DP Masters and has the same station number at both. The SUBNET block has two inputs (SUBNx_ID) and the type identifier SUBN_TYP. If the DP Master is the integrated interface of the CPU module, SUBN_TYP = FALSE is to be set. Otherwise SUBN_TYP = TRUE is to be set. If a DP line fails, all EN_Rxxx are set to TRUE and the redundancy loss or failure is signaled. The redundancy or DP Master return is signaled as soon as a failed DP slave has established the connection again. The state of the DP Master system, the set SUBNx_ID with type identifier, is saved in the output structure SUB_DIAG. If the event "Power failure fault" (OB81) occurs, the SUBNET block only enables the RACK blocks if they are expansion racks. Expansion racks exist if SUBNx_ID = 0. If you want to change the inputs SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) online without using the CFC function "Generate Module Driver", you have to set the input ACC_ID = TRUE. This updates the output values. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-17 09.10.2001 Signal blocks and diagnostic drivers Redundancy The SUBNET block supports the redundancy of DP Master systems of the CPU 417H in case of distributed I/O devices. To this purpose the inputs SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) are to be configured with the numbers of the redundant DP Master systems. If there is no redundancy, the remaining input must have the value 16#FF (default) assigned. Error handling Error handling of the block is limited to the error information of ALARM_8P. Refer to Error information of the MSG_STAT output parameter Start-up/Initial-start behavior The SUBNET block initializes the messages of ALARM_8P. The operating mode of the DP Master system is sampled and entered in the structure SUB_DIAG.V1_MODE with SSL 0X90H (0 = compatibility mode, 1= DPV1 mode). If the DPV1 mode is active, the structure CPU_DIAG.MODE_V1 is also set to TRUE. Overload behavior The SUBNET block counts the OB86 calls (only failures). The counter is reset in the OB1. If more than two OB86 failure events occur successively before the cycle checkpoint (OB1) is reached, these are rejected and a message "Failure OB86 DP Master system:x" is emitted. If an OB86 call is rejected, the DP Master system is registered as having failed. Time response Does not exist. Message characteristics After being called by an OB86, OB70 and OB72 the block analyzes the state of the DP master system assigned to it and generates the corresponding messages for redundancy loss and DP Master system failure by emitting an ALARM_8P. Messaging can be de-activated by using EN_MSG = FALSE. The SUBNET block generally only signals events whose cause lies within the DP Master system monitored by it. Exception CPU failure in the H system: 2-18 - Non-redundant DP Master system: Message "DP Master failure". - Redundant DP Master system: Message "DP Master redundancy loss". Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Operator Control and Monitoring The block has no faceplate. Note: In "Connection of SUBNET" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 2.4.2 Connections of SUBNET The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O ACC_ID 1=Accept MODE settings BOOL 0 I/O CPU_DIAG CPU diagnostics STRUCT EN_MSG 1=Enable message BOOL 1 I EN_Rxxx 1=Enable Rack xxx BOOL 0 O EV_ID Message ID DWORD 0 I MSG_STAT Message Failure WORD 0 O SUB_DIAG System Structure: CPU diagnostics STRUCT SUBN_TYP 1=External DP-Interface BOOL 0 I/O SUBN1_ID ID of Primary DP master system BYTE 255 I/O SUBN1ERR 1= Error in primary DP Master system BOOL 0 O SUBN2_ID ID of Redundant DP master system BYTE 255 I/O SUBN2ERR 1= Error in Redundant DP master system BOOL 0 O OC&M I/O O + + Note The number of racks possible results from the address volume of PROFIBUS. All available CPUs can thus be used. The entire address volume is used by the CPU 417-4. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-19 09.10.2001 Signal blocks and diagnostic drivers 2.4.3 Message texts and auxiliary process values of SUBNET Assignment of message text and message class Message No. Default message text Message class 1 DP master @1%d@: Redundancy loss S 2 DP master @2%d@: Redundancy loss S 3 DP master @1%d@: Failure S 4 DP master @2%d@: Failure S 5 Multiple line failure @2%d@OB86 lock Assignment of the auxiliary values 2.5 2.5.1 Value Block parameter 1 Primary DP Master system number (SUBN1_ID) 2 Redundant DP Master system number (SUBN2_ID) RACK: Signal rack failure RACK: Rack monitoring Object name (Type + Number) FB 107 Area of Application The block monitors the state of a rack, a DP/PA or Y-Link DP V1 and signals the corresponding error events. 2-20 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB81 Power failure fault OB82 Diagnostic interrupt OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The RACK block is installed automatically in the run sequence after the SUBNET block. * Configuration of - * The inputs RACK_NO, DADDR, SUBN1_ID, SUBN2_ID and SUBN_TYP. Interconnection of - The EN input with the output of an AND block. Its inputs are interconnected to the output EN_SUBx of the OB BEGIN block and to the output EN_Rxxx of the SUBNET block. - The OUT structure CPU_DIAG of the OB_BEGIN and SUB_DIAG of the SUBNET block with the INOUT structures of the same name of the RACK block. - OS operation: (LINK_MAN = 0): Low-speed and high-speed operation can be switched on via the input SP1_ON and SP2_ON repectively and the input MOT_OFF stops the operation. The enablings (S1_OP_EN, S2_OP_EN or OFFOP_EN) have to be available. Function and Operating principle The RACK block generates a process control system fault message for the OSs in case of redundancy losses and rack or stations failures. In addition it indicates faults within the rack/the station (SUBN1ERR, SUBN2ERR) and the preferred channel (SUBN1ACT, SUBN2ACT) when the DP slaves are activated at the outputs. The output structure RAC_DIAG contains the geographic address of the rack as well as the group error information RACK_ERR. If RACK_ERR = 1, the corresponding rack is not available. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-21 09.10.2001 Signal blocks and diagnostic drivers The block is installed into the OBs listed above for each connected station and once for the centrally plugged I/O devices. The runtime groups, in which the RACK block is installed is enabled by the SUBNET block. The start and diagnostic information is read from the I/O structure CPU_DIAG. It has to be interconnected to the structure CPU_DIAG of the OB_BEGIN block (is implemented automatically with the CFC function "Generate Module Driver"). The RACK block has one enable output per slot of the rack (station). The RACK block generates the number of a corresponding message (see Message Behavior) on the basis of the start information of the calling OBs if the current block is affected. The block determines the currently active preferred channel (SUBN1ACT, SUBN2ACT) in the case of redundant PROFIBUS DP interfaces by evaluating the error events and, if required, the diagnostic address ADDR of the DP slave. If you want to change the inputs SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) online without using the CFC function "Generate Module Driver", you have to set the input ACC_ID = TRUE. This updates the output values. Redundancy The RACK block supports the redundancy of DP Master systems within the H systems in case of distributed I/O devices. To this purpose the inputs of the RACK block SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) are to be configured with the numbers of the redundant DP Master systems. If there is no redundancy, the remaining input must have the value 16#FF (default) assigned. Error handling Error handling of the block is limited to the error information of ALARM_8P. Refer to Error information of the MSG_STAT output parameter Start-up characteristics The RACK block initializes the messages of ALARM_8P. A check whether the station is available is carried out. In the case of H systems the preferred channel of the station is determined. The structure SUB_DIAG.V1_MODE (0 = compatibility mode, 1= DPV1 mode) is transferred to the structure RAC_DIAG.V1_MODE. Overload behavior The RACK block counts the OB86 calls (exception DP Master system failure, see SUBNET block). The counter is reset in the OB1. If more than two OB86 events occur successively before the cycle checkpoint (OB1) is reached, these are rejected and a message "Failure OB86 DP Master:x Rack:y" is emitted. If an OB86 call is rejected, the rack (station) is registered as having failed. 2-22 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Time response See Message characteristics Message characteristics After being called by OB70, OB72, OB85 or OB86 the block analyzes the state of the CPU, DP master and DP slaves assigned to it. If necessary, it generates the corresponding messages for redundancy losses and rack (station) failures in the rack by emitting an ALARM_8P. Messaging can be de-activated by using EN_MSG = FALSE. The block generally only signals events whose cause lies within the rack monitored by it. Redundancy loss and station failures which are caused by the failure of a DP masters or of a CPU, are initially neither signaled nor indicated at the outputs SUBN1ERR and SUBN2ERR. The DELAY input allows a signal delay, which can be configured, for an outgoing higher-order error. If, for example, the RACK block recognizes an outgoing error in a DP master connected to it, it initially assumes that there is a faulty assigned DP slave in the rack monitored by it and sets the corresponding output SUBNxERR. The error is not canceled until the DP slave returns (in this case: OB86, OB70). The RACK blocks suppress the potential slave failure for DELAY seconds in order not to trigger a wave of messages from the DP slaves which are not synchronized yet after the master returns. An error message is not output to the OSs unless a DP slave does not report its return before this period expires. Note You should not set the value of DELAY too high. Otherwise DP slaves which were removed during the master failure or which are defective will be reported back to the OSs after the master returns with a correspondingly high delay period. The RACK block generates the following messages in the OBs listed below: OB Starting event Message OB1 Cyclic processing Repeat updating ALARM_8P outputs / messages, if necessary OB70 Redundancy loss DP Slave redundancy loss/return OB81 Power failure fault - Rack battery failure coming/going - Rack backup voltage failure coming/going - Rack 24 V supply failure coming/going OB85 I/O access error Rack failure going OB86 Rack monitoring Rack failure coming/going OB100 Restart: Initializing ALARM_8P Process Control System PCS 7, Driver Blocks A5E00127662-01 2-23 09.10.2001 Signal blocks and diagnostic drivers 2.5.2 Connections of RACK The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O ACC_ID 1=Accept MODE settings BOOL 0 I/O CPU_DIAG CPU diagnostics (System Structure) STRUCT DADDR Diagnostic Address of DP-Slave INT 0 I DELAY Alarm Delay (s) INT 15 I O&M I/O EN_MSG 1 = Enable message BOOL 1 I EN_Mxx 1=Enable module xx (xx = 00 - 30) BOOL 1 I EV_ID Message number DWORD 0 I 0 MSG_STAT Message error information WORD RAC_DIAG System Structure (reserve): STRUCT RACK_NO Rack Number BYTE SUB_DIAG OB_Start Information STRUCT SUBN_TYP 1=External DP interface BOOL 0 I/O SUBN1_ID ID of Primary DP master system BYTE 255 I/O SUBN1ACT 1=Slave 1 Active BOOL 0 O + SUBN1ERR 1=Error in Primary DP master system BOOL 0 O + SUBN2_ID ID of Redundant DP master system BYTE 255 I/O SUBN2ACT 1=Slave 2 Active BOOL 0 O + SUBN2ERR 1=Error in Redundant DP master system BOOL 0 O + 2.5.3 O I 0 I I/O Message texts and auxiliary process values of RACK Assignment of message text and message class 2-24 Message No. Default message text Message class 1 Station @1%d@/ @3%d@: Redundancy loss S 2 Station @2%d@/ @3%d@: Redundancy loss S 3 Station @1%d@/ @3%d@: Failure S 4 Station @2%d@/ @3%d@: Failure S 5 Station @1%d@/ @3%d@: Backup battery failure S 6 Station @1%d@/ @3%d@: Backup voltage failure S 7 Station @1%d@/ @3%d@: 24 V supply failure S 8 Multiple line failure @1%d@/ @3%d@ OB86 Lock S Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Assignment of the auxiliary values Value Block parameter 1 Primary DP Master system number (SUBN1_ID) 2 Redundant DP Master system number (SUBN2_ID) 3 Rack or station number (RACK_NO) Special case at OB81 (Power failure fault): If SUBN1_ID = 16#FF, auxiliary process value 1 = SUBN2_ID is set. 2.6 PO_UPDAT: Update process image Object name (Type + Number) FC 279 Area of Application The block ensures the functions "Hold last value" and "Apply substitution value" of the output modules when a CPU is restarted (OB100). Calling OBs The block must be installed at the end of the OB100. This is carried out for you by the CFC function "Generate Module Driver". Functional description When a CPU is restarted (OB100), the CH_AO, CH U AO, CH_DO and CH_U_DO blocks write the start values to the process image. The PO_UPDAT block sends all the (part) process images to the modules at the end of the OB100 in order for these values to be active immediately when the CPOU passes to RUN. The output PO_MAP indicates the part process images updated or used in the system (BIT0: Process image 0, BIT15: Part process image 15). Connections of PO_UPDAT Connection (Parameter) Meaning Data type Defalt. Type PO_MAP (Part) Process images updated or used in system (BIT0: OB1 process image, BIT1 - 15: part process image 1 - 15) WORD 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-25 09.10.2001 Signal blocks and diagnostic drivers 2.7 IM_DRV: Transferring time-stamped process signal changes Object name (Type + Number) FB 90 Calling OBs If you use CFC, the block is installed automatically in the run sequence. OB1 Cyclic program OB40 Process interrupt 0 OB100 Restart (warm start) Alternatively to OB40 the block can also be installed in another process interrupt (OB41 to OB47). Area of Application The block is used to transfer time-stamped process signal changes and non-signalspecific events (special messages) to the OS. Functional description and Operating principle In an AS the block forms the interface between an IM151-2 or IM153-2 and the OS (WinCC). It reads the messages from the message buffers (max. of 20 messages each) of an IM and uses the pseudo message function ALARM_T to transfer these to the OSs. 2-26 * Process interrupt: The IM creates a process interrupt when there are new messages. The status of the time stamp with the number of the record to be fetched of the IM and the number of messages in the record are stored for cyclic processing from the start information of the process interrupt OB (refer to the process interrupt data). The information of up to 17 process interrupts can be stored. If the maximum number is exceeded, the new information is lost. * Cyclic processing: If messages are ready to be fetched, the respective record (message buffer) is read by the SFC 59/RD_REC (read record). If several records are to be fetched, the record with the oldest messages (oldest process interrupt) is fetched. A maximum of 20 messages of a record (current number of messages is listed in the process interrupt data) are saved temporarily in the instance of the block As soon as a record has been read, new messages can be entered again from Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers the IM. If all the records are occupied, the IM enters the special message "Buffer overflow coming" into the message buffer. The special message "Buffer overflow going" is entered as the first message into the first free record. Messages which occur between the occurrence of a buffer overflow and the enabling of a record are lost. The slot no./channel no. of the stored messages are compared with the input parameters of the block for the slot no./channel no. (S_CH_xxx). If they agree, the message is assigned to the corresponding event ID (EV_ID_xxx) and signal number (1 to 8) of the pseudo ALARM_T (ALARM_8P) block. The time stamp of the message (8 bytes) is entered in the ARRAY of byte (index corresponding to the signal number of the pseudo ALARM_T). When all the messages have been assigned, the pseudo ALARM_T blocks which are to transfer the new messages to OSs are called up. The return signals of the pseudo ALARM_T and of the process control system message block ALARM_8P (STAT_xx, M_ACK_xx) are available at the block output. If STAT_xx = 11 (previous job not yet completed) the pseudo ALARM_T or ALARM_8P is called again in the next cycle. In all other cases messages can be lost. If no agreement can be found with the input parameters at a message, the output QBPARF is set TRUE for one cycle (see error handling). The event is signaled (see Message characteristics). Addressing/Configuration Also refer to Addressing The logical address of the IM determined with HW Config (corresponds to the diagnostic address) is entered at the block input (LADDR) of the driver. Each change to the LADDR block input leads to a single check corresponding to the start-up characteristics of the block. Saved process interrupt data are deleted. If you run the DP master system in the DPV1 mode, you have to enter the E address of the IM at the block input (LADDR). The RACK into which the IM is plugged is monitored by the RACK block. You have to connect the input RAC_DIAG with the output RAC_DIAG of the corresponding RACK block. The rack number is set at the RACK block. Process signals which are to be provided with a time stamp and are detected via an IM must be configured correspondingly in the HW Config. Each signal which is provided with a time stamp from the IM has a unique assignment through its slot in combination with the corresponding channel number. There are 128 inputs of data type WORD for 128 signals. The slot number of the respective digital input module is entered in the higher-value byte and the channel number (signal of the digital input module) in the lower-value byte. The slot and signal number of the process signals are entered in the block inputs (S_CH_xxx) (hexadecimal format). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-27 09.10.2001 Signal blocks and diagnostic drivers Example: You have set the digital signal 10 of a digital input module plugged into slot 5 of an ET200M to 10 ms exact time stamp by means of HW Config. You have to enter the number 16#050A at the first free input S_CH_xxx of the IM_DRV. Error handling I/O access error: QPERAF The block could not access IM. A record could not be read. If it is not stored in the IM, these messages are lost. Block processing error: QERR An error has occurred while the block was being processed. Module configuration error: QPARF Incorrect module configuration (incorrect logical basic address entered). Configuration error: QBPARF The block was configured incorrectly. The slot/channel number of an IM message does not agree with any slot/channel number of the block input parameters (message is lost). Rack error: QRACKF Failure of the rack in which the IM is plugged or a failure of IM Start-up characteristics of the IM When the IM is started up/restarted process interrupts are emitted again for those records which were occupied before restarting but had not been fetched. The special message "Begin start-up data" is entered as the first message into the first free record. Then all the digital signals to be monitored are checked for changes after the restart and a message is triggered, if appropriate. The special message "End start-up data" is generated finally. Start-up characteristics of the driver block IM_DRV Initialization of the ALARM_8P and the pseudo ALARM_T blocks with the data stored before the STOP state of the CPU. At a start-up the signal state is initialized to "Zero". At a start-up/initial start the driver checks whether there is an IM under the logical address LADDR. Otherwise the driver sets its output QPARF = TRUE and does not carry out any further I/O accesses in the subsequent cycles. Not until the right module has been plugged or until after new configuration does QPARF = FALSE and is the I/O access enabled. Stored process interrupt data which were not processed before the restart are deleted. 2-28 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Redundancy In the case of H systems with two IM units redundancy exists with regard to the time stamp if * The communication between the two IM units runs via the communication bus, * Updating of the active and passive IM has been completed free of errors A redundancy loss (failure of an IM) is signaled outside the IM_DRV by means of the SUBNET and RACK blocks. The time stamp function is interrupted during a changeover between the active and passive IM. The interruption period is displayed with the special message "Changeover at redundancy beginning/end". In a normal case the active informs the passive IM of the current I/O device state. If this communication is faulty, the special message "Redundancy_Info_Loss coming" is output. As soon as the I/O device state between the active and passive IM has been compared, the special message "Redundancy_Info_Loss going" is output. Time response Does not exist. Message characteristics The block uses one ALARM_8P and 17 pseudo ALARM_T blocks which are installed as multiple instances. Transferring of the 8 time-stamp values per pseudo ALARM_T call is carried out via an ARRAY [0..65] of BYTE. The ARRAY is structured as follows: BYTE 0 - 1: Format identifier of the following date/time stamp BYTE 2 - 9: Date/time stamp for Signal_1 BYTE 10 - 17: Date/time stamp for Signal_2 . . BYTE 58 - 65: . . Date/time stamp for Signal_8 Process Control System PCS 7, Driver Blocks A5E00127662-01 2-29 09.10.2001 Signal blocks and diagnostic drivers The format identifier of the bytes 0 -1 specifies the bit coding of the time stamp structure (8 bytes are assigned to one time stamp value): Format identifier: 0 Date/time in SIMATIC S7 BCD format ( DATE_AND_TIME) 1 Date/time in ISP format Year Month Day hours Minutes Seconds 1/10 s 1/100 s 1/1000 s Weekday Time stamp in ISP format Complete time by ISP method (time since 1.1.1900; 00:00 h). The 4 bytes for seconds allows the time which has passed since 1.1.1900; 0:00 h to be expressed in seconds. BYTE 0 Seconds (4 Bytes) 3 4 Second fragments (4 Bytes) 7 The time stamps provided by IM were passed on unchanged by the driver in ISP format. In cyclic operation of the driver the pseudo ALARM_T blocks and the process control system message block ALARM_8P are only called when the signal states have changed. This reduces unnecessary runtimes. Operator control and monitoring The block does not have a faceplate (display block). 2-30 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.7.1 Connections of IM_DRV The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O EV_ID Message ID for ALARM_8P DWORD 0 I EV_ID_xx Message ID for ALARM_T_xx (xx = 00 - 16) DWORD 0 I LADDR Logical Address IM WORD 0 I M_ACK_xx Message acknowledge (xx = 00 - 16) x WORD 0 I Q_ERR_xx Message failure (xx = 00 - 16) BOOL 0 O QBPARF 1: Param. failure block BOOL 0 O QERR 1: Block processing error (inverted value of ENO) BOOL 1 O QPARF 1: Param. failure module BOOL 0 O QPERAF 1: I/O access failure BOOL 0 O QRACKF 1:Rack Failure BOOL 0 O RAC_DIAG Rack Status Information STRUCT S_CH_xxx Slot-/channel-No.(xxx = 000 - 127) WORD 0 I STAT_xx STATUS Output (xx = 00 - 16) WORD 0 O 2.7.2 I/O Message texts and auxiliary process values of the IM_DRV Assignment of message texts and message classes to the signal and special messages An ALARM_8P block is used for the process control system messages in the following table. The geographic address of the IM is entered in Auxiliary Process Value 1 = Slot number of the message, Auxiliary Process Value 2 = Channel number of the message and Auxiliary Process Value 3 = RET_VAL of the SFC 59 (RD_REC) at an I/O access error. ALARM_8P_16 Message No. Output parameter Default message text Message class 1 2 QBPARF Error S_CHxx: Slot=@1%d@ Channel=@2%d@ S QPERAF I/O access error: Ret_Val@3%d@ S 3 QPARF Parameter assignment error S The following special messages which can be contained in the message buffer are generated with ALARM_8P_00 (multiple-instanced call of the pseudo ALARM_T) The format identifier and the 8 time-stamp values are entered in the first auxiliary value Process Control System PCS 7, Driver Blocks A5E00127662-01 2-31 09.10.2001 Signal blocks and diagnostic drivers ALARM_8P_00 Message No. Default message text Message class 1 Start-up data BEGINNING/END S 2 Time-of-day message failure COMING/GOING S 3 Time difference between message and internal clock endangers precision S 4 Time difference between message and internal clock > 1 second POSITIVE/NEGATIVE S 5 STOP of the functionality time stamp COMING/GOING S 6 Message loss at IM (buffer overflow) COMING/GOING S 7 Changeover at redundancy BEGINNING/END S 8 Redundancy_Info_Loss COMING/GOING S ALARM_8P_01 to ALARM_8P_16 (multiple-instanced call of the pseudo ALARM_T) can generate the following signal messages. The format identifier and the 8 time-stamp values are entered in the first auxiliary value ALARM_8P_01 Message No. Default message text Message class 1 TEXT S_CH_000 S 2 TEXT S_CH_001 S 3 TEXT S_CH_002 S 4 TEXT S_CH_003 S 5 TEXT S_CH_004 S 6 TEXT S_CH_005 S 7 TEXT S_CH_006 S 8 TEXT S_CH_007 S ALARM_8P_16 Message No. Default message text Message class 1 TEXT S_CH_120 S 2 TEXT S_CH_121 S 3 TEXT S_CH_122 S 4 TEXT S_CH_123 S 5 TEXT S_CH_124 S 6 TEXT S_CH_125 S 7 TEXT S_CH_126 S 8 TEXT S_CH_127 S ...... 2-32 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.7.3 Interface IM The IM 153-2 / IM151-2 triggers a process interrupt when it wants to send messages to the AS. The user data of the IM are specified in the start information of the process interrupt as follows. Hardware Interrupt Data Element Data type Meaning 0 1 BYTE BYTE Event class and identifiers: B#16#11 = Interrupt is active B#16#41 = Interrupt via interrupt line B#16#42 = Interrupt via interrupt line 2 (only for S7-400) B#16#43 = Interrupt via interrupt line 3 (only for S7-400) B#16#44 = Interrupt via interrupt line 4 (only for S7-400) 2 3 BYTE BYTE Configured priority class: Default values: 16 (OB 40) to 23 (OB 47) OB No. (40 to 47) 4 5 BYTE BYTE 6 WORD Reserved Input module: B#16#54 Output module: B#16#55 Logical basic address of the module which triggers the interrupt 7 BYTE 8 BYTE State of the time stamp (interrupt cause from the view of the time stamp)t Bit 7: State of the synchronization via time message = 0: No synchronization exists = 1: Synchronization exists Bit 6: (only 1 ms) State of the synchronization via optical fiber synchronization signal = 0: No optical fiber signal exists = 1: Optical fiber signal exists Bit 5: Renewed starting of the time stamp = 0: No renewed starting = 1: Renewed starting just started Bit 4: REDUNDANCY: Redundancy operation active/not active = 0: No redundant operation (no redundant plant or single operating mode or passive IM not yet ready) = 1: Redundant operation running (station in data exchange between active <-> passive IM) Bit 3: REDUNDANCY: active IM = 0: Right-hand IM active, = 1: Left-hand IM active Bit 2 = 1: Buffer overflow "internal" (messages are lost) Bit 1: = 1: Buffer overflow "external" (warning: message loss will occur soon) Bit 0: = 1: Message buffer is ready for fetching on the IM Record number if a record (message buffer) is to be fetched 9 10 BYTE BYTE Number of messages contained in the record n: 1 - 20 Reserved 11 DATE_AND _TIME Date and time at which the OB was requested Process Control System PCS 7, Driver Blocks A5E00127662-01 2-33 09.10.2001 Signal blocks and diagnostic drivers The IM_DRV only evaluates Bit 5 in Byte 7 (status of the time stamp function). If the bit = 1, all the process interrupts which have been received before but not processed are rejected. The bit is only set by the IM in the first process alarm after renewed starting. Examples for renewed starting: * REDUNDANCY: Changeover state active <-> passive IM * Restarting of the time stamp function after a total failure Record (message buffer) An IM153-2 has 15 records (message buffers). Access to a record is specified by the record number supplied in the process interrupt data. Structure of a record (message buffer) in the IM Date Number of bytes Remarks Message1 12 Signal or special message . . Message20 . . . . 12 Signal or special message A maximum of 20 signal or special messages can be stored in a message buffer. Structure of a special message from IM Element Meaning Data type Remarks 1 Slot number of the header module BYTE Fixed = 2 2 Identifier of the BYTE special message 01h: Start-up data (a) 02h: Time message failure Subsequent signal messages may (b) have a precision worse than 10ms 03h: Synchronization signal failure: Subsequent signal (b) messages may have a precision worse than 1ms 04h: Time difference between message and internal clock > 1 (d) second 05h: STOP of the functionality time stamp (b) 06h: Buffer overflow: Subsequent signal messages are lost (b) until the buffer is free again 2-34 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Element Meaning 3 Data type Characteristic of BYTE special message Remarks For further specification of the event 01h: BEGINNING 00h: END (a) 01h: COMING 00h: GOING (b) (c) or 01h: POSITIVE 00h: NEGATIVE (d) positive: Internal clock lost and was reset negative: Internal clock gained and was reset: or 4 Reserved BYTE Not used at present 5 Time of the signal change ISP time (8 BYTES) Complete time by ISP method (time since 1.1.1900; 00:00 h) Structure of a signal message from IM Element Meaning Data type Remarks 1 Slot number of the module BYTE In connection with the channel number for address referencing of the digital signal. Range of values: 0, 1, 2, 3 Not assigned 4 ... 11 Slot number of the DI module 12 ... 255 Not assigned 2 Channel number of the module BYTE In connection with the slot number for address referencing of the digital signal. Range of values: 0, 1, ... 15 Channel number of the DI module 16 ... 255 Not assigned 3 Signal state BYTE Bit 7 = 1: = 0: Bit 6 ... Bit 0: 4 Reserve BYTE Not used at present 5 Time of the signal change ISP time (8 BYTE) Complete time by ISP method (time since 1.1.1900; 00:00 h) Process Control System PCS 7, Driver Blocks A5E00127662-01 Signal coming Signal going Not used 2-35 09.10.2001 Signal blocks and diagnostic drivers 2.8 2.8.1 MOD_1: Diagnostic driver for S7-300/400 SM modules which cannot be diagnosed with 16 channels MOD_1: Monitoring of S7-300/400 SM modules which cannot be diagnosed with 16 channels maximum Object name (Type + Number) FB 91 Area of Application The block monitors S7-300/400 SM modules with 16 channels maximum which cannot be diagnosed (no mixed modules). Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: 2-36 * The MOD_1 block is installed behind the RACK block in the OBs mentioned above of the respective runtime group of the rack (station). * Configuration of - The MODE_xx inputs (mode of the channels xx of the module). - The logical basic address of the LADDR module. Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers * Interconnection of - The OUT structures CPU_DIAG of the OB_BEGIN block and RAC_DIAG of the RACK block with the INOUT structures of the same name of the MOD_1. - The EN input with the output of an AND block. Its inputs are interconnected with the outputs EN_SUBx (x = Number of the DP Master system) of the OB_BEGIN block, EN_Rxxx (xxx = Rack/station number) of the SUBNET block and EN_Mxx (xx = Module number) of the RACK block. Function and Operating Principle The block analyzes all the events which affect a module and its channels acyclically. It forms the MODE and value status (quality code) for the signal processing blocks channel-specifically. Events are signaled with ALARM_8P. The block is enabled for running by the higher-level RACK block. The event to be evaluated is entered in the start information (CPU_DIAG) of the OB_DIAG block. Each signal channel of the module has an input (MODE_xx). Here the configurations carried out with HW Config are signaled to the module channels. MODE_xx is read into the low word of the output OMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the channel is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "invalid value due to higher-level error" (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O access error (OB70) (if not switched, output parameter QRACKF = TRUE) * Rack failure (OB86) (output parameter QRACKF = TRUE) The above events are evaluated by the RACK block. The following ones by the MOD block: * I/O access error (OB85) (output parameter QPERAF = TRUE) * Module withdrawn (OB83) (output parameter QMODF = TRUE) The events "Module withdrawn" and "I/O access error" are signaled to the OSs by means of ALARM_8P. In the case of a diagnostic interrupt a difference is made between module and channel faults, whereby a message number is assigned to each channel. During starting up the system checks whether the module is available (plugged). The module state information read here is available in the form of service output parameters (MOD_INF). For detailed information on the faults: Please refer to the manual "System Software for S7-300/400 - System and Standard Functions". Process Control System PCS 7, Driver Blocks A5E00127662-01 2-37 09.10.2001 Signal blocks and diagnostic drivers Redundancy Redundancy monitoring of the DP Master systems on an H system is carried out in the higher-level RACK block. MODE setting The inputs MODE_xx are available for a maximum of 16 signal channels. The initial value is "Zero" (no signal). Depending on the signal channel xx you have to set the type and, if appropriate, the coding of the measuring range of an analog module at the MODE_xx input. Refer to MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Addressing Refer to Addressing In the case of HART modules which access the process image in reading and writing mode configuration is carried out as for input modules. It is generally not permissible to specify different input and output ranges. Example: SM332 AO 2x0/4..20mA HART 332-5TB00-0AB0: Address input range HW Config Address output range HW Config LADDR (decimal / hex) 544 544 544 / 16#0220 Error handling No plausibility checks are carried out with reference to the input parameters. Also refer to: Error information of the output MSG_STAT parameter Service information In order to analyze faults you can read the module state information, which is entered during starting up, via the structured output parameter MOD_INF (refer to the reference manual "System software for S7-300/400 - System and standard functions", system state list, module state information). 2-38 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Start-up characteristics After a restart or an initial start the system checks whether the module is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. Message characteristics MOD_1 signals module faults by means of ALARM_8P. The inputs DELAY1 and DELAY2 are used to delay signaling of the I/O access error. DELAY1 is used to specify the time in seconds which the block waits after an I/O access error (OB85) for a higher-level error (rack failure or withdrawn/plugged), before it outputs the message. The message is turned off only when no higher-level fault is detected after the set time expires. DELAY2 determines the number of seconds which the block waits until it signals the I/O access error still existing after a higher-level error has passed. Both values have a default value of 2 seconds. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate (Display block). Note: Under "Connections of ..." the variables are marked (column OC&M "+") which are transferred to the OS, if the option "Can be operator controlled and monitored" is set in the object properties of the block in CFC. Default: Option not set. 2.8.2 Connections of MOD_1 / MOD_2 The connections of the blocks MOD_1and MOD_2 are identical with the exception of the number of the MODE_xx and OMODE_xx. The number of channels to be monitored determines the number of the respective input and outputs (xx). The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O ACC_MODE 1=Accept MODE Settings BOOL 0 I/O CPU_DIAG System Structure STRUCT DELAY1 Alarm Delay 1 (s) INT 2 I DELAY2 Alarm Delay 2 (s) INT 2 I EN_MSG 1=Enable Message BOOL 1 I EV_ID Message ID DWORD 0 I LADDR Logical Address of Module INT 0 I Process Control System PCS 7, Driver Blocks A5E00127662-01 OC&M I/O 2-39 09.10.2001 Signal blocks and diagnostic drivers Connection (parameter) Meaning Data type MOD_INF System Structure:Module Information STRUCT MODE_xx Mode Channel xx WORD 0 I MSG_ACK Message Acknowledged WORD 0 O MSGSTAT Message Failure WORD 0 O OMODE_xx Mode Channel xx DWORD 0 O QERR 1=Program Error BOOL QMODF 1=Module Withdrawn/Out of Order BOOL 0 O QPERAF 1=Module I/O Access Failure BOOL 0 O QRACKF 1=Rack/Station Failure BOOL 0 O RAC_DIAG Rack diagnostics (System Structure) STRUCT RACK_NO Rack Number BYTE 0 I SLOT_NO Slot Number BYTE 0 I SUBN_TYP 1=External DP interface BOOL 0 I SUBN1_ID ID of Primary DP master system BYTE 255 I SUBN2_ID ID of Redundant DP master system BYTE 255 I 2.8.3 Initial I/O OC&M O + O + I/O Message texts and auxiliary process values of MOD_1 / MOD_2 Assignment of message texts and classes to the block parameters of MOD_1 / MOD_2 Message block ALARM_8P Message number EV_ID 1 Block Default message text parameter Message class Module @1%d@/@2%d@/@3%d@: Withdrawn S 2 QPERAF Module @1%d@/@2%d@/@3%d@: Access error S 3 QMODF Module @1%d@/@2%d@/@3%d@: S @4W%t#MOD_n_TXT@ (n = 1 or 2) 2-40 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Assignment of the auxiliary process values for the block parameters of MOD_1 / MOD_2 Message block ALARM_8P EV_ID Auxiliary process value Block parameter Meaning 1 MOD_INF.SUBN_ID Number DP Master system (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 Text number from MOD_n_TXT (n =1or 2) (Message 1) The event class/event number, the corresponding message texts and their text numbers of the text library MOD_n_TXT are listed in the text library for signal modules 2.9 2.9.1 MOD_2: Diagnostic driver for S7-300/400 SM modules which cannot be diagnosed with 32 channels MOD_2: Monitoring of S7-300/400 SM modules which cannot be diagnosed with 32 channels Object name (Type + Number) FB 92 Area of Application The block monitors S7-300/400 SM modules with 32 channels maximum which cannot be diagnosed (no mixed modules). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-41 09.10.2001 Signal blocks and diagnostic drivers Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MOD_2 block is installed behind the RACK block in the OBs mentioned above of the respective runtime group of the rack (station). * Configuration of * - The MODE_xx inputs (mode of the channels xx of the module) - The logical basic address of the LADDR module. Interconnection of - The OUT structures CPU_DIAG of the OB_BEGIN block and RAC_DIAG of the RACK block with the INOUT structures of the same name of the MOD_2. - The EN input with the output of an AND block. Its inputs are interconnected with the outputs EN_SUBx (x = Number of the DP Master system) of the OB_BEGIN block, EN_Rxxx (xxx = Rack/station number) of the SUBNET block and EN_Mxx (xx = Module number) of the RACK block. Function and Operating principle The block analyzes all the events which affect a module and its channels acyclically. It forms the MODE and value status (quality code) for the signal processing blocks channel-specifically. Events are signaled with ALARM_8P. The block is enabled for running by the higher-level RACK block. The event to be evaluated is entered in the start information (CPU_DIAG) of the OB_DIAG block. Each signal channel of the module has an input (MODE_xx). Here the configurations carried out with HW Config are signaled to the module channels. MODE_xx is read into the low word of the output OMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value 2-42 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers status of the channel is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "invalid value due to higher-level error" (OMODE_xx = 16#40xxxxxx): * * * CPU redundancy loss (OB72) I/O access error (OB70) Rack failure (OB86) (if not switched, output parameter QRACKF = TRUE) (if not switched, output parameter QRACKF = TRUE) (output parameter QRACKF = TRUE) The above events are evaluated by the RACK block. The following ones by the MOD block: * I/O access error (OB85) (output parameter QPERAF = TRUE) * Module withdrawn (OB83) (output parameter QMODF = TRUE) The events "Module withdrawn" and "I/O access error" are signaled to the OSs by means of ALARM_8P. In the case of a diagnostic interrupt a difference is made between module and channel faults, whereby a message number is assigned to each channel. During starting up the system checks whether the module is available (plugged). The module state information read here is available in the form of service output parameters (MOD_INF). For detailed information on the faults: Please refer to the manual "System Software for S7-300/400 - System and Standard Functions". Redundancy Monitoring of the redundancy of the DP Master systems at an H system is carried out in the higher-level RACK block. MODE setting The inputs MODE_xx are available for a maximum of 32 signal channels. The initial value is "Zero" (no signal). Depending on the signal channel xx you have to set the type and, if appropriate, the coding of the measuring range of an analog module at the MODE_xx input. Refer to MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-43 09.10.2001 Signal blocks and diagnostic drivers OMODE structure Refer to OMODE Addressing Refer to Addressing In the case of HART modules which access the process image in reading and writing mode configuration is carried out as for input modules. It is generally not permissible to specify different input and output ranges. Example: SM332 AO 2x0/4..20mA HART 332-5TB00-0AB0: Address input range HW Config Address output range HW Config LADDR (decimal / hex) 544 544 544 / 16#0220 Error handling No plausibility checks are carried out with reference to the input parameters. Also refer to: Error information of the output MSG_STAT parameter Service information In order to analyze faults you can read the module state information, which is entered during starting up, via the structured output parameter MOD_INF (refer to the reference manual "System software for S7-300/400 - System and standard functions", system state list, module state information). Start-up characteristics After a restart or an initial start the system checks whether the module is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. 2-44 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Message characteristics MOD_2 signals module faults by means of ALARM_8P. The inputs DELAY1 and DELAY2 are used to delay signaling of the I/O access error. DELAY1 is used to specify the time in seconds which the block waits after an I/O access error (OB85) for a higher-level error (rack failure or withdrawn/plugged), before it outputs the message. DELAY2 determines the number of seconds which the block waits until it signals the I/O access error still existing after a higher-level error has passed. Both values have a default value of 2 seconds. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate (display block). Note Under "Connections of ..." the variables are marked (column OC&M "+") which are transferred to the OS, if the option "Can be operator controlled and monitored" is set in the object properties of the block in CFC. Default: Option not set. 2.10 MOD_D1: Diagnostic driver for S7-300/400 SM modules which can be diagnosed with 16 channels 2.10.1 MOD_D1: Monitoring of S7-300/400 SM modules which can be diagnosed with 16 channels maximum Object name (Type + Number) FB 93 Area of Application The block monitors S7-300/400 SM modules with 16 channels maximum which can be diagnosed (no mixed modules). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-45 09.10.2001 Signal blocks and diagnostic drivers Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MOD_D1 block is installed behind the RACK block in the OBs mentioned above of the respective runtime group of the rack (station). * Configuration of * - The MODE_xx inputs (mode of the channels xx of the module), SUBN1_ID, SUBN2_ID and SUBN_TYP. - The logical basic address LADDR of the module. Interconnection of - The OUT structures CPU_DIAG of the OB_BEGIN block and RAC_DIAG of the RACK block with the INOUT structures of the same name of the MOD_D1. - The EN input with the output of an AND block. Its inputs are interconnected with the outputs EN_SUBx (x = Number of the DP Master system) of the OB_BEGIN block, EN_Rxxx (xxx = Rack/station number) of the SUBNET block and EN_Mxx (xx = Module number) of the RACK block. Function and Operating Principle The block analyzes all the events which affect a module and its channels acyclically. It forms the MODE and value status (quality code) for the signal processing blocks channel-specifically. The events are signaled with ALARM_8P. The MOD_D1 block is enabled for running by the higher-level RACK block. The event to be evaluated is entered in the start and diagnostic information (CPU_DIAG) of the CPU block. Each signal channel of the module has an input (MODE_xx). Here the configurations carried out with HW Config are signaled to the module channels. MODE_xx is read into the low word of the outputOMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the channel is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. 2-46 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers The following events lead to a value status "invalid value due to higher-level error" (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O redundancy error (OB70) (if not switched, output parameter QRACKF = TRUE) * Rack failure (OB86) (output parameter QRACKF = TRUE) The above events are evaluated by the RACK block. The following ones by the MOD block: * I/O access error (OB85) (output parameter QPERAF = TRUE) * Module withdrawn (OB83) (output parameter QMODF = TRUE) * Diagnostic interrupt (OB82) One differentiates between module faults and channels faults Module faults are the following events (output parameter QMODF = TRUE): * External auxiliary voltage lacking * Front connector missing * Module not configured * Incorrect parameters in the module * Module missing / incorrect * Communication fault CPU module * Time monitoring triggered (watchdog) * Module-internal supply voltage failed * Rack failure * Processor failure * EPROM fault * RAM fault * ADC/DAC fault * Fuse tripped Process Control System PCS 7, Driver Blocks A5E00127662-01 2-47 09.10.2001 Signal blocks and diagnostic drivers Channel faults are the following events (value status "invalid value", OMODE_xx = 16#00xxxx): * Configuration and parameterization errors * Common-Mode error, only analog input/output * P short-circuit * M short circuit * Output transistor has a break * Wire breakage * Reference channel error (only analog input) * Measuring range underflow (only analog input) * Measuring range overflow (only analog input) * Load voltage lacking (only analog and digital output) * Sensor supply lacking (only digital output) * Fuse tripped (only digital output) * Ground fault (only digital input/output) * Overtemperature (only digital output) The events "Module withdrawn", "I/O access error" and "Diagnostic interrupt" are signaled to WinCC by means of ALARM_8P. In the case of a diagnostic interrupt a difference is made between module and channel faults, whereby a message number is assigned to each channel. Only one event each per channel can be signaled as coming/going. As long as an event of a channel is active as coming, further events of the same channel are lost. During starting up the system checks whether the module is available (plugged). The module state information read here is available in the form of service output parameters (MOD_INF). The detailed information on the faults (refer to the reference manual "System software for S7-300/400 - System- and standard functions", diagnostic data, Byte0 to Byte8, structure of the channel-specific diagnostic data) is entered in the output parameter DIAG_INF on the data type STRUCT. Note Even if you operate a HART module in the HART operating MODE MODE=16#070C, possible HART protocol errors and re-configurations are masked by the MOD_D1 driver block and are not signaled as channel errors. Redundancy Monitoring of the redundancy of the DP Master systems at an H system is carried out in the higher-level RACK block. 2-48 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers MODE setting The inputs MODE_xx are available for a maximum of 16 signal channels. The initial value is "Zero" (no signal). Depending on the signal channel xx you have to set the type and, if appropriate, the coding of the measuring range of an analog module at the MODE_xx input. Refer to MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Addressing Refer to Addressing In the case of HART modules which access the process image in reading and writing mode configuration is carried out as for input modules. It is generally not permissible to specify different input and output ranges. Example: SM332 AO 2x0/4..20mA HART 332-5TB00-0AB0: Address input range HW Config Address output range HW Config LADDR (decimal / hex) 544 544 544 / 16#0220 Error handling No plausibility checks are carried out with reference to the inputs . Also refer to: Error information of the output MSG_STAT parameter Service information In order to analyze faults you can read the module state information, which is entered during starting up, via the structured output parameter MOD_INF (refer to the reference manual "System software for S7-300/400 - System and standard functions", system state list, module state information). In addition detailed module diagnostic information is contained in the output parameters MODDIAG0 to MODDIAG8 after a diagnostic interrupt (refer to the reference manual "System software for S7-300/400 - System- and standard Process Control System PCS 7, Driver Blocks A5E00127662-01 2-49 09.10.2001 Signal blocks and diagnostic drivers functions", diagnostic data, Byte0 to Byte8). The output parameters CHDIAG00 to CHDIAG15 contain detailed channel state information (refer to the reference manual "System software for S7-300/400 - System- and standard functions", structure of the channel-specific diagnostic data). The diagnostic information is reset after a going diagnostic interrupt (there are no channel errors or module faults). Start-up characteristics After a restart or an initial start the system checks whether the module is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Overload behavior The MOD_D1 block counts the OB82 calls. The counter is reset in the OB1. If more than two OB82 events occur successively before the cycle checkpoint (OB1) is reached, these are rejected and a message "Failure OB82 DP Master:x Rack:y Slot: z" is emitted. Time response Does not exist. Message characteristics MOD_D1 signals module faults by means of ALARM_8P_1. In addition the ALARM_8P_2 and ALARM_8P_3 specified for channel faults are called up. The inputs DELAY1 and DELAY2 are used to delay signaling of the I/O access error. DELAY1 is used to specify the time in seconds which the block waits after an I/O access error (OB85) for a higher-level erroe (rack failure or withdrawn/plugged), before it outputs the message. The message is turned off only when no higherlevel error is detected after the set time expires. DELAY2 determines the number of seconds which the block waits until it signals the I/O access error still existing after a higher-level error has passed. Both values have a default value of 2 seconds. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate (Display block). Note In "Connection of MOD_1 / MOD_2" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 2-50 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.10.2 Connections of MOD_D1 / MOD_D2 The connections of the blocks MOD_D1and MOD_D2 are identical with the exception of the number of the MODE_xx and OMODE_xx. The number of channels to be monitored determines the number of the respective input and outputs (xx). The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial ACC_MODE CPU_DIAG 1=Accept MODE Settings BOOL 0 CPU diagnostics (System structure) STRUCT DELAY1 Alarm Delay 1 (s) INT 2 2 I/O I/O I/O I DELAY2 Alarm Delay 2 (s) INT DIAG_INF Diagnostic Information STRUCT EN_MSG 1=Enable Message BOOL 1 I EV_IDx Message ID DWORD 0 I LADDR Logical Address of Module INT 0 I MOD_INF Module Parameter STRUCT MODE_xx Mode Channel xx WORD 0 I MSG_ACKx Message Acknowledged x WORD 0 O I O O MSGSTATx Message Failure x WORD 0 O OMODE_xx Mode Channel xx DWORD 0 O QERR 1=Program Error BOOL 0 O QMODF 1=Module Withdrawn/Out of Order BOOL 0 O QPERAF 1=Module I/O Access Failure BOOL 0 O QRACKF 1=Rack Failure BOOL 0 RAC_DIAG Rack diagnostic STRUCT RACK_NO Rack Number BYTE 0 I SLOT_NO Slot Number BYTE 0 I SUBN_TYP 1=External DP interface BOOL 0 SUBN1_ID ID of Primary DP master system BYTE 255 I SUBN2_ID ID of Redundant DP master system BYTE 255 I Process Control System PCS 7, Driver Blocks A5E00127662-01 OC&M + + O I/O 2-51 09.10.2001 Signal blocks and diagnostic drivers 2.10.3 Message texts and auxiliary process values of MOD_D1 Assignment of message texts and classes to the block parameters of MOD_D1 Message block ALARM_8P EV_ID1 EV_ID2 Message number Block parameter Default message text Message class 1 QMODF Module @1%d@/@2%d@/@3%d@: withdrawn S 2 QPERAF Module @1%d@/@2%d@/@3%d@: Access error S 3 QMODF Module @1%d@/@2%d@/@3%d@: @5W%t#MOD_D1_TXT@ S 4 Module @1%d@/@2%d@/@3%d@: Multi.Diagnose OB82 lock S 5 BG @1%d@/@2%d@/@3%d@: @4W%t#MOD_D1_TXT@ S Module @1%d@/@2%d@/@3%d@: Channel 00 @4W%t#MOD_D1_TXT@ S ... ... ... ... 1 - ... ... EV_ID3 8 - Module @1%d@/@2%d@/@3%d@: Channel 07 @10W%t#MOD_D1_TXT@ S 1 - Module @1%d@/@2%d@/@3%d@: Channel 08 @4W%t#MOD_D1_TXT@ S ... ... ... ... Module @1%d@/@2%d@/@3%d@: Channel 15 @10W%t#MOD_D1_TXT@ S ... ... 8 - The event class/event number, the corresponding message texts and their text numbers of the text library MOD_D1_TXT are listed in the text library for signal modules Note Detailed channel errors are only registered for modules with channels of channel type16#61, 16#63, 16#70, 16#71, 16#72, 16#73. Only the first 8 bits are registered for modules whose diagnostic bits per channel exceed 8 bits. Non-detailed messages have the following structure (Example): BG 1/2/10: Error Channel15 2-52 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Assignment of the auxiliary process values for the block parameters of MOD_D1 Message block ALARM_8P EV_ID1 Auxiliary process value Block parameter Meaning 1 MOD_INF.SUBN_ID Number DP Master system (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 EV_ID2 Text number (Message 1-3) from MOD_D1_TXT 1 MOD_INF.SUBN_ID Number DP Master system (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 EV_ID3 Text number (Message 1-8) from MOD_D1_TXT 1 MOD_INF.SUBN_ID 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 Number DP Master system (byte) Text number (Message 1-8) from MOD_D1_TXT 2.11 MOD_D2: Diagnostic driver for S7-300/400 SM modules which can be diagnosed with 32 channels 2.11.1 MOD_D2: Monitoring of S7-300/400 SM modules which can be diagnosed with 32 channels Object name (Type + Number) FB 94 Area of Application The block monitors S7-300/400 SM modules with 32 channels maximum which can be diagnosed (no mixed modules). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-53 09.10.2001 Signal blocks and diagnostic drivers Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB83 Withdrawn/plugged interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MOD_D2 block is installed behind the RACK block in the OBs mentioned above of the respective runtime group of the rack (station). * Configuration of * - The inputs MODE_xx (Mode of channels xx of the module) SUBN1_ID, SUBN2_ID and SUBN_TYP - The logical address LADDR of the module. Interconnection of - The OUT structures CPU_DIAG of the OB_BEGIN block and RAC_DIAG of the RACK block with the INOUT structures of the same name of the MOD_D2. - The EN input with the output of an AND block, of which the inputs are interconnected with the outputs EN_SUBx (x = ID of the DP master system) of the OB_BEGIN block, EN_Rxxx (xxx = Rack/Station ID) of the subnet block and EN_Mxx (xx = Module ID) of the rack block. Function and Operating Principle The block analyzes all the events which affect a module and its channels acyclically. It forms the MODE and value status (quality code) for the signal processing blocks channel-specifically. The events are signaled with ALARM_8P. The signaling function can be switched off. The block is enabled for running by the higher-level RACK block. The event to be evaluated is entered in the start and diagnostic information (CPU_DIAG) of the CPU block. Each signal channel of the module has an input (MODE_xx). Here the configurations carried out with HW Config are signaled to the module channels. MODE_xx is read into the low word of the output OMODE_xx. This is only carried 2-54 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the channel is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "invalid value due to higher-level error" (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O redundancy error (OB70) (if not switched, output parameter QRACKF = TRUE) The above events are evaluated by the RACK block. The following ones by the MOD block: * Rack failure (OB86) (output parameter QRACKF = TRUE) * I/O access error (OB85) (output parameter QPERAF = TRUE) * Module withdrawn (OB83) (output parameter QMODF = TRUE) * Diagnostic interrupt (OB82) One differentiates between module faults and channels faults Module faults are the following events (output parameter QMODF = TRUE): * External auxiliary voltage lacking * Front connector missing * Module not configured * Incorrect parameters in the module * Module missing / incorrect * Communication fault CPU module * Time monitoring triggered (watchdog) * Module-internal supply voltage failed * Rack failure * Processor failure * EPROM fault * RAM fault * ADC/DAC fault * Fuse tripped Process Control System PCS 7, Driver Blocks A5E00127662-01 2-55 09.10.2001 Signal blocks and diagnostic drivers Channel faults are the following events (value status "invalid value", OMODE_xx = 16#00xxxx): * Configuration and parameterization errors * Common-Mode error, only analog input/output * P short-circuit * M short circuit * Output transistor has a break * Wire breakage * Reference channel error (only analog input) * Measuring range underflow (only analog input) * Measuring range overflow (only analog input) * Load voltage lacking (only analog and digital output) * Sensor supply lacking (only digital output) * Fuse tripped (only digital output) * Ground fault (only digital input/output) * Overtemperature (only digital output) The events "Module withdrawn", "I/O access error" and "Diagnostic interrupt" are signaled to WinCC by means of ALARM_8P. In the case of a diagnostic interrupt a difference is made between module and channel faults, whereby a message number is assigned to each channel. Only one event each per channel can be signaled as coming/going. As long as an event of a channel is active as coming, further events of the same channel are lost. During starting up the system checks whether the module is available (plugged). The module state information read here is available in the form of service output parameters (MOD_INF). The detailed information on the faults (refer to the reference manual "System software for S7-300/400 - System- and standard functions", diagnostic data, Byte 0 to Byte 8, structure of the channel-specific diagnostic data) is entered in the output parameter DIAG_INF on the data type STRUCT. Redundancy The block supports the line redundancy of the CPU 417H in the case of decentralized I/Os To this purpose the inputs SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) are to be configured with the numbers of the redundant lines. If there is no line redundancy, the remaining input must have the value 16#FF (default) assigned. 2-56 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers MODE setting The inputs MODE_xx are available for a maximum of 32 signal channels. The initial value is zero (no signal). Depending on the signal channel xx you have to set the type and, if appropriate, the coding of the measuring range of an analog module at the MODE_xx input. Refer to MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Addressing Refer to Addressing Error handling No plausibility checks are carried out with reference to the input parameters. Also refer to: Error information of the output MSG_STAT parameter Service information In order to analyze faults you can read the module state information, which is entered during starting up, via the structured output parameter MOD_INF (refer to the reference manual "System software for S7-300/400 - System and standard functions", system state list, module state information). In addition detailed module diagnostic information is contained in the output parameters MODDIAG0 to MODDIAG10 after a diagnostic interrupt (refer to the reference manual "System software for S7-300/400 - System- and standard functions", diagnostic data, Byte 0 to Byte 10). The output parameters CHDIAG00 to CHDIAG31 contain detailed channel state information (refer to the reference manual "System software for S7-300/400 - System- and standard functions", structure of the channel-specific diagnostic data). The diagnostic information is reset after a going diagnostic interrupt (there are no channel errors or module faults). Process Control System PCS 7, Driver Blocks A5E00127662-01 2-57 09.10.2001 Signal blocks and diagnostic drivers Start-up characteristics After a restart or an initial start the system checks whether the module is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. Message characteristics MOD_D2 signals module faults by means of ALARM_8P_1. In addition the ALARM_8P_2, ALARM_8P_3, ALARM_8P_4 and ALARM_8P_5 specified for channel faults are called up. The inputs DELAY1 and DELAY2 are used to delay signaling of the I/O access error. DELAY1 is used to specify the time in seconds which the block waits after an I/O access error (OB85) for a higher-level error (rack failure or withdrawn/plugged), before it outputs the message. The message is turned off only when no higher-level error is detected after the set time expires. DELAY2 determines the number of seconds which the block waits until it signals the I/O access error still existing after a higher-level error has passed. Both values have a default value of 2 seconds. The message can be turned off with EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate. Note In "Connection of MOD_1 / MOD_2" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 2-58 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.11.2 Message texts and auxiliary process values of MOD_D2 Assignment of message texts and classes to the block parameters of MOD_D2 Message Message block number ALARM_8P EV_ID1 EV_ID2 Block parameter Default message text Message class 1 QMODF Module @1%d@/@2%d@/@3%d@: withdrawn S 2 QPERAF Module @1%d@/@2%d@/@3%d@: Access error S 3 QMODF Module @1%d@/@2%d@/@3%d@: @5W%t#MOD_D2_TXT@ S 4 Module @1%d@/@2%d@/@3%d@: Multi.Diagnose OB82 lock S 5 BG @1%d@/@2%d@/@3%d@: @4W%t#MOD_D2_TXT@ S 6 - S 7 - S 8 - S 1 - ... EV_ID3 8 - Module @1%d@/@2%d@/@3%d@: Channel 07 @4W%t#MOD_D2_TXT@ S 1 - Module @1%d@/@2%d@/@3%d@: Channel 08 @4W%t#MOD_D2_TXT@ S 8 - Module @1%d@/@2%d@/@3%d@: Channel 15 @4W%t#MOD_D2_TXT@ S 1 - Module @1%d@/@2%d@/@3%d@: Channel 16 @4W%t#MOD_D2_TXT@ S ... ... EV_ID5 S ... ... EV_ID4 Module @1%d@/@2%d@/@3%d@: Channel 00 @4W%t#MOD_D2_TXT@ ... 8 - Module @1%d@/@2%d@/@3%d@: Channel 23 @4W%t#MOD_D2_TXT@ S 1 - Module @1%d@/@2%d@/@3%d@: Channel 24 @4W%t#MOD_D2_TXT@ S ... 8 ... - Module @1%d@/@2%d@/@3%d@: Channel 31 @4W%t#MOD_D2_TXT@ S The event class/event number, the corresponding message texts and their text numbers of the text library MOD_D2_TXT are listed in the text library for signal modules Process Control System PCS 7, Driver Blocks A5E00127662-01 2-59 09.10.2001 Signal blocks and diagnostic drivers Assignment of the auxiliary process values for the block parameters of MOD_D2 Message block ALARM_8P EV_ID1 EV_ID2 EV_ID3 EV_ID4 EV_ID5 2-60 Auxiliary process value Block parameter Meaning 1 MOD_INF.SUBN_ID DP master system ID (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 - Text number (Message 1 - 3) from MOD_D2_TXT 1 MOD_INF.SUBN_ID DP master system ID (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 - Text number (Message 1 - 8) from MOD_D2_TXT 1 MOD_INF.SUBN_ID DP master system ID (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 - Text number (Message 1 - 8) from MOD_D2_TXT 1 MOD_INF.SUBN_ID DP master system ID (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 - Text number (Message 1 - 8) from MOD_D2_TXT 1 MOD_INF.SUBN_ID DP master system ID (byte) 2 MOD_INF.RACK_NO Rack / Station number (byte) 3 MOD_INF.SLOT_NO Slot number (byte) 4 - Text number (Message 1 - 8) from MOD_D2_TXT Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.12 CH_AI: Analog value input Object name (Type + Number) FC 275 Area of Application The block is used for signal processing of an analog input value from S7-300/400 SM analog input modules. Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32). Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block. Function and Operating principle The block cyclically processes all the channel-specific signal functions of an analog input module. The block reads an analog non-linearized value from the (part) process image and adapts it to its physical size or determines a percentage value from it. The MODE input is used to determine in which form the non-linearized value exists and is to be processed. If the high byte of the MODE input parameter = 16#40 (value status = higher-level error), the non-linearized value is handled as invalid. A quality code which can have the following states is generated for the resultant value State Quality code Valid value 16#80 Simulation 16#60 Last valid value 16#44 Substitution value 16#48 Invalid value 16#00 Process Control System PCS 7, Driver Blocks A5E00127662-01 2-61 09.10.2001 Signal blocks and diagnostic drivers Addressing The symbol generated with HW Config (symbol table) for the analog input channel has to be interconnected with the input VALUE. Non-linearized value check Depending on the measured value and the measuring range a nominal range of the analog input module is obtained by converting the analog signal into a digital value (non-linearized value). In addition there is an over- and underrange in which the analog signal can still be converted. There is an overflow or underflow outside these limits. The block indicates whether the non-linearized value lies inside the nominal range of the module. If the value drops below the nominal range, the output parameter value QCHF_LL = TRUE is set. If the value exceeds the nominal range, the output parameter value QCHF_HL = TRUE is set. In case of an overflow or underflow QBAD = TRUE (channel error) is also set. Note In case of a wire breakage at 4 to 20 mA signals the module response is not uniform. Depending on the module either 16#7FFF (overflow) or 16#8000 (underflow) is written as the non-linearized value into the process image. The channel block CH_AI then correspondingly emits either an overflow (QCHF_HL = TRUE) or an underflow (QCHF_LL = TRUE), each together with QBAD = TRUE. Exception: If you have set "Diagnostic interrupt" of the analog input module with HW Config, only QBAD = TRUE is set at a "Channel error" (for example wire break) at a diagnostic interrupt. NAMUR limit check The NAMUR guidelines for analog signal processing define limits for life zero (4 to 20 mA) analog signals which have a channel error: 3.6 mA = Analog signal = 21 mA The above NAMUR limits are set as fixed defaults for limit monitoring. If you want to set other limits, you have to set the inputCH_F_ON = TRUE and set corresponding new limits in mA at the inputs CH_F_HL and CH_F_LL. If the lower or upper active limit is exceeded, QBAD = TRUE is set at a life zero analog signal. Note The selectable limits must lie below the upper limit of the overrange or above the lower limit of the underrange of the module. Values outside the NAMUR range are also possible in as far as the module does not limit the measured values automatically to these. 2-62 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Normal value The non-linearized value is adjusted according to ist physical size by the inputs VLRANGE, VHRANGE and MODE (see also OMODE_xx). The interconnectability of the settings of VLRANGE and VHRANGE with other block parameters are determined by the outputs OVLRANGE and OVHRANGE. The conversion algorithm depends on a linearized input signal. If VLRANGE = 0 and VHRANGE = 100 you get a percentage value. If VHRANGE = VLRANGE is set, you get the the input signal of the analog input module (e.g. mA) according to the MODE setting. If the non-linearized value is already a physical value, please set VLRANGE = 0 and VHRANGE = 1. The Quality Code is set to QUALITY = 16#80. Note In the measuring mode "Thermocouples external or internal comparison", the physiacl size is adjusted to +/- 80 mV in the modules of S7 300. You have to determine the temperature with reference to the conversion tables concerned. The physical equivalence in mV is delivered by the module as non-linearized value, please set VHRANGE and VLRANGE +/- 80 mV here. Simulation With the input parameter SIM_ON = TRUE, the value of the input SIM_V is given with Quality Code QUALITY = 16#60. In simulation operation too, a valid operating mode has to be set in Low Word of the input MODE. Otherwise QBAD = 1 is output. Simulation has highest priority. If the block is in the simulation status, QSIM = TRUE is set. Substitute value With the input parameter SUBS_ON = TRUE, the value of the input SUBS_V is output as value, as long as the non-linearized value is invalid. The Quality Code is set as QUALITY = 16#48 and QBAD = 1. Hold last value With input parameter SUBS_ON = FALSE, the last valid output value (V_LAST) is output, if the non-linearized value is invalid. For V_DELTA > 0, the following applies: ABS (V - V_LAST) > V_DELTA: V = V_LAST1 (next to last valid output value) ABS (V - V_LAST) V_DELTA: V = V_LAST (last valid output value) The Quality Code is set as QUALITY = 16#44 and QBAD = 1. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-63 09.10.2001 Signal blocks and diagnostic drivers Accept value delay After restart or if the Quality Code is changed from "BAD" to "GOOD", the Quality Code and value are not updated until the CNT_LIM cycles have passed. If CNT_LIM = 0 (Default setting), this function is switched off. During the accept value delay, the Quality Code = 16#00 and QBAD = 1. The last value remains during the accept value delay. Error handling No plausibility checks are carried out with reference to the input parameters. In case of invalid operating mode in the low word of the MODE input it is assumed that the non-linearized value is invalid. Start-up characteristics Does not exist. Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2.12.1 Connections of CH_AI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O CH_F_HL High Limit of Input Value (mA) REAL 0 I/O CH_F_LL Low Limit of Input Value (mA) REAL 0 I/O CH_F_ON 1=Limit Failure Active BOOL 0 I/O CNT_LIM Restart Counter Limit INT 0 I/O CNT_RES Restart Counter INT 0 I/O DELTA_ON Last Difference (V - V_LAST) exceeded BOOL 0 I/O LAST_BAD Last QBAD BOOL 0 I/O MODE Quality and Mode DWORD 0 I/O OVHRANGE High Range of Process Value (Copy) REAL 0 O 2-64 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Connection (parameter) Meaning Data type Initial I/O OVLRANGE Low Range of Process Value (Copy) REAL 0 O QBAD 1=Bad Process Value BOOL 0 O QCHF_HL 1 = Overdriven Process Value BOOL 0 O QCHF_LL 1 = Underdriven Process Value BOOL 0 O QSIM 1 = Simulation Active BOOL 0 O QSUBS 1 = Failure Substitution Active BOOL 0 O QUALITY Quality Code of Process Value BYTE 0 O SIM_ON 1 = Activate Simulation BOOL 0 I/O SIM_V Simulation Value REAL 0 I/O SUBS_ON 1 = Enable Failure Substitution BOOL 0 I/O SUBS_V Substitution Value REAL 0 I/O V Process Value REAL 0 O VALUE Process Image Input Value WORD 0 I/O VHRANGE High Range of Process Value REAL 100 I/O VLRANGE Low Range of Process Value REAL 0 I/O V_DELTA Delta (V - V_LAST) Process Value REAL 0 I/O V_LAST Last Valid Process Value REAL 0 I/O V_LAST1 Second-last Valid Process Value REAL 0 I/O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-65 09.10.2001 Signal blocks and diagnostic drivers 2.13 CH_AO: Analog value output Object name (Type + Number) FC 276 Area of Application The block is used for signal processing of an analog output value from S7-300/400 SM analog output. Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32) and the restart OB100. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block. * The CH_AO block is installed after the MOD block assigned to it in the OB100. Note If you do not use the CFC function "Generate Module Driver", you have to ensure that the CH_AO block is installed after the MOD-/PADP block assigned to it in the OB100. Function and Operating principle The block processes all the channel-specific signal functions. The block writes a process value as an analog non-linearized value into the (part) process image. The MODE input is used to determine in which form the nonlinearized value is to be generated. If the high byte of the MODE input = 0 (value status), the non-linearized value continues to be written into the (part) process image - however, a quality code "invalid value" is set. 2-66 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers The quality code can have the following states: State Quality code Valid value 16#80 Open value limited 16#56 Lower value limited 16#55 Simulation 16#60 Invalid value 16#00 Addressing The symbol generated with HW Config (symbol table) for the analog output channel has to be interconnected to the VALUE output . Normal value The parameters ULRANGE and UHRANGE map the process value U onto the non-linearized value VALUE (quantification stages) of the analog output module depending on the MODE. For example in the mode 4..20mA (16#0203) the nonlinearized value for 4mA is output for U = ULRANGE and the non-linearized value for 20mA is output for U = UHRANGE. PHYS_LIM is used to set the limitation of the VALUE non-linearized value. In the default setting (PHYS_LIM = 0) the VALUE output value is limited to the normalizing limits of the module. In accordance with the above example the block calculates the non-linearized value for 20 mA for U > UHRANGE and the nonlinearized value for 4mA for U < ULRANGE Accordingly the quality codes 16#56 (upper value limited) and 16#55 (lower value limited) are applied at the QUALITY output instead of the 16#80 (valid value). In order to output analog values outside the normalization values up to the physical limits of the module, you have to set PHYS_LIM = 1. The output values are not limited until, in the above example, the module limits are exceeded by specifying U = 200 (36mA) or U = -50 (-4mA) at ULRANGE = 0 and UHRANGE = 100. The output values are then limited to the physical limits specified in the data sheets of the modules and the corresponding quality codes are output. The outputs QCHF_HL and QCHF_LL also provide information on whether the output values have been limited. Simulation If the input parameter SIM_ON = TRUE, the value of SIM_U is output with Quality Code (QUALITY) = 16#60. A valid mode must also be set in simulation mode in the low word of the input MODE. Otherwise QBAD = 1 is output. If there is a higherlevel fault, QBAD = FALSE is set. Simulation has the highest priority. If the block is in simulation state, QSIM = TRUE is set. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-67 09.10.2001 Signal blocks and diagnostic drivers I/O fault If the high byte of the input MODE = 0 (value status), the quality code QUALITY = 16#00 is set. The current non-linearized value is always written into the (part) process image. Value limiting You can limit very low or very high process values which lead to an error (QBAD = TRUE) before entry in the (part) process image. If the switch LIMIT_ON = TRUE, the process values (V) are limited: - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Error handling No plausibility checks are carried out with reference to the input parameters. In case of an invalid operating mode in the low word of the MODE input the digitized output value is set to 0 and QUALITY = 16#00 is output. Start-up characteristics The MOD blocks set the LSB in Byte 2 of their output OMODE_xx in the OB100. If the block recognizes this code, it acknowledges it and then reacts as follows: If START_ON is not set, the process value U is processed and is transferred to the process image. Otherwise the non-linearized value corresponding to the START_U process value is written to the process image. Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2-68 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.13.1 Connections of CH_AO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O LL_V Process value if U < V LL REAL 0 I/O LIMIT_ON 1 = Limit control process value BOOL 0 I/O MODE Quality and Mode DWORD 0 I/O PHYS_LIM 1=Enable Physical Module Limits BOOL 0 I/O QBAD 1=Bad Output Value BOOL 0 O QCHF_HL 1 = Process Value High Limit Failure BOOL 0 O QCHF_LL 1 = Process Value Low Limit Failure BOOL 0 O QSIM 1 = Simulation Active BOOL 0 O QUALITY Quality Code of Output Value BYTE 0 O SIM_ON 1 = Activate Simulation BOOL 0 I/O SIM_U Simulation Value REAL 0 I/O START_ON 1=Enable Startup Substitution Value BOOL 0 I/O START_U Startup Substitution Value REAL 0 I/O U Process Value REAL 0 I/O UHRANGE High Range of Process Value REAL 0 I/O ULRANGE Low Range of Process Value REAL 0 I/O V_HL HART high limit value REAL 0 I/O V_LL HART low limit value REAL 0 I/O VALUE Process Image Output Value WORD 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-69 09.10.2001 Signal blocks and diagnostic drivers 2.14 CH_DI: Digital value input Object name (Type + Number) FC 277 Area of Application The block is used for signal processing of a digital input value from S7-300/400 SM digital input modules or a PA field device (PA-Profile 3.0 Discrete Input). Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32). Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block (or of the PADP block). Function and Operating principle The block processes all the channel-specific signal functions. The block reads a digital value of the data type BOOL from the (part) process image. If the high byte of the input parameter MODE = 16#40 (value status = higher-level error), the digital value is treated as invalid. If the input parameter PQC = TRUE, the value status of the digital value is read from the (part) process image. A quality code which can have the following states is generated for the resultant value: 2-70 State Quality code Valid value 16#80 Simulation 16#60 Last valid value 16#44 Substitution value 16#48 Invalid value 16#00 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Addressing The symbol generated with HW Config (symbol table) for the digital input channel has to be interconnected to the VALUE input. If the value status of the digital input channel is also in the (part) process image, you have to interconnect the corresponding symbol with the input VALUE_QC and set the input PQC = TRUE. In the case of PA field devices (PA_ON = TRUE), the symbol generated with HW Config (symbol table) for the digital input channel has to be interconnected to the I_OUT_D input. The CFC function "Generate Module Driver" interconnects the symbol for the Quality Code of the digital input channel automatically to the input QC. Normal value The digital value of the (part) process image is output to the output parameter Q with Quality Code QUALITY = 16#80. Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_I (PA_ON = FALSE) or SIM_OUT (PA_ON = TRUE) is output to the output Q with Quality Code QUALITY = 16#60. Simulation has the highest priority. If there is a higher-level fault, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. Substitution value If the input parameter SUBS_ON = TRUE, the value of the input SUBS_I is output to the output Q with Quality Code QUALITY = 16#48 and QBAD = 1, in as far as the digital value of the (part) process image is invalid. Hold last value If the input parameter SUBS_ON = FALSE, the last valid output parameter is output if the non-linearized value is invalid. The Quality Code is set to QUALITY = 16#44 and QBAD = 1. * PA_ON = TRUE Last valid output value corresponds to V_LAST. * PA_ON = FALSE Last valid output value corresponds to Q_LAST. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Do not exist. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-71 09.10.2001 Signal blocks and diagnostic drivers Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2.14.1 Connections of CH_DI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O MODE Quality and Mode DWORD 0 I/O PQC 1=Use Process Image Quality Bit BOOL 0 I/O Q Process Value BOOL 0 O Q_LAST Last Valid Process Value BOOL 0 I/O QBAD 1=Bad Process Value BOOL 0 I/O QSIM 1 = Simulation Active BOOL 0 O QSUBS 1 = Failure Substitution Active BOOL 0 O QUALITY Quality Code of Process Value BYTE 0 O SIM_I Simulation Value BOOL 0 I/O SIM_ON 1 = Activate Simulation BOOL 0 I/O SUBS_I Substitution Value BOOL 0 I/O SUBS_ON 1 = Enable Failure Substitution BOOL 0 I/O VALUE Input Value BOOL 0 I/O VALUE_QC Process Image Quality Bit BOOL 0 I/O 2-72 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.15 CH_DO: Digital value output Object name (Type + Number) FC 278 Area of Application The block is used for signal processing of a digital output value from S7-300/400 SM digital output modules. Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32) and the restart OB100. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block. * The CH_DO block is installed after the MOD block assigned to it in the OB100. Note If you do not use the CFC function "Generate Module Driver", you have to ensure that the CH_DO block is installed after the MOD-/PADP block assigned to it in the OB100. Function and Operating principle The block processes all the channel-specific signal functions. The block writes a digital value into a (part) process image. If the high byte of the MODE input parameter = 0 (value status), the digital value continues to be written into the (part) process image - however, a quality code "invalid value" is set. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-73 09.10.2001 Signal blocks and diagnostic drivers The quality code can have the following states: State Quality code Valid value 16#80 Simulation 16#60 Invalid value 16#00 Addressing The symbol generated by HW Config in the symbol table for the digital output channel has to be interconnected to the VALUE output. Normal value The digital value I0 is written to the (part) process image and Quality Code (QUALITY) = 16#80 is set. Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_I (PA_ON = FALSE) or SIM_SP (PA_ON = TRUE) is written to the (part) process image and the Quality Code QUALITY = 16#60 is set. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. I/O fault If the high byte of the input MODE = 0 (value status), the quality code QUALITY = 16#00 is set. The current digital value is always written into the (part) process image. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics The MOD blocks set the LSB in Byte 2 of their outputs OMODE_xx in the OB100. If the block recognizes this code, it acknowledges it and then reacts as follows: If START_ON is not set, the Process Value I is written to the process image. Otherwise START_I is used instead of the Process Value I. Time response Does not exist. 2-74 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2.15.1 Connections of CH_DO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O I MODE Process value BOOL 0 I/O Quality and Mode DWORD 0 I/O QBAD 1=Bad Output Value BOOL 0 O QSIM 1=Simulation Active BOOL 0 O QUALITY Quality Code of Output Value BYTE 0 O SIM_I Simulation Value BOOL 0 I/O SIM_ON 1=Activate Simulation BOOL 0 I/O START_I Startup Substitution Value BOOL 0 I/O START_ON 1=Enable Startup Substitution Value BOOL 0 I/O VALUE Process Image Output Value BOOL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-75 09.10.2001 Signal blocks and diagnostic drivers 2.16 CH_U_AI: Analog value input (Universal) Object name (Type + Number) FC 283 Area of application The block is used for signal processing of a analog input value from S7-300/400 SM analog input modules or a PA field device (PA-Profile 3.0 Analog Input). Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The input PA_ON is configured in accordance with the I/O devices used (S7 signal modules (=0) or PA field devices (=1)). * The symbol for the Quality Code of the analog input channel is interconnected to the input QC (at PA devices). * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block (or of the PADP block). Function and Operating principle The block processes all the channel-specific signal functions and/or signals of a PA field device of data type REAL with or without Quality Code cyclically. The block uses the switch position (input PA_ON) to differentiate between a analog non-linearized value and a REAL value of a field device with Quality Code(see Adressing). PA_ON = TRUE As the REAL value of a PA field device is always defined with a status byte (STATUS), PQC = TRUE has to be set. The statusbyte contains information about the measured value and the status of the PROFIBUS PA field device. The quality code QUALITY for the process value is determined from the status of the input MODE and the output STATUS. PA MODE recognizes a higher level error e.g. DP/PA Link failure via the input MODE If the high byte of the input MODE = 16#40 (value status = higher-level 2-76 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers error), the analog value will be handled as invalid. The Quality Code (QUALITY) is set to 16#44 or 16#48. The same is true for a STATUS with status "BAD". Otherwise STATUS and QUALITZ are identical. PA_ON = FALSE The block reads an analog non-linearized value from a (part) process image and adjusts ist physical size accordingly or evaluates a process value. The MODE input determines in which form the non-linearized value appears and to be processed. If the high byte of the MODE input = 16#40 (value status = higher-level error), the non-linearized value is set as invalid. The quality code can have the following states: State Quality code Valid value 16#80 Simulation 16#60 Last valid value 16#44 Substitute value 16#48 Invalid value 16#00 Addressing The symbol generated by HW Config in the symbol table for the analog input channel has to be interconnected to the VALUE input or (with PA_ON = TRUE) OUT (process value) and QC (Quality Code). The CFC function "Generate Module Driver" interconnects the symbol for Quality Code automatically with the QC input. Non-linearized value check Only if PA_ON = FALSE: Depending on the measured value and the measuring range a nominal range of the analog input module is obtained by converting the analog signal into a digital value (non-linearized value). In addition there is an overand underrange in which the analog signal can still be converted. There is an overflow or underflow outside these limits. The block indicates whether the nonlinearized value lies inside the nominal range of the module. If the value drops below the nominal range, the output parameter value QCHF_LL = TRUE is set. If the value exceeds the nominal range, the output parameter value QCHF_HL = TRUE is set. In case of an overflow or underflow QBAD = TRUE (channel error) is also set. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-77 09.10.2001 Signal blocks and diagnostic drivers Note In case of a wire breakage at 4 to 20 mA signals the module response is not uniform. Depending on the module either 16#7FFF (overflow) or 16#8000 (underflow) is written as the non-linearized value into the process image. The channel block CH_U_AI then correspondingly emits either an overflow (QCHF_HL = TRUE) or an underflow (QCHF_LL = TRUE), each together with QBAD = TRUE. Exception: If you have set "Diagnostic interrupt" of the analog input module with HW Config, only QBAD = TRUE is set at a "Channel error" (for example wire break) at a diagnostic interrupt. NAMUR limit check Only if PA_ON = FALSE: The NAMUR guidelines for analog signal processing define limits for life zero (4 to 20 mA) analog signals which have a channel error: 3.6 mA = Analog signal = 21 mA The above NAMUR limits are set as fixed defaults for limit monitoring. If you want to set other limits, you have to set the inputsCH_F_ON = TRUE and set corresponding new limits in mA at the input parameters CH_F_HL and CH_F_LL. If the lower or upper active limit is exceeded, QBAD = TRUE is set at a life zero analog signal. Note The selectable limits must lie below the upper limit of the overrange or above the lower limit of the underrange of the module. Values outside the NAMUR range are also possible in as far as the module does not limit the measured values automatically to these. Normal value Only if PA_ON = FALSE: The non-linearized value is adjusted according to ist physical size by the inputs VLRANGE, VHRANGE and MODE (see also OMODE_xx). The interconnectability of the settings of VLRANGE and VHRANGE with other block connections are determined by the outputs OVLRANGE and OVHRANGE. The conversion algorithm depends on a linearized input signal. If VLRANGE = 0 and VHRANGE = 100 you get a percentage value. If VHRANGE = VLRANGE is set, you get the the input signal of the analog input module (e.g. mA) according to the MODE setting. If the non-linearized value is already a physical value, please set VLRANGE = 0 and VHRANGE = 1. The Quality Code is set to QUALITY = 16#80. 2-78 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Note In the measuring mode "Thermocouples external or internal comparison", the physiacl size is adjusted to +/- 80 mV in the modules of S7 300. You have to determine the temperature with reference to the conversion tables concerned. The physical equivalence in mV is delivered by the module as non-linearized value, please set VHRANGE and VLRANGE +/- 80 mV here. Simulation With the input parameter SIM_ON = TRUE, the value of the input SIM_V is given with Quality Code QUALITY = 16#60. In simulation operation too, a valid operating mode has to be set in Low Word of the input MODE. Otherwise QBAD = 1 is output. If there is a higher-level error, QBAD = FALSE is set. Simulation has highest priority. If the block is in the simulation status, QSIM = TRUE is set. Substitute value With the input parameter SUBS_ON = TRUE, the value of the input SUBS_V is output as value, as long as the non-linearized value is invalid. The Quality Code is set as QUALITY = 16#48 and QBAD = 1. Hold last value With input parameter SUBS_ON = FALSE, the last valid output value (V_LAST) is output, if the non-linearized value is invalid. For V_DELTA > 0, the following applies: ABS (V - V_LAST) > V_DELTA: V = V_LAST1 (second last valid output value) ABS (V - V_LAST) V_DELTA: V = V_LAST (last valid output value) The Quality Code is set as QUALITY = 16#44 and QBAD = 1. Accept value delay Only if PA_ON = FALSE: After restart or if the Quality Code is changed from "BAD" to "GOOD", the Quality Code and value are not updated until the CNT_LIM cycles have passed. If CNT_LIM = 0 (Default setting), this function is switched off. During the accept value delay, the Quality Code = 16#00 and QBAD = 1. The last value remains during the accept value delay. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-79 09.10.2001 Signal blocks and diagnostic drivers Value limiting If PA_ON = TRUE, you can limit very low or very high process values from the (part) process image. If the switch LIMIT_ON = TRUE, the process values (V) are limited: - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Error handling No plausibility checks are carried out with reference to the input parameters. In case of invalid operating mode in the low word of the MODE input it is assumed that the non-linearized value is invalid. Start-up characteristics Does not exist. Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2.16.1 Connections of CH_U_AI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O CH_F_HL Overrange of the Input Value (mA) REAL 0 I/O CH_F_LL Underrange of the Input Value (mA) REAL 0 I/O CH_F_ON 1 = Activate Limit-value Monitoring BOOL 0 I/O CNT_LIM Counter limit INT 0 I/O CNT_RES Counter INT 0 I/O PA_ON 1 = Use PA field device in process image BOOL 0 I/O LAST_BAD Last invalid process value BOOL 0 I/O 2-80 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Connection (parameter) Meaning Data type Initial I/O LIMIT_ON 1 = Limit value control PA field device process value BOOL 0 I/O LL_V Process value, if V < V_LL REAL 0 I/O MODE Value status and operating mode DWORD 0 I/O OUT Input value process image REAL 0 I/O OVHRANGE High limit of the process value (copy) REAL 0 O OVLRANGE Low limit of the process value (copy) REAL 0 O PQC 1 = Use value status in process image BOOL 0 I/O QBAD 1 = Process value invalid BOOL 0 O QC Value status of the input process value BYTE 0 I/O QCHF_HL 1=Input value high limit failure BOOL 0 O QCHF_LL 1=Input value low limit failure BOOL 0 O QSIM 1 = Simulation activ BOOL 0 O QSUBS 1 = Substitute value switching-in active BOOL 0 O QUALITY Value status of the process value BYTE 0 O SIM_ON 1 = Activate simulation BOOL 0 I/O SIM_V Simulation value REAL 0 I/O STATUS Status process value BYTE 0 O SUBS_ON 1 = Enable substitute value switching-in BOOL 0 I/O SUBS_V Substitute value REAL 0 I/O V Process value REAL 0 O VALUE Input value WORD 0 I/O VHRANGE Upper limit of the process value REAL 100 I/O VLRANGE Lower limit of the process value REAL 0 I/O V_DELTA Difference (V - V_LAST) Process value REAL 0 I/O V_HL Upper limit value REAL 0 I/O V_LAST Last valid process value REAL 0 I/O V_LAST1 Second-last valid process value REAL 0 I/O V_LL Lower limit value REAL 0 I/O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-81 09.10.2001 Signal blocks and diagnostic drivers 2.17 CH_U_AO: Analog value output (Universal) Object name (Type + Number) FC 284 Area of application The block is used for signal processing of a analog input value from S7-300/400 SM analog output modules or a PA field device (PA-Profile 3.0 Analog Output only output of REAL value (e.g. SP) with Quality Code). Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32)and the restart OB100 Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The input PA_ON is configured in accordance with the I/O devices used (S7 signal modules (=0) or PA field devices (=1)). * The symbol for the Quality Code of the analog output channel is interconnected to the input QC_SP (at PA devices). * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block (or of the PADP block). * The CH_U_AO block is installed after the MOD/PADP block which is assigned to it in the OB100. Note If you do not use the CFC function "Generate Module Driver", you have to ensure that the CH_U_AO block is installed after the MOD-/PADP block assigned to it in the OB100. 2-82 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Function and Operating principle The block processes all the channel-specific signal functions or the REAL value with Quality Code cyclically. The CH_U_AO block uses the switch position (input PA_ON) to differentiate between an analog non-linearized value and a REAL value with Quality Code of a PA field device (see Addressing). * PA_ON = TRUE The REAL value (SP) with Quality Code (ST_SP) of a PA field device is written in the (part) process image. * PA_ON = FALSE The block writes the process value as analog non-linearized value in a (part) process image. The MODE input determines in which form the non-linearized value is to be created. If the high byte of the MODE input = 0 (value status), the nonlinearized value continues to be written into the (part) process image - however, a quality code "invalid value" is set. The quality code can have the following states: State Quality Code Valid value 16#80 Upper value limited 16#56 Lower value limited 16#55 Simulation 16#60 Invalid value 16#00 Addressing The symbol generated by HW Config in the symbol table for the analog output channel has to be interconnected to the VALUE output . At PA field devices (PA_ON = TRUE), the symbol for the REAL value with O_SP output is interconnected with the symbol of the Quality Code with the QC_SP output . The CFC function "Generate Module Driver" interconnects the symbol for Quality Code automatically with the QC_SP output. Normal value Only if PA_ON = FALSE: The parameters ULRANGE and UHRANGE map the process value U onto the non-linearized value VALUE (quantification stages) of the analog output module depending on the MODE. For example in the mode 4..20mA (16#0203) the non-linearized value for 4mA is output for U = ULRANGE and the non-linearized value for 20mA is output for U = UHRANGE. PHYS_LIM is used to set the limitation of the VALUE non-linearized value. In the default setting (PHYS_LIM = 0) the VALUE output value is limited to the normalizing limits of the module. In accordance with the above example the block calculates the non-linearized value for 20 mA for U > UHRANGE and the nonProcess Control System PCS 7, Driver Blocks A5E00127662-01 2-83 09.10.2001 Signal blocks and diagnostic drivers linearized value for 4mA for U < ULRANGE Accordingly the quality codes 16#56 (upper value limited) and 16#55 (lower value limited) are applied at the QUALITY output instead of the 16#80 (valid value). In order to output analog values outside the normalization values up to the physical limits of the module, you have to set PHYS_LIM = 1. The output values are not limited until, in the above example, the module limits are exceeded by specifying U = 200 (36mA) or U = -50 (-4mA) at ULRANGE = 0 and UHRANGE = 100. The output values are then limited to the physical limits specified in the data sheets of the modules and the corresponding quality codes are output. The outputs QCHF_HL and QCHF_LL also provide information on whether the output values have been limited. Simulation If the input parameter SIM_ON = TRUE, the value of SIM_U is output with Quality Code (QUALITY) = 16#60. A valid mode must also be set in simulation mode in the low word of the input MODE. Otherwise QBAD = 1 is output. Simulation has the highest priority. If there is a higher-level fault, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. I/O fault If the high byte of the input MODE = 0 (value status), the quality code QUALITY = 16#00 is set. The current non-linearized value is always written into the (part) process image. Value limiting (PA_ON = TRUE) you can limit very low or very high process values which lead to an error (QBAD = TRUE) before entry in the (part) process image. If the switch LIMIT_ON = TRUE, the process values (V) are limited: - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Error handling No plausibility checks are carried out with reference to the input parameters. In case of an invalid operating mode in the low word of the MODE input the digitized output value is set to 0 and QUALITY = 16#00 is output. 2-84 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Start-up characteristics The MOD blocks set the LSB in Byte 2 of their outputs OMODE_xx in the OB100. If the block recognizes this code, it acknowledges it and then reacts as follows: If START_ON is not set, the process value U is processed and is transferred to the process image. Otherwise the non-linearized value corresponding to the START_U process value is written to the process image. At PA field devices (PA_ON = TRUE), the current REAL value with Quality Code is written to the process image. Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate. 2.17.1 Connections of CH_U_AO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O LIMIT_ON 1 = Limit value control process value BOOL 0 I/O LL_V Process value, if U < V_LL REAL 0 I/O MODE Value status and operating mode DWORD 0 I/O PA_ON 1 = PA field device, 0 = Signal module BOOL 0 I/O O_SP Process image Setpoint REAL 0 O PHYS_LIM 1 = Enable physical module limit values BOOL 0 I/O QBAD 1 = Invalid output value BOOL 0 O QCHF_HL 1 = Overdriven process value BOOL 0 O QCHF_LL 1 = Underdriven process value BOOL 0 O QC_SP Process image Quality Code Setpoint BYTE 0 O QSIM 1 = Simulation active BOOL 0 O QUALITY Value status of the output value BYTE 0 O SIM_ON 1 = Activate simulation BOOL 0 I/O SIM_U Simulation value REAL 0 I/O START_ON 1 = Substitute value switching-in at start-up BOOL 0 I/O START_U Substitute value at start-up REAL 0 I/O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-85 09.10.2001 Signal blocks and diagnostic drivers Connection (parameter) Meaning Data type Initial I/O ST_SP Status Setpoint BYTE 0 I/O U Process value REAL 0 I/O UHRANGE Upper limit of the process value REAL 100 I/O ULRANGE Lower limit of the process value REAL 0 I/O VALUE Output value WORD 0 O V_HL Upper limit value REAL 0 I/O V_LL Lower limit value REAL 0 I/O 2.18 CH_U_DI: Digital value input (Universal) Object name (Type + Number) FC 285 Area of application The block is used for signal processing of a digital input value from S7-300/400 SM digital input modules or a PA field device (PA-Profile 3.0 Discrete Input). Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32). Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: 2-86 * The input PA_ON is configured in accordance with the I/O devices used (S7 signal modules (=0) or PA field devices (=1)). * The symbol for the Quality Code of the analog output channel is interconnected to the input QC (at PA devices). * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block (or of the PADP block). Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Function and Operating principle The block processes all the channel-specific signal functions or a process value with Quality Code of a PA field device cyclically. The block uses the switch position (input PA_ON) to differentiate between a digital value with or without Quality Code of the data type BOOL or a digital value with Quality Code of the data type BYTE of a PA field device (see Addressing). * PA_ON = TRUE The block cyclically reads in the (part) process image the process value (OUT_D) with status byte (STATUS, see Adressing) of the PROFIBUS PA field device (structure an accordance with the Discrete Input of the PA profiles). The status byte contains information on the measured value and the state of the PROFIBUS PA field device.The process value is displayed in the Q output as below: Q = FALSE, if process value = 0 Q = TRUE, if process value <> 0 If the high byte of the MODE input parameter = 16#40 (value status = higher-level error), the process value and Quality Code are treated as in PA_ON = FALSE. The quality code QUALITY for the process value is determined from the status of the input MODE and the output STATUS. PA MODE recognizes a higher level error e.g. DP/PA Link failure via the input MODE If the high byte of the input MODE = 16#80, the values in the (part) process image are valid. If the high byte of the input MODE = 16#40 (value status = higher-level error), the digital value will be handled as invalid. The Quality Code (QUALITY) is set to 16#44 or 16#48. The same is true for a STATUS with status "BAD". Otherwise STATUS and QUALITY are identical. * PA_ON = FALSE The block reads a digital value of the data type BOOL from the (part) process image. If the high byte of the MODE input parameter = 16#40 (value status = higher-level error), the digital value is treated as invalid. If the input parameter PQC = TRUE, the value status of the digital value is read in the (part) process image. The quality code can have the following states: State Quality Code Valid value 16#80 Simulation 16#60 Last valid value 16#44 Substitute value 16#48 Invalid value 16#00 Process Control System PCS 7, Driver Blocks A5E00127662-01 2-87 09.10.2001 Signal blocks and diagnostic drivers Addressing The symbol generated with HW Config (symbol table) for the digital input channel has to be interconnected to the VALUE input. If the value status of the digital input channel is also in the (part) process image, you have to interconnect the corresponding symbol with the input VALUE_QC and set the input PQC = TRUE. In the case of PA field devices (PA_ON = TRUE), the symbol generated with HW Config (symbol table) for the digital input channel has to be interconnected to the I_OUT_D input. The CFC function "Generate Module Driver" interconnects the symbol for the Quality Code of the digital input channel automatically to the input QC. Normal value The digital value of the (part) process image is output to the output Q with Quality Code QUALITY = 16#80. Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_I (PA_ON = FALSE) or SIM_OUT (PA_ON = TRUE) is output to the output Q with Quality Code QUALITY = 16#60. Simulation has the highest priority. If there is a higher-level fault, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. Substitution value If the input parameter SUBS_ON = TRUE, the value of the input SUBS_I is output to the output Q with Quality Code QUALITY = 16#48 and QBAD = 1, in as far as the digital value of the (part) process image is invalid. Hold last value If the input parameter SUBS_ON = FALSE, the last valid output value is output if the non-linearized value is invalid. The Quality Code is set to QUALITY = 16#44 and QBAD = 1. * Last valid output value corresponds to Q_LAST. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Do not exist. Time response Does not exist. 2-88 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2.18.1 Connections of CH_U_DI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O I_OUT_D Input value of the process image BYTE 0 I/O MODE Value status and operating mode DWORD 0 I/O OUT_D Process value BYTE 0 O PA_ON 1 = PA field device BOOL 0 I/O PQC 1 = Use value status in the process image BOOL 0 I/O Q Process value BOOL 0 O Q_LAST Last valid process value BOOL 0 I/O QBAD 1 = Invalid process value BOOL 0 I/O QC Value status in the process image (Symbol) BYTE 0 I/O QSIM 1 = Simulation active BOOL 0 O QSUBS 1 = Substitute value switching-in active BOOL 0 O QUALITY Value status of the process value BYTE 0 O SIM_I Simulation value BOOL 0 I/O SIM_ON 1 = Activate simulation BOOL 0 I/O SIM_OUT Simulation Value BYTE 0 I/O STATUS Status process value BYTE 0 O SUBS_I Substitute value BOOL 0 I/O SUBS_ON 1 = Enable substitute value switching-in BOOL 0 I/O SUBS_OUT Substitution Value BYTE 0 I/O V_LAST Last valid process value BYTE 0 I/O VALUE Input value BOOL 0 I/O VALUE_QC Value status in the process image BOOL 0 I/O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-89 09.10.2001 Signal blocks and diagnostic drivers 2.19 CH_U_DO Digital value output (Universal) Object name (Type + Number) FC 286 Area of application The block is used for signal processing of a digital output value from S7-300/400 SM digital output modules or a PA field device (PA-Profile 3.0 Discrete Input only SP or RCAS_IN). Calling OBs The calling OB is the watchdog interrupt OB3x into which the block is installed (for example OB 32) and the restart OB100. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The input PA_ON is configured in accordance with the I/O devices used (S7 signal modules (=0) or PA field devices (=1)). * The symbol for the Quality Code of the analog output channel is interconnected to the input QC (at PA devices). * The MODE input is interconnected to the corresponding output OMODE_xx of the MOD block (or of the PADP block). * The CH_U_DO block is installed after the MOD/PADP block assigned to it in the OB100. Note If you do not use the CFC function "Generate Module Driver", you have to ensure that the CH_U_DO block is installed after the MOD-/PADP block assigned to it in the OB100. 2-90 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers Function and Operating principle The block processes all the channel-specific signal functions or a process value with Quality Code of a PA field device cyclically. The block uses the switch position (input PA_ON) to differentiate between a digital output value without Quality Code of the data type BOOL and a digital output value with Quality Code of the data type BYTE of a PA field device (see Addressing). * PA_ON = TRUE The block writes the process value with Quality Code (structure of the process value corresponds to the Digital Output of the PA Profile, 1 Byte (SP) with 1 Byte (ST_SP) Quality Code) in a (part) process image. The Quality Code contains information on the state of the process value. The coding of the Quality Code is described in the PROFIBUS PA 3.0 "General Requirements". If the high byte of the MODE input = 16#40 (value status = higher-level error), the process value with Quality Code continues to be written into the (part) process image - however, a quality code "invalid value" is set at the block output QUALITY. * PA_ON = FALSE The block writes a digital value in a (part) process image. If the high byte of the MODE input = 0 (value status), the digital value continues to be written into the (part) process image - however, a quality code "invalid value" is set. The quality code can have the following states: State Quality Code Valid value 16#80 Simulation 16#60 Invalid value 16#00 Addressing The symbol generated with HW Config (symbol table) for the digital output channel has to be interconnected to the VALUE input. In the case of PA field devices (PA_ON = TRUE), the symbol generated with HW Config (symbol table) for the process value with Quality Code has to be interconnected to the output variable O_SP. The CFC function "Generate Module Driver" interconnects the symbol for the Quality Code of the analog output channel automatically to the output QC_SP. Normal value The digital value is written to the (part) process image and Quality Code (QUALITY) = 16#80 is set. Process Control System PCS 7, Driver Blocks A5E00127662-01 2-91 09.10.2001 Signal blocks and diagnostic drivers Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_I (PA_ON = FALSE) or SIM_OUT (PA_ON = TRUE) is written to the (part) process image and the Quality Code QUALITY = 16#60 is set. Simulation has the highest priority. If there is a higher-level fault, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. I/O fault If the high byte of the input parameter MODE = 0 (value status), the quality code QUALITY = 16#00 is set. The current non-linearized value is always written into the (part) process image. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics The MOD blocks set the LSB in Byte 2 of their outputs OMODE_xx in the OB100. If the block recognizes this code, it acknowledges it and then reacts as follows: If START_ON is not set, the process value U is processed and is transferred to the process image. Otherwise the non-linearized value corresponding to the START_U process value is written to the process image. At PA field devices (PA_ON = TRUE), the current BYTE value with Quality Code is entered in the process image. Time response Does not exist. Message characteristics The block does not have message characteristics. Operator control and monitoring The block does not have a faceplate (display block). 2-92 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 Signal blocks and diagnostic drivers 2.19.1 Connections of CH_U_DO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O I Process value BOOL 0 I/O MODE Value status and operating mode DWORD 0 I/O O_SP Process Image Setpoint BYTE 0 O PA_ON 1 = PA field device BOOL 0 I/O QBAD 1 = Invalid output value BOOL 0 O QC_SP Process Image Quality Code Setpoint BYTE 0 O QSIM 1 = Simulation active BOOL 0 O QUALITY Value status of the output value BYTE 0 O SIM_I Simulation value BOOL 0 I/O SIM_ON 1 = Activate simulation BOOL 0 I/O SIM_SP Simulation Setpoint BYTE 0 I/O SP Setpoint BYTE 0 I/O ST_SP Status Setpoint BYTE 0 I/O START_I Substitute value at start-up BOOL 0 I/O START_ON 1 = Substitute vale switching-in at start-up BOOL 0 I/O VALUE Output value BOOL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 2-93 09.10.2001 Signal blocks and diagnostic drivers 2-94 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 3 3.1 3.1.1 PROFIBUS PA blocks PA_AI: Analog value input PROFIBUS PA PA_AI: Analog Input PROFIBUS PA Object name (Type + Number) FB 101 Area of Application The block processes (cyclic operation) the PA Profile "Transmitter" of a PA field device in accordance with PROFIBUS PA 3.0 Class A and B or a main or secondary variable of a HART analog input module. Calling OBs The calling OB is the watchdog interrupt OB3x, in which you install the block (for example OB32) and OB1. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The installation of block in OB1. * The symbol for the Quality Code of the analog input channel is interconnected to the input QC. * The MODE input is interconnected to the corresponding output OMODE_xx of the PADP_L0x block. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-1 09.10.2001 PROFIBUS PA blocks Function and Operating principle The block cyclically reads the process value with status byte (STATUS) of the PROFIBUS PA field device (structure in accordance with the Analog Input of the PA profiles) from the (part) process image. The process value exists as a physical value. The status byte contains information on the measured value and the state of the PROFIBUS PA field device. In order to improve the interconnectability further important detailed information in addition to the status byte as Boolean (BOOL) values is supplied at the output interface. They correspond to the bit combinations specified in the PROFIBUS PA 3.0 "General Requirements". Device-specific control system messages are generated via ALARM_8P on the basis of the status of the status byte. The quality code (QUALITY) is determined by the status of the input MODE and the output STATUS and used as a process value. The block recognizes a higher-level error (for example failure of DP/PA-Link) via the MODE input . If the High Byte of the input MODE = 16#80, the values in the (part) process image are valid. If the high byte of the MODE input = 16#40 (value status = higher-level error), the analog value is handled as invalid. The Quality Code (QUALITY) is set to 16#44 or 16#48. The same is also true for a STATUS with "BAD" status. Otherwise STATUS and QUALITY are identical. In case of a higher-level error no messages are generated. The operating mode in the Low Word of the MODE input is not taken into consideration. Addressing The symbol generated with HW Config in the symbol table for the analog input channel has to be interconnected to the VALUE input. The symbol for the Quality Code of the analog input channel interconnects the CFC function "Generate Module Driver" with the input parameter QC for you. Simulation If the input parameter SIM_ON = TRUE, the value of the input parameter SIM_V is output with Quality Code (QUALITY =) 16#60. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in the simulation state, QSIM = TRUE is set. If there is no higher-level error and the PA field device displays a Quality Code "BAD", either the substitute value SUBS_V (SUBS_ON= TRUE) or the last value is output. Substitution value If the input parameter SUBS_ON = TRUE, the value of the input SUBS_V is output as the value, in as far as the values are invalid. The Quality Code is set to (QUALITY =) 16#48 and QBAD = 1. 3-2 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Hold last value If the input parameter SUBS_ON = FALSE, the last valid output parameter is output if the values are invalid. The Quality Code is set to (QUALITY =) 16#44 and QBAD = 1. Value limiting You can limit very low or very high process values from the (part) process image. If the switch LIMIT_ON = TRUE, the process values (V) are limited: - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Input MODE = 16#xx01xxxx: Initializing ALARM_8P. Time response Does not exist. Message characteristics As long as there is no higher-level error, the block signals the current state of the Quality Code (status byte) when there is a change. The messages are event messages which do not have to be acknowledged and are only stored in the chronic list of the OS. If the QBAD and QUNCERT outputs are interconnected to the CSF input (external error) of the technological block, this block generates a control system message if a malfunction arises. The DELAY input (default setting 2 seconds) is used to delay an event message when there is a change in the Quality Code. With DELAY you can specify the period in seconds which the block waits when there is a change in the Quality Code after a higher-level error (DP Master system failure, DP/PA-Link failure, device failure or I/O access error), (MODE = 16#40xxxxxx) has gone, until it emits the message. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring Does not exist. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-3 09.10.2001 PROFIBUS PA blocks 3.1.2 Connections of PA_AI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection Meaning (parameter) Data type Initial I/O DELAY INT 2 I Alarm Delay (s) EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I LIMIT_ON 1=Limit on Input Value BOOL 0 I LL_V High Limit Input Value. Set Value if V < V_LL REAL 0 I MSG_STAT Message Failure of Alarm_8P WORD 0 O MODE Value status and operating mode DWORD 0 O QA_1 1 = Alarm/Warning 1 BOOL 0 O QA_2 1 = Alarm/Warning 2 BOOL 0 O QBAD 1 = Collected event QBAD_X BOOL 0 O QBAD_0 1 = Non-specific BOOL 0 O QBAD_1 1 = Configuration error BOOL 0 O QBAD_2 1 = Not connected BOOL 0 O QBAD_3 1 = Device failure BOOL 0 O QBAD_4 1 = Sensor failure BOOL 0 O QBAD_5 1 = No communication (last usable value) BOOL 0 O QBAD_6 1 = No communication (no usable value) BOOL 0 O QBAD_7 1 = Out of service BOOL 0 O QBAD_HL 1 = High limit upper physical range of sensor has been reached BOOL 0 O QBAD_LL 1 = Low limit lower physical range of sensor has been reached BOOL 0 O QC Process Image Input Value Quality Code BYTE 0 I QCASCAD0 1 = OK (cascade) BOOL 0 O QCASCAD1 1 = Initialization acknowledged BOOL 0 O QCASCAD2 1 = Initialization request BOOL 0 O QCASCAD3 1 = Not requested BOOL 0 O QCASCAD4 1 = Reserved BOOL 0 O QCASCAD5 1 = Do not select BOOL 0 O QCASCAD6 1 = Local override BOOL 0 O QCASCAD7 1 = Reserved BOOL 0 O QCASCAD8 1 = Initiate fail safe BOOL 0 O QCONST 1 = Constant BOOL 0 O QERR 1 = Error output (inverted value of ENO) BOOL 1 O QOUT_HHL 1 = Active critical alarm, high limit of OUT has been exceeded BOOL 0 O QOUT_HL 1 = Active advisory alarm, high limit of OUT has been exceeded BOOL 0 O QOUT_LL 1 = Active advisory alarm, low limit of OUT has been exceeded BOOL 0 O 3-4 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Connection Meaning (parameter) Data type Initial I/O QOUT_LLL BOOL 0 O QNONCAS0 1 = OK (non-cascade) BOOL 0 O QNONCAS1 1 = Update event BOOL 0 O QNONCAS2 1 = Active advisory alarm (priority <8) BOOL 0 O 1 = Active critical alarm, low limit of OUT has been exceeded QNONCAS3 1 = Active critical alarm (priority >8) BOOL 0 O QNONCAS4 1 = Unacknowledged update event BOOL 0 O QNONCAS1 1 = Active block alarm BOOL 0 O QNONCAS2 1 = Active advisory alarm (priority <8) BOOL 0 O QNONCAS3 1 = Active critical alarm (priority >8) BOOL 0 O QNONCAS4 1 = Unacknowledged block alarm BOOL 0 O QNONCAS5 1 = Unacknowledged advisory alarm BOOL 0 O QNONCAS6 1 = Unacknowledged critical alarm BOOL 0 O QNONCAS7 1 = Initial fail safe BOOL 0 O QNONCAS8 1 = Maintenance required BOOL 0 O QSIM BOOL 0 O 1 = Simulation Active QSUBS 1 = Failure Substitution Active BOOL 0 O QUALITY Value status of the process value BYTE 0 O QUNCERT 1 = Collected event QUNCERTx BOOL 0 O QUNCERT0 1 = Non-specific BOOL 0 O QUNCERT1 1 = Last usable value BOOL 0 O QUNCERT2 1 = Substitute set BOOL 0 O QUNCERT3 1 = Initial value BOOL 0 O QUNCERT4 1 = Sensor conversion not accurate BOOL 0 O QUNCERT5 1 = Engineering unit violation (unit not in the valid set) BOOL 0 O QUNCERT6 1 = Sub-normal BOOL 0 O QUNCERT7 1 = Configuration error BOOL 0 O QUNCERT8 1 = Sensor calibration BOOL 0 O QUNCERT9 1 = Simulated value BOOL 0 O SIM_ON 1 = Activate Simulation BOOL 0 I SIM_V Simulation Value REAL 0 I STATUS Process value status BYTE 0 O SUBS_ON 1 = Enable Failure Substitution BOOL 0 I SUBS_V Substitution Value REAL 0 I V Process value REAL 0 O VALUE Process Image Input Value REAL 0 I V_HL High Limit Input Value REAL 0 I V_LL Low Limit Input Value REAL 0 I Process Control System PCS 7, Driver Blocks A5E00127662-01 3-5 09.10.2001 PROFIBUS PA blocks 3.1.3 Message texts and auxiliary process values of PA_AI Assignment of message texts and classes to the block parameters of PA_AI Message block ALARM_8P Message number Block parameter Default message text EV_ID 1 QBAD Device error S 2 QUNCERT Uncertain value S 3 QNONCAS1 Update event S 4 QNONCAS7 Initiate fail safe S 5 QNONCAS8 Maintenance required M 6 QOUT_LLL Lower alarm AL 7 QOUT_HHL Upper alarm 8 Message class AH No message The block has no auxiliary process values. If QBAD = TRUE because of a higherlevel error, no message is created. 3.2 3.2.1 PA_AO: Analog value output PROFIBUS PA PA_AO: Analog Output PROFIBUS PA Object name (Type + Number) FB 103 Area of Application The block processes (cyclic operation) the PA Profile "Actuator" of a PA field device in accordance with PROFIBUS PA 3.0 Class A and B. Calling OBs The calling OB is the watchdog interrupt OB3x, in which you install the block (for example OB32) and OB1 and the restart OB100. 3-6 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The installation of block in OB1 and in OB100. * The symbol for the Quality Code of the analog output channel O_SP is interconnected to the output QC_SP and other selected options. * The MODE input is interconnected to the corresponding output OMODE_xx of the PADP_L0x block. Function and Operating principle The block reads the user data from the (part) process image and writes them into the (part) process image depending on the selection (with HW Config or SIMATIC PDM) of the user data configuration of the PA-Profile "Analog Output" in accordance with PROFIBUS PA 3.0. The coding of the set user data configuration of the PROFIBUS PA 3.0 Profile "Analog Output" is contained in the Low Word of the input variable MODE. This specifies which variables are to be read and written in the (part) process image. The block cyclically writes the setpoint (SP) with Quality Code (configuration of the setpoints and process values in accordance with the Analog Output of the PA profiles, REAL with 1 byte Quality Code) into the (part) process image. The PAProfile contains the setpoint and other analog values as a physical unit. The Quality Code contains the information on the state of the setpoint. The coding of the Quality Code is described in the PROFIBUS PA 3.0 "General Requirements". Optionally the reference variable (RCAS_IN) with Quality Code can be transferred in the same cycle into the (part) process image. The data of the PROFIBUS PA field device, as well as the process variable (READBACK) and the discrete position feedback (POS_D) are read cyclically from the (part) process image. Optionally you can additionally read the active reference variable (RCAS_OUT) and the detailed device information (CHECKBACK). The device information is available at the block output in bit-granular form. The data are read from the (part) process image. In order to improve the interconnectability important detailed information is offered from the status bytes read (READBACK) as Boolean (BOOL) values at the output interface. They correspond to the bit combinations specified in the PROFIBUS PA 3.0 "General Requirements". If there is a higher-level error, the data continue to be written into the (part) process image and no data are read from the (part) process image. As long as the higherlevel error exists, the last values are retained with QBAD = TRUE. Note Zero is assigned as the initial value to the status byte of the setpoint (ST_SP) and the reference variable (ST_RCAS_IN). The setpoint or the reference variable only becomes active in the PROFIBUS PA field device if you set the corresponding Quality Code to 16#80. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-7 09.10.2001 PROFIBUS PA blocks Addressing You have to interconnect one of the symbols configured with HW Config (for example SP) for the analog output channel (PROFIBUS PA 3.0 Profile "Analog Output") with the corresponding connection: Connection Data type I_READBACK REAL I_RCAS_OUT REAL I_POS_D BYTE O_SP REAL O_RCAS_IN REAL In CFC the "Generate Module Driver" function is used to automatically interconnect the symbol for the corresponding Quality Code (if it exists) of the connection and the remaining configured symbols of the analog output channel (with Quality Code). Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_SP (and the options SIM_RCAS_IN) is output with Quality Code (QUALITY) = 16#60. A valid mode must also be set in the simulation mode in the Low Word of the MODE input. Otherwise QBAD = 1 is output. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. Value limiting You can limit very low or very high process values which lead to an error (QBAD = TRUE) before entry in the (part) process image. All the process values (V) (both input and output values) are limited at the switch LIMIT_ON = TRUE: - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Input MODE = 16#xx01xxxx: Initializing ALARM_8P. 3-8 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Time response Does not exist. Message characteristics As long as there is no higher-level error, the block signals the state of the Quality Code (status byte) of READBACK and the state of CHECKBACK when there is a change. If the options READBACK or CHECKBACK are not activated, no messages are output. The messages are event messages which do not have to be acknowledged and are only stored in the chronic list of the OS. If the QBAD, QCB and QUNCERT outputs are interconnected to the CSF input (external error) of the technological block, this block generates a control system message if a malfunction arises. The DELAY input (default setting 2 seconds) is used to delay an event message when there is a change in the Quality Code or change in the CHECKBACK state (only rising edge). With DELAY you can specify the period in seconds which the block waits after a higher-level error (DP Master system failure, DP/PA-Link failure, device failure or I/O access error), (MODE = 16#40xxxxxx) has gone, until it emits the message. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring via OS The block does not have a faceplate. 3.2.2 Connections of PA_AO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O CHECK_0 Checkback Field Device BYTE 0 I CHECK_1 Checkback Field Device BYTE 0 I CHECK_2 Checkback Field Device BYTE 0 I DELAY Alarm Delay (s) INT 2 I EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I I_POS_D The current position of the valve (discrete) (symbol) BYTE 0 I I_RCAS_OUT Function Block setpoint REAL 0 I I_READBACK The actual position of the final control element within the travel span (between OPEN and CLOSE position) in PV units. (symbol) REAL 0 I LIMIT_ON 1=Limit on Input Value BOOL 0 I LL_V High Limit Input Value. Set Value if V < V_LL REAL MODE MODE Input parameter BYTE 0 I/O MSG_STAT Message Failure WORD 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 I 3-9 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O O_RCAS_IN Target setpoint provided by a supervisory host to the analog control or output block (symbol) REAL 0 O O_SP Setpoint (symbol) REAL 0 O POS_D The current position of the valve (discrete). The coding of the POS bytes is as follows: 0 = Not initialized 1 = Closed 2 = Opened 3 = Intermediate BYTE 0 O QA_1 1 = Alarm/Warning 1 BOOL 0 O QA_2 1 = Alarm/Warning 2 BOOL 0 O QBAD 1 = Collected event QBAD_X BOOL 0 O QBAD_0 1 = Non-specific BOOL 0 O QBAD_1 1 = Configuration error BOOL 0 O QBAD_2 1 = Not connected BOOL 0 O QBAD_3 1 = Device failure BOOL 0 O QBAD_4 1 = Sensor failure BOOL 0 O QBAD_5 1 = No communication (last usable value) BOOL 0 O QBAD_6 1 = No communication (no usable value) BOOL 0 O QBAD_7 1 = Out of service BOOL 0 O QCASCAD0 1 = OK (cascade) BOOL 0 O QCASCAD1 1 = Initialization acknowledged BOOL 0 O QCASCAD2 1 = Initialization request BOOL 0 O QCASCAD3 1 = Not requested BOOL 0 O QCASCAD4 1 = Reserved BOOL 0 O QCASCAD5 1 = Do not select BOOL 0 O QCASCAD6 1 = Local override BOOL 0 O QCASCAD7 1 = Reserved BOOL 0 O QCASCAD8 1 = Initiate fail safe BOOL 0 O QCB 1 = CHECKBACK (1 or more bits true) BOOL 0 O QCB_0 1 = Field device in fail-safe position active BOOL 0 O QCB_1 1 = Request for local operation BOOL 0 O QCB_2 1 = Field device under local control, LOCKED OUT switch is in gear. BOOL 0 O QCB_3 1 = Emergency override active BOOL 0 O QCB_4 1 = Actual position feedback different from expected position BOOL 0 O QCB_5 1 = Indicates that the torque limit in OPEN direction is exceeded BOOL 0 O QCB_6 1 = Indicates that the torque limit in CLOSE direction is exceeded BOOL 0 O QCB_7 1 = Indicates status of travel monitoring equipment. If YES, travel time for actuator has exceeded BOOL 0 O QCB_8 1 = Actuator is moving towards open direction BOOL 0 O QCB_9 1 = Actuator is moving towards close direction BOOL 0 O QCB_10 1 = The alert generated by any change to the static data (Function and Transducer Block) BOOL 0 O 3-10 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O QCB_11 1 = Simulation of process values is enabled BOOL 0 O QCB_12 Not used BOOL 0 O QCB_13 1 = Internal control loop disturbed BOOL 0 O QCB_14 1 = Positioner inactive (OUT status = BAD) BOOL 0 O QCB_15 1 = Device under self test BOOL 0 O QCB_15 1 = Device under self test ( MODE = out of service) BOOL 0 O QCB_16 1 = Indicates that total valve travel limit is exceeded BOOL 0 O QCB_17 1 = Indicates that an additional input (i.e. for diagnostics) is activated BOOL 0 O QCONST 1 = Constant BOOL 0 O QC_POS_D Quality Code POS BYTE 0 I QC_RCAS_IN Quality Code RCAS_IN (symbol) BYTE 0 O QC_RCAS_OU Quality Code Function Block Setpoint T BYTE 0 I QC_READBA CK Quality Code Function Block Setpoint (symbol) BYTE 0 I QC_SP Quality Code Setpoint (symbol) BYTE 0 O QERR 1 = Error output (inverted value of ENO) BOOL 1 O QNONCAS0 1 = OK (non-cascade) BOOL 0 O QNONCAS1 1 = Update event BOOL 0 O QNONCAS2 1 = Active advisory alarm (priority <8) BOOL 0 O QNONCAS3 1 = Active critical alarm (priority >8) BOOL 0 O QNONCAS4 1 = Unacknowledged update event BOOL 0 O QNONCAS5 1 = Unacknowledged advisory alarm BOOL 0 O QNONCAS6 1 = Unacknowledged critical alarm BOOL 0 O QNONCAS7 1 = Initial fail safe BOOL 0 O QNONCAS8 1 = Maintenance required BOOL 0 O QSIM 1=Simulation Active BOOL 0 O QUNCERT 1 = Collected event QUNCERTx BOOL 0 O QUNCERT0 1 = Non-specific BOOL 0 O QUNCERT1 1 = Last usable value BOOL 0 O QUNCERT2 1 = Substitute set BOOL 0 O QUNCERT3 1 = Initial value BOOL 0 O QUNCERT4 1 = Sensor conversion not accurate BOOL 0 O QUNCERT5 1 = Engineering unit violation (unit not in the valid set) BOOL 0 O QUNCERT6 1 = Sub-normal BOOL 0 O QUNCERT7 1 = Configuration error BOOL 0 O QUNCERT8 1 = Sensor calibration BOOL 0 O QUNCERT9 1 = Simulated value BOOL 0 O RCAS_IN Target setpoint provided by a supervisory host to the analog control or output block REAL 0 I RCAS_OUT Function Block setpoint REAL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 3-11 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O READBACK The actual position of the final control element within the travel span (between OPEN and CLOSE position) in PV units. REAL 0 O SIM_ON 1 = Active Simulation BOOL 0 I SIM_SP Simulation Setpoint REAL 0 I SIM_RCAS_IN Simulation RCAS_IN REAL 0 I SP Setpoint REAL 0 I ST_POS_D Status POS BYTE 0 O ST_READBAC Function Block setpoint status K BYTE 0 O ST_RCAS_IN RCAS_IN status BYTE 0 I ST_RCAS_OU T Function Block setpoint status BYTE 0 O ST_SP Status setpoint BYTE 0 I V_HL High Limit Input Value REAL 0 I V_LL Low Limit Input Value REAL 0 I 3.2.3 Message texts and auxiliary process values of PA_AO Assignment of message texts and classes to the block parameters of PA_AO Message block ALARM_8P EV_ID Message number Block parameter Default message text Message class 1 QBAD Device failure S 2 QUNCERT Uncertain value S 3 QNONCAS1 Update event S 4 QNONCAS7 Initiate fail safe S 5 QNONCAS8 Maintenance required M 6 QCB_0 Field device in fail safe active S 7 QCB_3 or QCB_11 Emergency override active /Simulation enabled S 8 QCB_4 or QCB_7 or QCB_16 Discrepancy in direction S The block has no auxiliary process value. If QBAD = TRUE because of a higherlevel error, no message is created. 3-12 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks 3.3 3.3.1 PA_DI: Digital value input PROFIBUS PA PA_DI: Discrete Input PROFIBUS PA Object name (Type + Number) FB 104 Area of Application The block is used to cyclically input digital values (Discrete Input) via a PROFIBUS PA field device Class A and B. Calling OBs The calling OB is the watchdog interrupt OB3x, in which you install the block (for example OB32) and OB1. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The installation of block in OB1. * The symbol for the Quality Code of the digital input channel is interconnected to the input QC. * The MODE input Setting_PA_MODE is interconnected to the corresponding output OMODE_xx of the PADP_L0x block. Function and Operating Principle The block cyclically reads the process value (OUT_D) with status byte (STATUS) of the PROFIBUS PA field device (structure an accordance with the Discrete Input of the PA profiles) from the (part) process image. The status byte contains information on the measured value and the state of the PROFIBUS PA field device. The process value and status bytes (total of 2 bytes) are read directly and coherently as a WORD. Further important detailed information is supplied as Boolean (BOOL) values at the output interface in addition to the status byte in order to improve the interconnectability. They correspond to the bit combinations specified in the PROFIBUS PA 3.0 "General Requirements". Device-specific process control system messages are generated via ALARM_8P from the status of the status bytes. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-13 09.10.2001 PROFIBUS PA blocks The quality code QUALITY for the process value is determined from the status of the input MODE and the output STATUS. PA MODE recognizes a higher level error e.g. DP/PA Link failure via the input MODE If the high byte of the input MODE = 16#80, the values in the (part) process image are valid. If the high byte of the input MODE = 16#40 (value status = higher-level error), the digital value will be handled as invalid. The Quality Code (QUALITY) is set to 16#44 or 16#48. The same is true for a STATUS with status "BAD". Otherwise STATUS and QUALITY are identical. Addressing The symbol generated with HW Config in the symbol table for the digital input channel has to be interconnected to the I_OUT_D input. The CFC function "Generate Module Driver" interconnects the symbol for the Quality Code of the digital input channel to the input parameter QC. Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_I is output with Quality Code (QUALITY =) 16#60. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. If there is no higher-level error and the PA field device displaysa Quality Code "BAD", either the substitute value SUBS_I (SUBS_ON= TRUE) or the last value is outpit. Substitution value If the input parameter SUBS_ON = TRUE, the value of the input SUBS_I is output as the value, in as far as the values are invalid. The Quality Code is set to (QUALITY =) 16#48 and QBAD = 1. Hold last value If the input parameter SUBS_ON = FALSE, the last valid output parameter is output if the values are invalid. The Quality Code is set to (QUALITY =) 16#44 and QBAD = 1. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Input MODE = 16#xx01xxxx: Initializing ALARM_8P. Time response Does not exist. 3-14 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Message characteristics As long as there is no higher-level error, the block signals the current state of the Quality Code (status byte) when there is a change. The messages are event messages which do not have to be acknowledged and are only stored in the chronic list of the OS. If the QBAD and QUNCERT outputs are interconnected to the CSF input (external error) of the technological block, this block generates a control system message if a malfunction arises. The DELAY input (default setting 2 seconds) is used to delay an event message when there is a change in the Quality Code. With DELAY you can specify the period in seconds which the block waits when there is a change in the Quality Code after a higher-level error (DP Master system failure, DP/PA-Link failure, device failure or I/O access error), (MODE = 16#40xxxxxx) has gone, until it emits the message. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate. 3.3.2 Connections of PA_DI The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O DELAY Alarm Delay (s) INT 2 I EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I I_OUT_D Process Image Process Value BYTE 0 I MODE MODE Input parameter DWORD 0 I/O MSG_STAT Message Failure WORD 0 O OUT_D Process value BYTE 0 O QA_1 1 = Alarm/Warning 1 BOOL 0 O QA_2 1 = Alarm/Warning 2 BOOL 0 O QBAD 1 = Collected event QBAD_X BOOL 0 O QBAD_0 1 = Non-specific BOOL 0 O QBAD_1 1 = Configuration error BOOL 0 O QBAD_2 1 = Not connected BOOL 0 O QBAD_3 1 = Device failure BOOL 0 O QBAD_4 1 = Sensor failure BOOL 0 O QBAD_5 1 = No communication (last usable value) BOOL 0 O QBAD_6 1 = No communication (no usable value) BOOL 0 O QBAD_7 1 = Out of service BOOL 0 O QC Process Image Value Quality Code BYTE 0 I QCONST 1 = Constant BOOL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 3-15 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O QERR 1 = Error output (inverted value of ENO) BOOL 1 O QSIM 1=Simulation Active BOOL 0 O QSUBS 1=Failure Substitution Active BOOL 0 O QUALITY Value status of the process value BYTE 0 O QUNCERT 1 = Collected event QUNCERTx BOOL 0 O QUNCERT0 1 = Non-specific BOOL 0 O QUNCERT1 1 = Last usable value BOOL 0 O QUNCERT2 1 = Substitute set BOOL 0 O QUNCERT3 1 = Initial value BOOL 0 O QUNCERT4 1 = Sensor conversion not accurate BOOL 0 O QUNCERT5 1 = Engineering unit violation (unit not in the valid set) BOOL 0 O QUNCERT6 1 = Sub-normal BOOL 0 O QUNCERT7 1 = Configuration error BOOL 0 O QUNCERT8 1 = Sensor calibration BOOL 0 O QUNCERT9 1 = Simulated value BOOL 0 O Q0 Process Value Bit 0 BOOL 0 O Q1 Process Value Bit 1 BOOL 0 O Q2 Process Value Bit 2 BOOL 0 O Q3 Process Value Bit 3 BOOL 0 O Q4 Process Value Bit 4 BOOL 0 O Q5 Process Value Bit 5 BOOL 0 O Q6 Process Value Bit 6 BOOL 0 O Q7 Process Value Bit 7 BOOL 0 O SIM_I Simulation Value BYTE 0 I SIM_ON 1 = Activate Simulation BOOL 0 I STATUS Process Value Status BYTE 0 O SUBS_I Substitute Value BYTE 0 I SUBS_ON 1 = Enable failure substitution BOOL 0 I 3-16 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks 3.3.3 Message texts and auxiliary process values of PA_DI Assignment of message texts and classes to the block parameters of PA_DI Message block ALARM_8P EV_ID Message number Block parameter Default message text Message class 1 QBAD Device failure S 2 QUNCERT Uncertain value S 3 QNONCAS1 Update event S 4 QNONCAS7 Initiate fail safe S 5 QNONCAS8 Maintenance required M 6 No message 7 8 No message - - No message The block has no auxiliary process value. If QBAD = TRUE because of a higherlevel error, no message is created. 3.4 3.4.1 PA_DO: Digital value output PROFIBUS PA PA_DO: Discrete Output PROFIBUS PA Object name (Type + Number) FB 105 Area of Application The block is used to cyclically output digital values (SP or RCAS_IN, max. of 8) via a PROFIBUS PA field device Class A and B. Calling OBs The calling OB is the watchdog interrupt OB3x, in which you install the block (for example OB32) and OB1 and the restart OB100. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-17 09.10.2001 PROFIBUS PA blocks Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The installation of block in OB1 and OB100. * The symbol for the Quality Code of the digital output channel O_SP is interconnected to the output QC_SP and other selected options. * The MODE input Setting_PA_MODE is interconnected to the corresponding output OMODE_xx of the PADP_L0x block. Function and Operating principle The block reads the user data from the (part) process image and writes them into the (part) process image depending on the selection (with HW Config or SIMATIC PDM) of the user data configuration of the PA-Profile "Digital Output" in accordance with PROFIBUS PA 3.0. The coding of the set user data configuration of the PROFIBUS PA 3.0 Profile "Discrete Output" is contained in the Low Word of the input variable MODE. This specifies which variables are to be read and written in the (part) process image. The block cyclically writes the setpoint (SP) with Quality Code (configuration of the setpoints and process values in accordance with the Digital Output of the PA Profiles, 1 byte with 1 byte Quality Code) into the (part) process image. The Quality Code contains the information on the state of the setpoint. The coding of the Quality Code is described in the PROFIBUS PA 3.0 "General Requirements". Optionally the setpoint in the state RCAS (Remote Cascade) (RCAS_IN) with Quality Code can be transferred in the same cycle into the (part) process image. Optionally, the data are read cyclically from the PROFIBUS PA field such as the state of the valve (READBACK), the process value of the valve setting in the state RCAS (RCAS_OUT) and the detailed device information (CHECKBACK) from the (part) process image. The device information is available at the block output in bitgranular form. In order to improve the interconnectability important detailed information is offered from the status bytes read as Boolean (BOOL) values at the output interface. They correspond to the bit combinations specified in the PROFIBUS PA "General Requirements". If READBACK and RCAS_OUT exist simultaneously, the detailed information is derived from the READBACK status byte. If there is a higher-level error, the data continue to be written into the (part) process image and no data are read from the (part) process image. As long as the higherlevel error exists, the last values are retained with QBAD = TRUE. Note "Zero" is assigned as the initial value to the status byte of the setpoint (ST_SP) and the reference variable (ST_RCAS_IN). The setpoint or the reference variable only becomes active in the PROFIBUS PA field device if you set the corresponding status byte to 16#80. 3-18 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Addressing You have to interconnect one of the symbols configured with HW Config (for example SP) for the digital output channel (PROFIBUS PA 3.0 Profile "Analog Output") with the corresponding connection: Connection Data type I_READBACK BYTE I_RCAS_OUT BYTE O_SP BYTE O_RCAS_IN BYTE In CFC the "Generate Module Driver" function is used to automatically interconnect the symbol for the corresponding Quality Code (if it exists) of the connection and the remaining configured symbols of the digital output channel (with Quality Code). Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_SP (and the option SIM_RCAS_IN) is output with Quality Code (QUALITY) = 16#60. A valid mode must also be set in the simulation mode in the Low Word of the MODE input. Otherwise QBAD = 1 is output. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Input MODE = 16#xx01xxxx: Initializing ALARM_8P. Time response Does not exist. Message characteristics As long as there is no higher-level error, the block signals the state of the Quality Code (status byte) of READBACK and the state of CHECKBACK when there is a change. If the options READBACK or CHECKBACK are not activated, no messages are output. The messages are event messages which do not have to be acknowledged and are only stored in the chronic list of the OS. If the QBAD, QCB and QUNCERT outputs are interconnected to the CSF input (external error) of the technological block, this block generates a control system message if a malfunction arises. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-19 09.10.2001 PROFIBUS PA blocks The DELAY input (default setting 2 seconds) is used to delay an event message when there is a change in the Quality Code or change in the CHECKBACK state (only rising edge). With DELAY you can specify the period in seconds which the block waits after a higher-level error (DP Master system failure, DP/PA-Link failure, device failure or I/O access error), (MODE = 16#40xxxxxx) has gone, until it emits the message. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate. 3.4.2 Connections of PA_DO The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O CHECK_0 Checkback Field Device BYTE 0 I CHECK_1 Checkback Field Device BYTE 0 I CHECK_2 Checkback Field Device BYTE 0 I DELAY Alarm Delay (s) INT 2 I EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I I_RCAS_OUT Function Block setpoint BYTE 0 I I_READBACK Process value (READBACK) (symbol) BYTE 0 I MODE MODE Input parameter BYTE 0 I/O MSG_STAT Message Failure WORD 0 O O_RCAS_IN Process image target setpoint provided by a supervisory host BYTE to the analog control or output block (symbol) 0 O O_SP Setpoint (symbol) BYTE 0 OI QA_1 1 = Alarm/Warning 1 BOOL 0 O QA_2 1 = Alarm/Warning 2 BOOL 0 O QBAD 1 = Collected event QBAD_X BOOL 0 O QBAD_0 1 = Non-specific BOOL 0 O QBAD_1 1 = Configuration error BOOL 0 O QBAD_2 1 = Not connected BOOL 0 O QBAD_3 1 = Device failure BOOL 0 O QBAD_4 1 = Sensor failure BOOL 0 O QBAD_5 1 = No communication (last usable value) BOOL 0 O QBAD_6 1 = No communication (no usable value) BOOL 0 O QBAD_7 1 = Out of service BOOL 0 O QCONST 1 = Constant BOOL 0 O QCB_0 1 = Field device in fail-safe position active BOOL 0 O QCB_1 1 = Request for local operation at device BOOL 0 O 3-20 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O QCB_2 1 = Field device under local control BOOL 0 O QCB_3 1 = Emergency override active BOOL 0 O QCB_4 1 = The actuator left the final position it had already reached BOOL 0 O QCB_5 1 = Indicates a lead break of the valve connection BOOL 0 O QCB_6 1 = Indicates a short circuit of the valve connection BOOL 0 O QCB_7 Not used BOOL 0 O QCB_8 1 = Actuator is moving towards open direction BOOL 0 O QCB_9 1 = Actuator is moving towards close direction BOOL 0 O QCB_10 1 = The alert generated by any change to the static data of FB and TB BOOL 0 O QCB_11 1 = Simulation of process values is enabled BOOL 0 O QCB_12 Not used BOOL 0 O QCB_13 1 = Internal control loop disturbed BOOL 0 O QCB_14 1 = Valve inactive (status OUT_D bad) BOOL 0 O QCB_15 1 = Device under self test BOOL 0 O QCB_16 1 = Indicates that total valve travel limit is exceeded BOOL 0 O QCB_17 1 = Limit for break time of change from OPEN to CLOSE exceeded BOOL 0 O QCB_18 1 = Limit for break time of change from CLOSE to OPEN exceeded BOOL 0 O QCB_19 1 = Error occurred in the internal cycle test BOOL 0 O QCB_20 1 = Limit for time between change from OPEN to CLOSE exceeded BOOL 0 O QCB_21 1 = Limit for time between change from CLOSE to OPEN exceeded BOOL 0 O QCB_22 1 = Valve blocked mechanically BOOL 0 O QC_RCAS_IN Quality Code Target Setpoint (symbol) BYTE 0 O QC_RCAS_OUT Quality Code FB Setpoint (symbol) BYTE 0 I QC_READBAC K Quality Code Function Block Setpoint (symbol) BYTE 0 I QC_SP Quality Code Setpoint (symbol) BYTE 0 O QERR 1 = Error output (inverted value of ENO) BOOL 1 O QSIM 1=Simulation Active BOOL 0 O QSUBS 1=Failure Substitution Active BOOL 0 O QUNCERT 1 = Collected event QUNCERTx BOOL 0 O QUNCERT0 1 = Non-specific BOOL 0 O QUNCERT1 1 = Last usable value BOOL 0 O QUNCERT2 1 = Substitute set BOOL 0 O QUNCERT3 1 = Initial value BOOL 0 O QUNCERT4 1 = Sensor conversion not accurate BOOL 0 O QUNCERT5 1 = Engineering unit violation (unit not in the valid set) BOOL 0 O QUNCERT6 1 = Sub-normal BOOL 0 O QUNCERT7 1 = Configuration error BOOL 0 O Process Control System PCS 7, Driver Blocks A5E00127662-01 3-21 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O QUNCERT8 1 = Sensor calibration BOOL 0 O QUNCERT9 1 = Simulated value BOOL 0 O RCAS_IN Target setpoint BYTE 0 I RCAS_OUT Function Block setpoint BYTE 0 O READBACK Process Value (READBACK) BYTE 0 O SIM_ON 1 = Activate simulation BOOL 0 I SIM_RCAS_IN Simulation target setpoint BYTE 0 I SIM_SP Simulation Value BYTE 0 I SP Setpoint REAL 0 I ST_READBAC K Function Block setpoint status BYTE 0 O ST_RCAS_IN RCAS_IN status BYTE 0 I ST_RCAS_OUT Function Block setpoint status BYTE 0 O ST_SP Setpoint status BYTE 0 I V_HL High Limit Input Value REAL 0 I V_LL Low Limit Input Value REAL 0 I 3.4.3 Message texts and auxiliary process values of PA_DO Assignment of message texts and classes to the block parameters of PA_DO Message block ALARM_8P Message Block parameter number Default message text Message class EV_ID 1 QBAD Device failure S 2 QUNCERT Uncertain value S 3 QNONCAS1 Update event S 4 QNONCAS7 Initiate fail safe S 5 QNONCAS8 Maintenance required M 6 QCB_0 Field device in fail safe active S 7 QCB_3 or QCB_11 Emergency override active /Simulation anabled S 8 QCB_17or QCB_18 or QCB_20 or QCB_21 Break/Transit time OPEN / CLOSE S The block has no auxiliary process value. If QBAD = TRUE because of a higherlevel error, no message is created. 3-22 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks 3.5 3.5.1 PADP_L0x: Monitoring of DP/PA slaves PADP_L00: Monitoring of DP/PA slaves with up to 7 slots Object name (Type + Number) FB 109 Area of Application The block monitors DP/PA field devices which are operated as a DP-V0 or DP-V1 slave behind a DP/PA Y-Link which is operated as a DP-V0 slave. The PA field devices have to fulfill the PROFIBUS PA V3.0 Profile. For DP field devices individual blocks have to be available for their diagnostic and signal processing. Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The PADP_L00 block is installed in the run sequence behind the DPAY_V0 block * Configuration of - The MODE_xx input (mode of slot xx of a field device). - The PADP_ADR input (DP/PA Slave address behind DP/PA-Link or YLink). Process Control System PCS 7, Driver Blocks A5E00127662-01 3-23 09.10.2001 PROFIBUS PA blocks * Interconnection of - The inputs to the inputs of the DPAY_V0 - The OUT structure CPU_DIAG of the OB_BEGIN and RAC_DIAG of the DPAY_V0 block with the INOUT structures of the same name of the PADP_L00 block. Function and Operating Principle The block acyclically analyzes all the events which concern a DP or PA field device and its slots. Depending on the slot it forms the respective DP_MODE or PA_MODE and value status for the DP or PA signal processing blocks. The permissible PA_MODE is already defined for the PA signal processing blocks. In the case of DP field devices the DP_MODE has to be defined individually for the DP field device blocks. The events are signaled with ALARM_8P. The signaling function can be switched off. The block is enabled for running by the higher-level DPAY_V0 block. The event to be evaluated is entered in the start information (CPU_DIAG) of the OB_BEGIN block. In diagnostic cases the data are already evaluated by the LINK block (DPAY_V0). The diagnostic information which concern the PA field device are saved in the structure DPA_M. The structure consists of two DWORD (S_01 for Module 1 to 16 and S_02 for Module 17 to 32) and one BOOL (S_ERR = DP/PA field device faulty) variables. Two bits of the DWORD are assigned per slot of the DP/PA field device, whereby Bit 0 and Bit 1 belong to Slot 1 of the DP/PA field device, etc. The slots 1 to 7 are evaluated. They are defined as follows: State Bit 0 State Bit 1 Meaning 0 0 Module x OK (valid user data) 0 1 Module x fault (invalid user data) 1 0 Incorrect Module x (invalid user data) 1 1 No Module x (invalid user data) An input (MODE_xx) exists for every slot (module) of the DP/PA field device. In the case of PA field devices the configurations carried out with HW Config of the PA field device slots (modules) are communicated. In the case of DP field devices the user has to carry out its codings at the MODE input himself. 3-24 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks MODE_xx is read into the low word of the output OMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the slot is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "Invalid value" due to higher-level error (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O access error (OB70) (if not switched, output parameter QRACKF = TRUE) * Rack failure (OB86) (output parameter QRACKF = TRUE) * Diagnostic interrupt concerning a complete field device (OB82) (output parameter QMODF = TRUE, if DPA_M.S_ERR = TRUE) * Diagnostic interrupt slot xx concerning a field device (OB82): (output parameter OMODE_xx = Module-(slot-)error specific DPA_M) The above events are evaluated by the DPAY_V0 block. In the case of a diagnostic interrupt the block signals to the WinCC field-devicespecifically by means of the ALARM_8P. A difference is made between a field device and its slots, whereby a message number is assigned to each slot. Redundancy The redundancy evaluation of the DP Master systems at an H system is carried out in the higher-level DPAY_V0 block. MODE Setting for PA-Profiles PA_MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Error handling No plausibility checks are carried out with reference to the input parameters. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-25 09.10.2001 PROFIBUS PA blocks Start-up characteristics After a restart or an initial start the system checks whether the PA field device is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. Message characteristics The block signals field device faults by means of ALARM_8P and creates the following messages in the OBs listed below: OB No. Starting event Message OB1 Cyclic processing Repeat updating ALARM_8P outputs / messages, if necessary OB82 Diagnostic interrupt Device fault coming/going Device module xx fault coming/going Device module xx incorrect coming/going Device module xx missing coming/going OB100 Restart Initializing ALARM_8P Operator control and monitoring The block does not have a faceplate (display block). Note In "Connection of PADP L0x" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 3-26 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks 3.5.2 Message texts and auxiliary process values of PADP_L00 Assignment of message texts and classes to the block parameters of PADP_L00 Message block ALARM_8P EV_ID Message number Block parameter Default message text Message class 1 QMODF Device @1%d@/@2%d@/@3%d@: Failure S 2 - Device @1%d@/@2%d@/@3%d@: Module 00 @4W%t#PADP_L00_TXT@ S - Device @1%d@/@2%d@/@3%d@: Module 06 @10W%t#PADP_L00_TXT@ ... ... 8 S The message texts and their text numbers in the text library PADP_L00_TXT are listed in the Text Library for DP-/PA-Slaves after a PA-/Y-LINK DP V0 Assignment of the auxiliary process values for the block parameters of PA_TOT Message block ALARM_8P Value Block parameter Meaning EV_ID 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 2-8) from PADP_L00_TXT If the PA field device is connected behind a DP/PA-Link V0 which is not connected and SUBN1_ID = 16#FF, SUBN2_ID is entered as the auxiliary process value. 3.5.3 PADP_L01: Monitoring of DP/PA slaves with up to 16 slots Object name (Type + Number) FB 110 Process Control System PCS 7, Driver Blocks A5E00127662-01 3-27 09.10.2001 PROFIBUS PA blocks Area of Application The block monitors DP/PA field devices which are operated as a DP-V0 or DP-V1 slave behind a DP/PA Y-Link which is operated as a DP-V0 slave. The PA field devices have to fulfill the PROFIBUS PA V3.0 Profile. For DP field devices individual blocks have to be available for their diagnostic and signal processing. Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The PADP_L01 block is installed in the run sequence behind the DPAY_V0 block * Configuration of * - The MODE_xx input (mode of slot xx of a field device). - The PADP_ADR input (DP/PA Slave address behind DP/PA-Link or YLink). Interconnection of - The inputs to the inputs of the DPAY_V0 - The OUT structure CPU_DIAG of the OB_BEGIN and RAC_DIAG of the DPAY_V0 block with the INOUT structures of the same name of the PADP_L01 block. Function and Operating Principle The block acyclically analyzes all the events which concern a DP or PA field device and its slots. Depending on the slot it forms the respective DP_MODE or PA_MODE and value status for the DP or PA signal processing blocks. The permissible PA_MODE is already defined for the PA signal processing blocks. In the case of DP field devices the DP_MODE has to be defined individually for the 3-28 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks DP field device blocks. The events are signaled with ALARM_8P. The signaling function can be switched off. The block is enabled for running by the higher-level DPAY_V0 block. The event to be evaluated is entered in the start information (CPU_DIAG) of the OB_BEGIN block. In diagnostic cases the data are already evaluated by the LINK block (DPAY_V0). The diagnostic information which concern the PA field device are saved in the structure DPA_M. The structure consists of two DWORD (S_01 for Module 1 to 16 and S_02 for Module 17 to 32) and one BOOL (S_ERR = DP/PA field device faulty) variables. Two bits of the DWORD are assigned per slot of the DP/PA field device, whereby Bit 0 and Bit 1 belong to Slot 1 of the DP/PA field device, etc. The slots 1 to 16 are evaluated. They are defined as follows: State Bit 0 State Bit 1 Meaning 0 0 Module x OK (valid user data) 0 1 Module x fault (invalid user data) 1 0 Incorrect Module x (invalid user data) 1 1 No Module x (invalid user data) An input (MODE_xx) exists for every slot (module) of the DP/PA field device. In the case of PA field devices the configurations carried out with HW Config of the PA field device slots (modules) are communicated. In the case of DP field devices the user has to carry out its codings at the MODE input himself. MODE_xx is read into the low word of the outputOMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the slot is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "Invalid value" due to higher-level error (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O access error (OB70) (if not switched, output parameter QRACKF = TRUE) * Rack failure (OB86) (output parameter QRACKF = TRUE) * Diagnostic interrupt concerning a complete field device (OB82) (output parameter QMODF = TRUE, if DPA_M.S_ERR = TRUE) * Diagnostic interrupt slot xx concerning a field device (OB82): (output parameter OMODE_xx = Module-(slot-)error specific DPA_M) The above events are evaluated by the DPAY_V0 block. In the case of a diagnostic interrupt the block signals to the WinCC field-devicespecifically by means of the ALARM_8P. A difference is made between a field device and its slots, whereby a message number is assigned to each slot. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-29 09.10.2001 PROFIBUS PA blocks Redundancy The redundancy evaluation of the DP Master systems at an H system is carried out in the higher-level DPAY_V0 block. MODE Setting for PA-Profiles PA_MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics After a restart or an initial start the system checks whether the PA field device is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. Message characteristics The block signals field device faults by means of ALARM_8P and creates the following messages in the OBs listed below: OB No. Starting event Message OB1 Cyclic processing Repeat updating ALARM_8P outputs / messages, if necessary OB82 Diagnostic interrupt Device fault coming/going Device module xx fault coming/going Device module xx incorrect coming/going Device module xx missing coming/going OB100 Restart 3-30 Initializing ALARM_8P Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Operator control and monitoring The block does not have a faceplate (display block). Note In "Connection of PADP L0x" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 3.5.4 Message texts and auxiliary process values of PADP_L01 Assignment of message texts and classes to the block parameters of PADP_L01 Message block ALARM_8P Message number Block parameter Default message text Message class EV_ID1 1 QMODF Device @1%d@/@2%d@/@3%d@: Failure S 2 - Device @1%d@/@2%d@/@3%d@: Module 00 @4W%t#PADP_L01_TXT@ S ... EV_ID2 ... 8 - Device @1%d@/@2%d@/@3%d@: Module 06 @10W%t#PADP_L01_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 07 @4W%t#PADP_L01_TXT@ S ... EV_ID3 ... 8 - Device @1%d@/@2%d@/@3%d@: Module 14 @10W%t#PADP_L01_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 15 @5W%t#PADP_L01_TXT@ S - - 2 ... 8 ... - - - The message texts and their text numbers in the text library PADP_L01_TXT are listed in the Text Library for DP-/PA-Slaves after a PA-/Y-LINK DP V0 Process Control System PCS 7, Driver Blocks A5E00127662-01 3-31 09.10.2001 PROFIBUS PA blocks Assignment of the auxiliary process values for the block parameters of PADP_L01 Message block ALARM_8P Value Block parameter Meaning EV_ID1 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 2-8) from PADP_L01_TXT EV_ID2 EV_ID3 1 SUBN_ID DP Master system ID(byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1-8) from PADP_L01_TXT 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1) from PADP_L01_TXT If the PA field device is connected behind a DP/PA-Link V0 which is not connected and SUBN1_ID = 16#FF, SUBN2_ID is entered as the auxiliary process value. 3.5.5 PADP_L02: Monitoring of DP/PA slaves with up to 32 slots Object name (Type + Number) FB 111 Area of Application The block monitors DP/PA field devices which are operated as a DP-V0 or DP-V1 slave behind a DP/PA Y-Link which is operated as a DP-V0 slave. The PA field devices have to fulfill the PROFIBUS PA V3.0 Profile. For DP field devices individual blocks have to be available for their diagnostic and signal processing. 3-32 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The PADP_L02 block is installed in the run sequence behind the DPAY_V0 block * Configuration of * - The MODE_xx input (mode of slot xx of a field device). - The PADP_ADR input (DP/PA Slave address behind DP/PA-Link or YLink). Interconnection of - The inputs to the inputs of the DPAY_V0 - The OUT structure CPU_DIAG of the OB_BEGIN and RAC_DIAG of the DPAY_V0 block with the INOUT structures of the same name of the PADP_L02 block. Function and Operating principle The block acyclically analyzes all the events which concern a DP or PA field device and its slots. Depending on the slot it forms the respective DP_MODE or PA_MODE and value status for the DP or PA signal processing blocks. The permissible PA_MODE is already defined for the PA signal processing blocks. In the case of DP field devices the DP_MODE has to be defined individually for the DP field device blocks. The events are signaled with ALARM_8P. The signaling function can be switched off. The block is enabled for running by the higher-level DPAY_V0 block. The event to be evaluated is entered in the start information (CPU_DIAG) of the OB_BEGIN block. In diagnostic cases the data are already evaluated by the LINK block (DPAY_V0). The diagnostic information which concern the PA field device are saved in the structure DPA_M. The structure consists of two DWORD (S_01 for Module 1 to 16 Process Control System PCS 7, Driver Blocks A5E00127662-01 3-33 09.10.2001 PROFIBUS PA blocks and S_02 for Module 17 to 32) and one BOOL (S_ERR = DP/PA field device faulty) variables. Two bits of the DWORD are assigned per slot of the DP/PA field device, whereby Bit 0 and Bit 1 belong to Slot 1 of the DP/PA field device, etc. The slots 1 to 32 are evaluated. They are defined as follows: State Bit 0 State Bit 1 Meaning 0 0 Module x OK (valid user data) 0 1 Module x fault (invalid user data) 1 0 Incorrect Module x (invalid user data) 1 1 No Module x (invalid user data) An input (MODE_xx) exists for every slot (module) of the DP/PA field device. In the case of PA field devices the configurations carried out with HW Config of the PA field device slots (modules) are communicated. In the case of DP field devices the user has to carry out its codings at the MODE input himself. MODE_xx is read into the low word of the output OMODE_xx. This is only carried out during the start-up/initial start or if ACC_MODE = TRUE. The current value status of the slot is entered in the highest-value byte. If good, OMODE_xx = 16#80xxxxxx is set. The following events lead to a value status "Invalid value" due to higher-level error (OMODE_xx = 16#40xxxxxx): * CPU redundancy loss (OB72) (if not switched, output parameter QRACKF = TRUE) * I/O access error (OB70) (if not switched, output parameter QRACKF = TRUE) * Rack failure (OB86) (output parameter QRACKF = TRUE) * Diagnostic interrupt concerning a complete field device (OB82) (output parameter QMODF = TRUE, if DPA_M.S_ERR = TRUE) * Diagnostic interrupt slot xx concerning a field device (OB82): (output parameter OMODE_xx = Module-(slot-)error specific DPA_M) The above events are evaluated by the DPAY_V0 block. In the case of a diagnostic interrupt the block signals to the WinCC field-devicespecifically by means of the ALARM_8P. A difference is made between a field device and its slots, whereby a message number is assigned to each slot. Redundancy The redundancy evaluation of the DP Master systems at an H system is carried out in the higher-level DPAY_V0 block. 3-34 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks MODE Setting for PA-Profiles PA_MODE Note If you change the configuration of the MODE_xx inputs during operation, the change does not become active until the input ACC_MODE = 1 has been set at the outputs. OMODE structure Refer to OMODE Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics After a restart or an initial start the system checks whether the PA field device is available under the logical base address. A restart (OB100) is signaled via the LSB in Byte 2 of the outputs OMODE_xx. Time response Does not exist. Message characteristics The block signals field device faults by means of ALARM_8P and creates the following messages in the OBs listed below: OB No. Starting event Message OB1 Cyclic processing Repeat updating ALARM_8P outputs / messages, if necessary OB82 Diagnostic interrupt Device fault coming/going Device module xx fault coming/going Device module xx incorrect coming/going Device module xx missing coming/going OB100 Restart Initializing ALARM_8P Process Control System PCS 7, Driver Blocks A5E00127662-01 3-35 09.10.2001 PROFIBUS PA blocks Operator control and monitoring The block does not have a faceplate (display block). Note In "Connection of PADP L0x" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 3.5.6 Message texts and auxiliary process values of PADP_L02 Assignment of message texts and classes to the block parameters of PADP_L02 Message block ALARM_8P Message number Block parameter Default message text Message class EV_ID1 1 QMODF Device @1%d@/@2%d@/@3%d@: Failure S 2 - Device @1%d@/@2%d@/@3%d@: Module 07 @4W%t#PADP_L02_TXT@ S 3 - Device @1%d@/@2%d@/@3%d@: Module 15@5W%t#PADP_L02_TXT@ S 4 - Device @1%d@/@2%d@/@3%d@: Module 23@5W%t#PADP_L02_TXT@ S 5 - Device @1%d@/@2%d@/@3%d@: Module 31 @5W%t#PADP_L02_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 00 @4W%t#PADP_L02_TXT@ S 7 - Device @1%d@/@2%d@/@3%d@: Module 06 @10W%t#PADP_L02_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 08 @4W%t#PADP_L02_TXT@ S 7 - Device @1%d@/@2%d@/@3%d@: Module 14 @10W%t#PADP_L02_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 16 @4W%t#PADP_L02_TXT@ S EV_ID2 EV_ID3 ... EV_ID4 ... 3-36 ... ... Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Message block ALARM_8P EV_ID5 Message number Block parameter Default message text Message class 7 - Device @1%d@/@2%d@/@3%d@: Module 22 @10W%t#PADP_L02_TXT@ S 1 - Device @1%d@/@2%d@/@3%d@: Module 24 @4W%t#PADP_L02_TXT@ S ... ... 7 - Device @1%d@/@2%d@/@3%d@: Module 30 @10W%t#PADP_L02_TXT@ S The message texts and their text numbers in the text library PADP_L02_TXT are listed in the Text Library for DP-/PA-Slaves after a PA-/Y-LINK DP V0 Assignment of the auxiliary process values for the block parameters of PADO_L02 Message block ALARM_8P EV_ID1 EV_ID2 EV_ID3 EV_ID4 EV_ID5 Value Block parameter Meaning 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 2-8) from PADP_L02_TXT 1 SUBN_ID DP Master system ID(byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1-8) from PADP_L02_TXT 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1-8) from PADP_L02_TXT 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1-8) from PADP_L02_TXT 1 SUBN_ID DP master system ID (byte) 2 RACK_NO Rack / Station number (byte) 3 PADP_ADR DP/PA device address (byte) 4 - Text number (Message 1) from PADP_L02_TXT If the PA field device is connected behind a DP/PA-Link V0 which is not connected and SUBN1_ID = 16#FF, SUBN2_ID is entered as the auxiliary process value. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-37 09.10.2001 PROFIBUS PA blocks 3.5.7 Connections of PADP_L0x The connections of the blocks PADP_L00, PADP_L01 and PADP_L02 are identical with the exception of the number of MODE_xx and OMODE_xx. The number of slots to be monitored determines the number of the respective input and outputs. The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O ACC_MODE 1=Accept New Mode Settings BOOL 0 I/O CPU_DIAG CPU diagnostics STRUCT I/O DPA_M Status Modules of DP/PA Slave STRUCT I EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I MODE_xx Mode Channel (xx = 00 - 06 / 00 - 15 / 00 - 31) WORD 0 I MSG_ACK Message Acknowledged WORD 0 O MSGSTAT Message Failure WORD 0 O OMODE_xx Mode Channel (xx = 00 - 06 / 00 - 15 / 00 - 31) DWORD 0 O PADP_ADR Address DP/PA field device BYTE 0 I QERR 1=Program Error BOOL 1 O QMODF 1=Module Withdrawn / Out of Order BOOL 0 O QRACKF 1=Rack/Station failure BOOL 0 O RAC_DIAG 1=DPV1 mode STRUCT 3.6 3.6.1 OC&M + + I/O DPAY_V0: Monitoring of DP/PA-Link and Y-Link as V0 slave DPAY_V0: Monitoring of DP/PA-Link and Y-Link as V0 slave Object name (Type + Number) FB 108 3-38 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Area of Application The block monitors the state of a DP/PA- or Y-Link as a V0 slave (IM157) and signals the corresponding error events. The DP/PA-Link is a PA master for the subordinate PA field devices and a slave at the DP bus. The Y-Link is a DP master for the subordinate DP field devices and a slave at the higher-level DP bus. Calling OBs The block has to be installed in the following OBs in the run sequence (is carried out automatically in CFC): OB1 Cyclic program OB70 I/O redundancy error OB72 CPU redundancy error OB82 Diagnostic interrupt OB85 Program execution error OB86 Rack failure OB100 Restart (warm start) If the CFC function "Generate Module Driver" is used, the block is installed in the run sequence behind the SUBNET block and before the PADP_L0x block and * * Configured - RACK_NO (Rack/Station number) - DADDR (Diagnostic address of the DP/PA-Link or Y-Link) - DPPA_xx (Slave xx address, 1st module (slot) address of the slave xx in the link, number of slots of the slave xx) Interconnection of - The OUT structures CPU_DIAG of the OB_BEGIN block and SUB_DIAG of the SUBNET block with the INOUT structures of the same name of the DPAY_V0. - In case of PA or DP field devices, PADP_L0x Function and Operating Principle The DPAY_V0 block generates a process control system fault message for the OS in case of redundancy losses and link failures. In addition it indicates faults within the link (SUBN1ERR, SUBN2ERR) and the preferred channel (SUBN1ACT, SUBN2ACT) when the links are activated at the output bar. The output structure RAC_DIAG contains the geographic address of the link as well as the group error information RACK_ERR. If RACK_ERR = 1, the corresponding link is not available. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-39 09.10.2001 PROFIBUS PA blocks The block requires an interfacing to the PROFIBUS DP. This can be integrated either in the CPU or be effected as an external DP interface (CP). The conversion of PROFIBUS DP to PROFIBUS PA is carried out by means of a SIMATIC DP/PALink. All the field devices of a link are only addressed via the DP address of the IM157 at the higher-level DP bus. The AS addresses the field devices via the link, meaning indirectly. The topological structure of the PA bus is mapped in the flat structure of the slave interface. A maximum of 64 field devices can be operated behind a link. Any number of virtual slots (maximum of 223) of the link can be assigned per field device. In order to assign the diagnostic data to the field devices, the block has an input structure (DPPA_xx) of 3 bytes per field device with the following meaning: 1. Byte (SLAV_NO) = User number (address) of the field device at the PA or DP Master system of the LINK 2. Byte (SLOT_NO) = 1st module address of the field device in the LINK 3. Byte (SLAV_SL) = Number of slots of the field device The CFC function "Generate Module Driver" imports these data from HW Config. The start information is read from the I/O structure CPU_DIAG. It has to be interconnected to the structure CPU_DIAG of the OB_BEGIN block (is implemented with the CFC function "Generate Module Driver" for you). The block generates a corresponding message (see Message behavior) on the basis of the start information of the calling OBs if the current instance is affected. The block determines the currently active preferred channel (SUBN1ACT, SUBN2ACT) in the case of redundant PROFIBUS DP interfaces by evaluating the error events and, if required, the diagnostic address ADDR of the link. The diagnostic data (OB82) are read with SFC 13 (DPNRM_DG, Diagnostic data consistent). The reading process can take several cycles (OB1). In rare cases it is therefore possible that the triggering diagnostic event cannot be recognized. The diagnostic user data contain information on the state of the link and the connected field devices. The state of the link is displayed in the structure DPPA_ST. The state of a field device is entered in the structure DPA_M_xx. A field device can have a maximum of 32 slots (module). Depending on the number of slots of a field device three block types are available: * PADP_L00 (field device with a maximum of 7 slots) * PADP_L01 (field device with a maximum of 16 slots) * PADP_L02 (field device with a maximum of 32 slots) The structure DPA_M_xx is interconnected to the structure DPA_M and the output EN_Mx with EN of one of the PADP_Lxx blocks (is carried out for you by the CFC function "Generate Module Driver"). The structure DPA_M_xx consists of two DWORD (S_01 for Module 1 to 16 and S_02 for Module 17 to 32) and one BOOL (S_ERR = DP/PA field device faulty). Two bits of the DWORD are assigned per slot of the DP/PA field device, whereby 3-40 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Bit 0 and Bit 1 belong to Slot 1 (Module 1) of the DP/PA field device, etc. They are defined as follows: State Bit 0 State Bit 1 Meaning 0 0 Module x OK (valid user data) 0 1 Module x fault (invalid user data) 1 0 Incorrect Module x (invalid user data) 1 1 No Module x (invalid user data) If the diagnostic interrupt applies for the complete DP/PA field device, DPA_M_xx.S_ERR = TRUE is set. If you want to change the inputs of the SUBNET block SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) online without using the CFC function "Generate Module Driver", you have to set the input ACC_ID = TRUE at the corresponding block. This checks the link states and updates the output values. Redundancy The block supports the redundancy of the DP Master systems at an H system (only distributed I/O devices). To this purpose the inputs of the SUBNET block SUBN1_ID (connection to CPU 0) and SUBN2_ID (connection to CPU 1) are to be configured with the numbers of the redundant DP Master systems. If there is no redundancy of the DP Master systems, the remaining input must have the value 16#FF (default) assigned. Error handling Error handling of the block is limited to the error information of ALARM_8P. Refer to Error information of the MSG_STAT output parameter Start-up characteristics The block initializes the messages of ALARM_8P. A check whether the link is available is carried out. In the case of H systems the preferred channel of the links is determined. Overload behavior The block counts the OB86 (no DP Master system failure, see SUBNET block) and OB82 calls. Both counters are reset in the OB1. If more than two OB86s or more than two OB82 events occur successively before the cycle checkpoint (OB1) is reached, these are rejected and either the message "Failure OB86 DP Master:x Rack:y" or the message "Failure OB82 DP Master:x Rack:y Slot: z" is emitted. If an OB86 is rejected, the DP/PA-Link / Y-Link is registered as failed. If an OB82 is rejected, the corresponding DP Slave is registered as failed. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-41 09.10.2001 PROFIBUS PA blocks Time response Does not exist Message characteristics After it has been called up by OB70, OB72, OB85 or OB86, the block analyses the state of the CPU, DP Master and link assigned to it. If necessary, it generates the corresponding messages for redundancy loss and failure of the link by emitting an ALARM_8P. The block generally only signals events whose cause lies within the link monitored by it. Redundancy losses and link failures which result from the failure of a DP Master or of a CPU, are initially neither signaled nor indicated at the outputs SUBN1ERR and SUBN2ERR. The DELAY input allows a signal delay, which can be configured, for an outgoing higher-order error. If, for example, the block recognizes an outgoing error in a DP master connected to it, it initially assumes that there is a faulty assigned DP slave in the link monitored by it and sets the corresponding output SUBNxERR. The error is not canceled until the DP slave returns (in this case: OB86, OB70). The blocks suppress the potential slave failure for DELAY seconds in order not to trigger a wave of messages from the DP slaves which are not synchronized yet after the master returns. An error message is not output to the OS unless a DP slave does not report its return before this period expires. You should not set the value of DELAY too high. Otherwise DP slaves which were removed during the master failure or which are defective will be reported back to the OS after the master returns with a correspondingly high delay period. The block generates the following messages in the OBs listed below: OB No. Starting event Message OB1 Cyclic processing Repeat updating ALARM_8P outputs / messages, if necessary OB70 Redundancy loss Link redundancy loss/return OB85 I/O access error Link failure going OB86 Rack monitoring Link failure coming/going OB100 Restart Initializing ALARM_8P 3-42 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Operator control and monitoring The block does not have a faceplate. Note In "Connection of DPAY V0" the variables are identified (with a "+" in the column OCM ) which are transferred from this instance block to the OS when the option "Operator C and M capability for diagnostic blocks" in the "Generate Module Driver" settings is selected. Default: option is not set. 3.6.2 Connections of DPAY_V0 The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection Meaning (parameter) Data type Initial I/O ACC_ID 1=Accept New ID Settings BOOL 0 I/O CPU_DIAG CPU diagnostics STRUCT DADDR Diagnostic Address of DP-Slave INT 0 I DELAY Alarm Delay (s) INT 15 I DPA_M_xx Status Modules of DP/PA Slave (xx = 00 - 63) STRUCT O DPPA_ST DP/PA-/Y-Link Status STRUCT O DPPA_xx Information of DP/PA-Slave (xx = 00 - 63) STRUCT I OC& M I/O EN_MSG 1=Enable Alarm BOOL 1 I EN_Mxx 1=Enable module (xx = 00 - 63) BOOL 0 O EV_ID Event ID DWORD 0 I MSG_STAT Message Failure WORD 0 O RAC_DIAG Rack diagnostic BOOL 0 O RACK_NO Rack/Station Number WORD 0 I SUB_DIAG OB_Start Information STRUCT I/O SUBN_TYP 1=External DP interface BOOL 0 I SUBN1_ID BYTE 255 I BOOL 0 O + + ID of Primary Subnet SUBN1ACT 1 = Slave 1 Active SUBN1ERR 1 = Subnet Failure of Primary Subnet BOOL 0 O SUBN2_ID BYTE 255 I SUBN2ACT 1 = Slave 2 Active BOOL 0 O + SUBN2ERR 1 = Subnet Failure of Primary Subnet BOOL 0 O + ID of Redundant Subnet Process Control System PCS 7, Driver Blocks A5E00127662-01 3-43 09.10.2001 PROFIBUS PA blocks 3.6.3 Message texts and auxiliary process values of DPAY_V0 Assignment of message text and message class Message No. Default message text Message class 1 DP-Link @1%d@/ @3%d@: Redundancy loss S 2 DP-Link @2%d@/ @3%d@: Redundancy loss S 3 DP-Link @1%d@/ @3%d@: Failure S 4 DP-Link @2%d@/ @3%d@: Failure S 5 - - 6 - - 7 - - 8 - - Assignment of the auxiliary values 3-44 Value Block parameter 1 Primary DP Master system ID (SUBN1_ID) 2 Redundant DP Master system ID (SUBN2_ID) 3 Rack/Station number (RACK_NO) Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks 3.7 PA_TOT: Totalizer PROFIBUS PA Object name (Type + Number) FB 102 Area of Application The block processes the cyclic parameters of the PA Profile "Totalizer" of a PA field device in accordance with PROFIBUS PA 3.0 Class A and B. Calling OBs The calling OB is the watchdog interrupt OB3x, in which you install the block (for example OB32) and OB1 and the restart OB100. Use in the CFC If the CFC function "Generate Module Driver" is used, the following steps are carried out automatically: * The installation of block in OB1 and OB100. * The symbol for the Quality Code of the analog input channel is interconnected to the input QC and other selected options. * The MODE input is interconnected to the corresponding output OMODE_xx of the PADP_L0x block. Function and Operating principle The block cyclically reads the process value (TOTAL) with status byte (Quality Code) of the PROFIBUS PA field device (structure in accordance with the Totalizer of the PA profiles) from the (part) process image. The process value exists as a physical value. The status byte contains information on the measured value and the state of the PROFIBUS PA field device or HART device. In order to improve the interconnectability further important detailed information in addition to the status byte as Boolean (BOOL) values is supplied at the output interface. They correspond to the bit combinations specified in the PROFIBUS PA 3.0 "General Requirements". Device-specific control system messages are generated via ALARM_8P on the basis of the status of the status byte. The quality code QUALITY for the process value is determined from the status of the input MODE and the output STATUS. PA MODE recognizes a higher level error e.g. DP/PA Link failure via the input MODE The block recognizes a higherlevel error (for example failure of DP/PA-Link) via the MODE input MODE. If the Process Control System PCS 7, Driver Blocks A5E00127662-01 3-45 09.10.2001 PROFIBUS PA blocks High Byte of the input MODE = 16#80, the values in the (part) process image are valid. If the High Byte of the MODE input = 16#40 (value status = higher-level error), the analog value is handled as invalid. The Quality Code (QUALITY) is set to 16#44 or 16#48. The same is true for a STATUS with status "BAD". Otherwise STATUS and QUALITY are identical. In case of a higher-level error no messages are generated Optionally the input variables SET_TOT and MODE_TOT can be written to the (part) process image. Addressing The symbol generated with HW Config in the symbol table for the analog input channel has to be interconnected to the TOTAL input . The symbol for the Quality Code of the analog input channel interconnects the CFC function "Generate Module Driver" with the input QC and, as far as they exist, the outputsO_SET_TOT and O_MODE_TOT for you. Simulation If the input parameter SIM_ON = TRUE, the value of the input SIM_V is output with Quality Code (QUALITY =) 16#60. Simulation has the highest priority. If there is a higher-level error, QBAD = FALSE is set. If the block is in simulation state, QSIM = TRUE is set. If there is no higher-level error and the PA field device displays a Quality Code "BAD", either the substitute value SUBS_V (SUBS_ON= TRUE) or the last value is output. Substitution value If the input parameter SUBS_ON = TRUE, the value of the input parameter SUBS_V is output as the value, in as far as the values are invalid. The Quality Code is set to (QUALITY =) 16#48 and QBAD = 1. Hold last value If the input parameter SUBS_ON = FALSE, the last valid output parameter is output if the values are invalid. The Quality Code is set to (QUALITY =) 16#44 and QBAD = 1. Value limiting You can limit very low or very high process values from the (part) process image. If the switch LIMIT_ON = TRUE, the process values (V) are limited: 3-46 - To V_HL, if V > V_HL. - To LL_V, if V < V_LL. Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Error handling No plausibility checks are carried out with reference to the input parameters. Start-up characteristics Input MODE = 16#xx01xxxx: Initializing ALARM_8P. Time response Does not exist. Message characteristics As long as there is no higher-level error, the block signals the current state of the Quality Code (status byte) when there is a change. The messages are event messages which do not have to be acknowledged and are only stored in the chronic list of the OS. If the QBAD and QUNCERT outputs are interconnected to the CSF input (external error) of the technological block, this block generates a control system message if a malfunction arises. The DELAY input (default setting 2 seconds) is used to delay an event message when there is a change in the Quality Code. With DELAY you can specify the period in seconds which the block waits when there is a change in the Quality Code after a higher-level error (DP Master system failure, DP/PA-Link failure, device failure or I/O access error), (MODE = 16#40xxxxxx) has gone, until it emits the message. Messaging can be de-activated by using EN_MSG = FALSE. Operator control and monitoring The block does not have a faceplate. Process Control System PCS 7, Driver Blocks A5E00127662-01 3-47 09.10.2001 PROFIBUS PA blocks 3.7.1 Connections of PA_TOT The state of delivery of the block display in the CFC is marked in the "Connection" column: Connection name bold = Connection displayed, normal = Not displayed. Connection (parameter) Meaning Data type Initial I/O DELAY Alarm Delay (s) INT 2 I EN_MSG 1=Enable Alarm BOOL 1 I EV_ID Event ID DWORD 0 I LIMIT_ON 1=Limit on Input Value BOOL 0 I LL_V High Limit Input Value. Set Value if V < V_LL REAL 0 I MODE MODE Input parameter DWORD 0 I/O MODE_TOT Mode Totalizer 0=Balanced, 1=pos_only, 2=neg_only, 3=hold BYTE 0 I MSG_STAT Message Failure WORD 0 O O_SET_TOT Totalize Algorithm BYTE 0 O O_MODE_TOT Totalizer Mode BYTE 0 O QA_1 1 = Alarm/Warning 1 BOOL 0 O QA_2 1 = Alarm/Warning 2 BOOL 0 O QBAD 1 = Collected event QBAD_X BOOL 0 O QBAD_0 1 = Non-specific BOOL 0 O QBAD_1 1 = Configuration error BOOL 0 O QBAD_2 1 = Not connected BOOL 0 O QBAD_3 1 = Device failure BOOL 0 O QBAD_4 1 = Sensor failure BOOL 0 O QBAD_5 1 = No communication (last usable value) BOOL 0 O QBAD_6 1 = No communication (no usable value) BOOL 0 O QBAD_7 1 = Out of service BOOL 0 O QBAD_HL 1 = High limit upper physical range of sensor has been reached BOOL 0 O QBAD_LL 1 = Low limit lower physical range of sensor has been reached BOOL 0 O QC Input Process Value Quality Code BYTE O I QCASCAD0 1 = OK (cascade) BOOL 0 O QCASCAD1 1 = Initialization acknowledged BOOL 0 O QCASCAD2 1 = Initialization request BOOL 0 O QCASCAD3 1 = Not requested BOOL 0 O QCASCAD4 1 = Reserved BOOL 0 O QCASCAD5 1 = Do not select BOOL 0 O QCASCAD6 1 = Local override BOOL 0 O QCASCAD7 1 = Reserved BOOL 0 O QCASCAD8 1 = Initiate fail safe BOOL 0 O QCONST 1 = Constant BOOL 0 O QERR 1 = Error output (inverted value of ENO) BOOL 1 O QOUT_HHL 1 = Active critical alarm, high limit of OUT has been exceeded BOOL 0 O 3-48 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 PROFIBUS PA blocks Connection (parameter) Meaning Data type Initial I/O QOUT_HL 1 = Active advisory alarm, high limit of OUT has been exceeded BOOL 0 O QOUT_LL 1 = Active advisory alarm, low limit of OUT has been exceeded BOOL 0 O QOUT_LLL 1 = Active critical alarm, low limit of OUT has been exceeded BOOL 0 O QNONCAS0 1 = OK (non-cascade) BOOL 0 O QNONCAS1 1 = Update event BOOL 0 O QNONCAS2 1 = Active advisory alarm (priority <8) BOOL 0 O QNONCAS3 1 = Active critical alarm (priority >8) BOOL 0 O QNONCAS4 1 = Unacknowledged update event BOOL 0 O QNONCAS5 1 = Unacknowledged advisory alarm BOOL 0 O QNONCAS6 1 = Unacknowledged critical alarm BOOL 0 O QNONCAS7 1 = Initial fail safe BOOL 0 O QNONCAS8 1 = Maintenance required BOOL 0 O QSIM 1 = Simulation Active BOOL 0 O QSUBS 1 = Failure Substitution Active BOOL 0 O QUALITY Value status of the process value BYTE 0 O QUNCERT 1 = Collected event QUNCERTx BOOL 0 O QUNCERT0 1 = Non-specific BOOL 0 O QUNCERT1 1 = Last usable value BOOL 0 O QUNCERT2 1 = Substitute set BOOL 0 O QUNCERT3 1 = Initial value BOOL 0 O QUNCERT4 1 = Sensor conversion not accurate BOOL 0 O QUNCERT5 1 = Engineering unit violation (unit not in the valid set) BOOL 0 O QUNCERT6 1 = Sub-normal BOOL 0 O QUNCERT7 1 = Configuration error BOOL 0 O QUNCERT8 1 = Sensor calibration BOOL 0 O QUNCERT9 1 = Simulated value BOOL 0 O SET_TOT Algorithm 0=Totalize, 1=Reset assign 0, 2=preset assign PRESET_TOT BYTE 0 I SIM_ON 1 = Activate Simulation BOOL 0 I SIM_V Simulation Value REAL 0 I STATUS Process Value Status BYTE 0 O SUBS_ON 1 = Enable Failure Substitution BOOL 0 I SUBS_V Substitution Value REAL 0 I TOTAL Input Value REAL 0 I V Process Value REAL 0 O V_HL High Limit Input Value REAL 0 I V_LL Low Limit Input Value REAL 0 I Process Control System PCS 7, Driver Blocks A5E00127662-01 3-49 09.10.2001 PROFIBUS PA blocks 3.7.2 Message texts and auxiliary process values of PA_TOT Assignment of message texts and classes to the block parameters of PA_TOT Message block ALARM_8P EV_ID Message number Default message text Message class 1 QBAD Device failure S 2 QUNCERT Uncertain value S 3 QNONCAS1 Update event S 4 QNONCAS7 Initiate fail safe S 5 QNONCAS8 Maintenance required M 6 QOUT_LLL Lower alarm AL 7 QOUT_HHL Upper alarm AH 8 3-50 Block parameter No message Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 A A.1 Appendix Addressing If you do not use the CFC function "Generate Module Driver", you have to set the logical basic address of the module created with HW Config at the input LADDR. If the input SUBN_TYP = FALSE, the RACK of the module is connected to an integrated DP interface (distributed I/O device interface) of the CPU module by means of a line. Otherwise set SUBN_TYP = TRUE. The following points are generally to be observed for all the SM and PA modules: * In the case of pure input modules, that is modules which write data exclusively into the input range of the CPU process image the basic address can be taken directly from HW Config., for example: the module SM331 AI 8x12Bit 331-7KF01-0AB0: Address input range HW Config Address output range HW Config LADDR (decimal / hex) 512 - 512 / 16#0200 * In the case of pure output modules, that is modules which read data exclusively from the output range of the CPU process image, the MSB (most significant bit) has to be set in the basic address from HW Config.; for example the module SM332 AO 4x12Bit 332-5HD01-0AB0: Address input range HW Config Address output range HW Config LADDR (decimal / hex) - 512 -32256 / 16#8200 Process Control System PCS 7, Driver Blocks A5E00127662-01 A-1 09.10.2001 04.10.2001 Appendix A.2 Error information of the MSG_STAT output parameter The messages can be de-activated via the input EN_MSG = FALSE (output parameter MSG_STAT(_x) remains unchanged). The ALARM8_P(_x) block is called in the acyclic OBs and OB1 if message suppression has not been suppressed Error information of the ALARM_8P(_x) (messages cannot be emitted) is displayed in the output parameter MSG_STAT(_x). The error information of the output parameter MSG_STAT and of the acknowledgment word MSG_ACK(_x) of ALARM8_8P is described in the on-line help for SSFB35 (ALARM_8P). A.3 MODE settings for Signal Modules Measuring range coding of the analog input module Depending on the coding of the measuring range of the analog input modules, the parameter MODE_xx (measuring range coding) corresponding to the channel must be specified in accordance with the table. When thermoelements are used (due to the various combinations of the measuring type (Coding A) with the measuring range (Coding B)) this is to be calculated in accordance with the following formula and the result then entered as an INTEGER value at the MODE input: MODE = 256 Coding A + Coding B Please note that in the table Codings A and B are binary encoded and that the result is shown as the MODE parameter as a hexadecimal number. Measuring type Coding (A) Measuring range Voltage 2#0001 4-wire measuring transducer A-2 2#0010 Coding (B) MODE (256A+B) 25 mV 2#1010 16#010A 50 mV 2#1011 16#010B 80 mV 2#0001 16#0101 250 mV 2#0010 16#0102 500 mV 2#0011 16#0103 1V 2#0100 16#0104 2.5 V 2#0101 16#0105 5V 2#0110 16#0106 1 to 5 V 2#0111 16#0107 10 V 2#1001 16#0109 100 V 2#1100 16#010C 3.2 mA 2#0000 16#0200 5 mA 2#0101 16#0205 10 mA 2#0001 16#0201 0 to 20 mA 2#0010 16#0202 4 to 20 mA 2#0011 16#0203 20 mA 2#0100 16#0204 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Appendix Measuring type Coding (A) Measuring range Coding (B) MODE (256A+B) HART interface 2#0111 4 to 20 mA 2#1100 16#070C 2-wire measuring transducer 2#0011 4 to 20 mA 2#0011 16#0303 Resistor 4-wire connection 2#0100 48 2#0000 16#0400 150 2#0010 16#0402 300 2#0100 16#0404 600 2#0110 16#0406 6000 2#1000 16#0408 48 2#0000 16#0500 150 2#0010 16#0502 300 2#0100 16#0504 600 2#0110 16#0506 6000 2#1000 16#0508 48 2#0000 16#0600 150 2#0010 16#0602 300 2#0100 16#0604 600 2#0110 16#0606 6000 2#1000 16#0608 Pt 100 climate range 2#0000 16#0800 Pt 200 climate range 2#0111 16#0807 Pt 500 climate range 2#1000 16#0808 Resistor 3-wire connection Resistor 2-wire connection Thermal resistor + linearization 4-wire connection Thermal resistor + linearization 3-wire connection 2#0101 2#0110 2#1000 2#1001 Process Control System PCS 7, Driver Blocks A5E00127662-01 Pt 1000 climate range 2#1001 16#0809 Ni 100 climate range 2#0001 16#0801 Ni 1000 climate range 2#1010 16#080A Pt 100 standard range 2#0010 16#0802 Pt 200 standard range 2#0011 16#0803 Pt 500 standard range 2#0100 16#0804 Pt 1000 standard range 2#0101 16#0805 Ni 100 standard range 2#1011 16#080B Ni 1000 standard range 2#0110 16#0806 Ni 120 standard range 2#1100 16#080C Ni 120 climate range 2#1101 16#080D Cu10 climate range 2#1110 16#080E Cu10 standard range 2#1111 16#080F Ni 200 standard range 2#10000 16#0810 Ni 200 climate range 2#10001 16#0811 Ni 500 standard range 2#10010 16#0812 Ni 500 climate range 2#10011 16#0813 Pt 100 climate range 2#0000 16#0900 Pt 200 climate range 2#0111 16#0907 Pt 500 climate range 2#1000 16#0908 A-3 09.10.2001 04.10.2001 Appendix Measuring type Coding (A) Measuring range Pt 1000 climate range Thermal resistor + linearization 2-wire connection A-4 2#1100 Coding (B) MODE (256A+B) 2#1001 16#0909 Ni 100 climate range 2#0001 16#0901 Ni 1000 climate range 2#1010 16#090A Pt 100 standard range 2#0010 16#0902 Pt 200 standard range 2#0011 16#0903 Pt 500 standard range 2#0100 16#0904 Pt 1000 standard range 2#0101 16#0905 Ni 100 standard range 2#1011 16#090B Ni 1000 standard range 2#0110 16#0906 Ni 120 standard range 2#1100 16#090C Ni 120 climate range 2#1101 16#090D Cu10 climate range 2#1110 16#090E Cu10 standard range 2#1111 16#090F Ni 200 standard range 2#10000 16#0910 Ni 200 climate range 2#10001 16#0911 Ni 500 standard range 2#10010 16#0912 Ni 500 climate range 2#10011 16#0913 Pt 100 climate range 2#0000 16#0C00 Pt 200 climate range 2#0111 16#0C07 Pt 500 climate range 2#1000 16#0C08 Pt 1000 climate range 2#1001 16#0C09 Ni 100 climate range 2#0001 16#0C01 Ni 1000 climate range 2#1010 16#0C0A Pt 100 standard range 2#0010 16#0C02 Pt 200 standard range 2#0011 16#0C03 Pt 500 standard range 2#0100 16#0C04 Pt 1000 standard range 2#0101 16#0C05 Ni 100 standard range 2#1011 16#0C0B Ni 1000 standard range 2#0110 16#0C06 Ni 120 standard range 2#1100 16#0C0C Ni 120 climate range 2#1101 16#0C0D Cu10 climate range 2#1110 16#0C0E Cu10 standard range 2#1111 16#0C0F Ni 200 standard range 2#10000 16#0C10 Ni 200 climate range 2#10001 16#0C11 Ni 500 standard range 2#10010 16#0C12 Ni 500 climate range 2#10011 16#0C13 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Appendix Measuring type Coding (A) Measuring range Coding (B) MODE (256A+B) Thermocouples internal comparison 2#1010 Type B [PtRh-PtRh] 2#0000 16#0A00 Type N [NiCrSi-NiSi] 2#0001 16#0A01 Type E [NiCr-CuNi] 2#0010 16#0A02 Type R [PtRh-Pt] 2#0011 16#0A03 Type S [PtRh-Pt] 2#0100 16#0A04 Type J [Fe-CuNi IEC] 2#0101 16#0A05 Type L [Fe-CuNi DIN] 2#0110 16#0A06 Type T [Cu-CuNi IEC] 2#0111 16#0A07 Type K [NiCr-Ni] 2#1000 16#0A08 Thermocouples external comparison Thermocouples + linearization internal comparison Thermocouples + linearization external comparison 2#1011 2#1101 2#1110 Process Control System PCS 7, Driver Blocks A5E00127662-01 Type U [Cu-CuNi DIN] 2#1001 16#0A09 Type B [PtRh-PtRh] 2#0000 16#0B00 Type N [NiCrSi-NiSi] 2#0001 16#0B01 Type E [NiCr-CuNi] 2#0010 16#0B02 Type R [PtRh-Pt] 2#0011 16#0B03 Type S [PtRh-Pt] 2#0100 16#0B04 Type J [Fe-CuNi IEC] 2#0101 16#0B05 Type L [Fe-CuNi DIN] 2#0110 16#0B06 Type T [Cu-CuNi IEC] 2#0111 16#0B07 Type K [NiCr-Ni] 2#1000 16#0B08 Type U [Cu-CuNi DIN] 2#1001 16#0B09 Type B [PtRh-PtRh] 2#0000 16#0D00 Type N [NiCrSi-NiSi] 2#0001 16#0D01 Type E [NiCr-CuNi] 2#0010 16#0D02 Type R [PtRh-Pt] 2#0011 16#0D03 Type S [PtRh-Pt] 2#0100 16#0D04 Type J [Fe-CuNi IEC] 2#0101 16#0D05 Type L [Fe-CuNi DIN] 2#0110 16#0D06 Type T [Cu-CuNi IEC] 2#0111 16#0D07 Type K [NiCr-Ni] 2#1000 16#080D Type U [Cu-CuNi DIN] 2#1001 16#090D Type B [PtRh-PtRh] 2#0000 16#0E00 Type N [NiCrSi-NiSi] 2#0001 16#0E01 Type E [NiCr-CuNi] 2#0010 16#0E02 Type R [PtRh-Pt] 2#0011 16#0E03 Type S [PtRh-Pt] 2#0100 16#0E04 Type J [Fe-CuNi IEC] 2#0101 16#0E05 Type L [Fe-CuNi DIN] 2#0110 16#0E06 Type T [Cu-CuNi IEC] 2#0111 16#0E07 Type K [NiCr-Ni] 2#1000 16#080E Type U [Cu-CuNi DIN] 2#1001 16#090E A-5 09.10.2001 04.10.2001 Appendix Measuring range coding of the analog output modules Depending on the coding of the measuring range of the analog output modules, the parameter MODE_xx (measuring range coding) corresponding to the channel must be specified in accordance with the table. Measuring type Voltage Current HART interface Measuring range MODE 1 to 5 V 16#0107 0 to 10 V 16#0108 10 V 16#0109 0 to 20 mA 16#0202 4 to 20 mA 16#0203 20 mA 16#0204 4 to 20 mA 16#070C Measuring range coding of the digital input and digital output modules There is neither a measuring type nor a measuring range for digital input and digital output modules: MODE = 16#FFFF (at DI) MODE = 16#FFFE (at DO) OMODE structure The outputs OMODE_xx of data type DWORD are structured as follows and have the following meaning: Byte 3: 16#80: Value status "valid value" 16#20: Value status "valid value" 16#00: Value status "invalid value" 16#40: Value status "invalid value" (redundancy error) (channel error) (higher-level error) Byte 2: 16#01: Restart (OB100) has been carried out Byte 1, 0 (Low Word): MODE (see above) Example: 16#80010203 corresponds to value state "valid value", restart has been carried out, current 4 to 20mA A-6 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Appendix A.4 MODE settings for PA Devices MODE_xx inputsare available for a maximum of 32 slots of a PA field device. Their initial value is zero (no reading/writing). Per Slot xx you have to set the selected combination of the options of the PROFIBUS PA 3.0 - Profile at the MODE_xx input: Block Connection (parameter) (cyclic data) Input (I) / Output (O) (PLS view) MODE 16#xxyy, O=xx I=yy I 16#0001 permitted combination and sequence Analog Input (PA_AI) OUT Totalizer (PA_TOT) TOTAL I 16#000F Totalizer (PA_TOT) TOTAL SET_TOT I O 16#070F Totalizer (PA_TOT) TOTAL SET_TOT MODE_TOT I O O 16#080F Analog Output (PA_AO) SP O 16#0100 Analog Output (PA_AO) SP READBACK POS_D O I I 16#0103 Analog Output (PA_AO) SP CHECK_BACK O I 16#0104 Analog Output (PA_AO) SP READBACK POS_D CHECK_BACK O I I I 16#0105 Analog Output (PA_AO) RCAS_IN, RCAS_OUT O I 16#0206 Analog Output (PA_AO) RCAS_IN, RCAS_OUT, CHECK_BACK O I I 16#0207 Analog Output (PA_AO) SP RCAS_IN READBACK RCAS_OUT POS_D CHECK_BACK O O I I I I 16#0308 Discrete Input (PA_DI) OUT_D I 16#0002 Discrete Output (PA_DO) SP_D O 16#0400 Discrete Output (PA_DO) SP_D READBACK_D O I 16#0409 Discrete Output (PA_DO) SP_D CHECKBACK_D O I 16#040A Discrete Output (PA_DO) SP_D READBACK_D CHECK_BACK_D O I I 16#040B Discrete Output (PA_DO) RCAS_IN_D RCAS_OUT_D O I 16#050C Process Control System PCS 7, Driver Blocks A5E00127662-01 A-7 09.10.2001 04.10.2001 Appendix Block Connection (parameter) (cyclic data) Input (I) / Output (O) (PLS view) MODE 16#xxyy, O=xx I=yy permitted combination and sequence Discrete Output (PA_DO) RCAS_IN_D RCAS_OUT_D CHECK_BACK_D O I I 16#0D05 Discrete Output (PA_DO) SP_D RCAS_IN_D READBACK_D RCAS_OUT_D CHECK_BACK_D O O I I I 16#0E06 A.5 Text Library for Signal Modules The event class/event ID, their message texts and text IDs of the text libraries MOD_1_TXT / MOD_2_TXT / MOD_D1_TXT and MOD_D2_TXT are summarized in the following table: Text ID. Event class / ID Message text Remark 1 08/50, 08/60, 08/70, 08/80 Configuration error 2 08/51, 08/61 Common mode error 3 08/52, 08/62, 08/72, 08/82 P short circuit 4 08/53, 08/63, 08/73, 08/83 M short circuit 5 08/54, 08/64, 08/74, 08/84 Wire breakage 6 08/55 Reference channel error 7 08/56 Below measuring range 8 08/57 Above measuring range 9 08/66, 08/86 Load voltage missing 10 08/71, 08/81 Mass error 11 08/75 Sensor supply missing 12 08/87 Over-temperature 13 08/00 Module OK 14 08/01 Internal error 15 08/02 External error 16 08/04 External auxiliary voltage missing 17 08/05 Front connector missing 18 08/06 No configuration 19 08/07 False parameter in BG 20 08/30 False/Missing user module 21 08/31 Communication error 22 08/32 Operating mode RUN/STOP 23 08/33 Time-check operates A-8 STOP: incoming, RUN: outgoing Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Appendix Text ID. Event class / ID Message text 24 08/34 Failed BG-int. Supply voltage 25 08/35 Battery 1 empty Remark 26 08/36 Standby supply fails 27 08/41 Processor failure 28 08/42 EPROM error 29 08/43 RAM error 30 08/44 ADU/DAU error 31 08/45 Fuse blown 32 08/46 Process interrupt lost 33 03/61 withdrawn EV_CLAS = 16#39 34 03/61 plugged EV_CLAS = 16#38 35 03/63 false BG type plugged EV_CLAS = 16#39 36 03/64 faulty BG plugged EV_CLAS = 16#39 37 03/65 BG plugged (Param.error) EV_CLAS = 16#39 38 Chatter error 39 Changeover contact diagnostics A.6 Text Libraries for DP-/PA-Slaves after a PA-/Y-LINK DP V0 PADP_L00_TXT PADP_L01_TXT PADP_L02_TXT Text ID. Message text 1 Module error 2 False module 3 Module missing Process Control System PCS 7, Driver Blocks A5E00127662-01 A-9 09.10.2001 04.10.2001 Appendix A.7 Technical data The column headings have the following meaning: Block type name The symbolic identifier in the symbol table of the library for the respective FB or FC. FC It must be unique within the project. Object name The object name consists of the block type (FB, FC) and the number. Typical Execution Time The time which the CPU needs to process the corresponding block program under normal circumstances (for example, for a driver this is the execution time in the watchdog interrupt organization block (OB3x) without message generation in the event of channel errors). The table below shows the execution times of the blocks in a 417-4H CPU (6ES7 417-4HL01-0AB0). With other CPUs the run time depends on their performance. Block Length in Load/Work Memory Memory requirements of the program code, with each block type having unique requirements. Length of the Instance Data in Load/Work Memory Memory requirement of an instance DB. Length of the Local Data The local-data memory required in the OB when the block is called. This is limited CPU-specifically. When it is exceeded, a CPU STOP is caused. The local data requirements are checked in CFC when you compile/download and downloading is prevented if there is not enough local data memory. A-10 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Appendix Block Outputs Messages Where "yes" is indicated for a block, this means that the block outputs messages. Block Type Name (Object Name) Typical Executio n Time CPU 4174H [ ms ] Block Length in Load/Work Memory [ bytes ] CH_AI (FC 275) 0,080 5484 / 4724 Length of the Instance Data in Load /Work Memory [ bytes ] Length of the Local Data [ bytes ] Block Outputs Messag es 28 CH_AO (FC 276) 0,060 1696 / 1436 28 CH_DI (FC 277) 0,035 418 / 314 4 CH_DO (FC 278) 0,025 330 / 248 2 CH_U_AI (FC 283) 0,065 5036 / 4340 30 CH_U_AO (FC 284) 0,050 1472 / 1254 28 CH_U_DI (FC 285) 0,024 658 / 512 4 CH_U_DO (FC 286) 0,018 522 / 416 IM_DRV (FB 90) 0,300 13090 / 10398 5938 / 4056 2 112 yes MOD_1 (FB 91) 0,400 4584 / 3580 1080 / 326 60 yes MOD_2 (FB 92) 0,600 4982 / 3912 1240 / 422 58 yes MOD_D1 (FB 93) 0,400 12876 / 10960 1724 / 666 68 yes MOD_D2 (FB 94) 0,600 13092 / 11052 2396 / 1070 70 yes OB_BEGIN (FB 100) 0,500 20470 / 17092 6164 / 3632 208 yes OB_END (FC 280) 0,010 514 / 86 4 OB_DIAG (FC 281) 0,080 5148 / 4266 DPAY_V0 (FB 108) 0,900 9986 / 7362 3568 / 1374 86 PADP_L00 (FB 109) 0,220 3564 / 2728 PADP_L01 (FB 110) 0,900 4704 / 3662 PADP_L02 (FB 111) 1,000 PA_AI (FB 101) PA_AO (FB 103) PA_DI (FB 104) 0,080 PA_DO (FB 105) 0,120 2804 / 2392 PA_TOT (FB 102) 0,100 2176 / 1814 134 yes 888 / 254 40 yes 1394 / 570 40 yes 6330 / 5040 1992 / 944 40 yes 0,100 2046 / 1706 504 / 222 12 yes 0,140 3058 / 2592 636 / 272 18 yes 1782 / 1488 440 / 192 12 yes 552 / 218 18 yes 520 / 226 18 yes PO_UPDAT (FC 279) - 324 / 252 RACK (FB 107) 0,300 8366 / 7048 1108 / 236 100 yes SUBNET (FB 106) 0,800 5374 / 4132 1146 / 214 106 yes Process Control System PCS 7, Driver Blocks A5E00127662-01 10 A-11 09.10.2001 04.10.2001 Appendix A-12 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Index A Addressing .................................................... A-1 Analog Input PROFIBUS PA ..........................3-1 Analog Output PROFIBUS PA .......................3-6 Analog value output................... 2-66, 2-80, 2-82 AS ...........................................................2-2, 2-3 Assignment of the control system messages of the OB_BEGIN .......................................2-6 Auxiliary process values...............................3-22 B Block description ............................................1-3 General information on...............................1-2 C CH_AI..................................................2-62, 2-64 Connections .............................................2-64 CH_AO................................................2-66, 2-69 Connections .............................................2-69 CH_DI .................................................2-70, 2-72 Connections .............................................2-72 CH_DO................................................2-73, 2-75 Connections .............................................2-75 CH_U_AI .............................................2-78, 2-80 CH_U_AO ................................. 2-82, 2-83, 2-85 Connections .............................................2-85 CH_U_DI.............................................2-86, 2-89 Connections .............................................2-89 CH_U_DO ...........................................2-90, 2-93 Connections .............................................2-93 Connections ............... 2-2, 2-5, 2-11, 2-14, 2-19, .................. 2-24, 2-31, 2-39, 2-51, 2-64, 2-69, .................. 2-72, 2-75, 2-80, 2-85, 2-89, 2-93, .............. 3-4, 3-9, 3-15, 3-20, 3-38, 3-43, 3-48 CH_U_AO ................................................2-85 CH_U_DI ..................................................2-89 CH_U_DO ................................................2-93 MOD_1 / MOD_2......................................2-39 MOD_D1 / MOD_D2 ................................2-51 PADP_L0x................................................3-38 Connections of CH_AI..................................2-64 Connections of CH_AO ................................2-69 Connections of CH_DI..................................2-72 Connections of CH_DO................................2-75 Connections of DPAY_V0 ............................3-43 Connections of IM_DRV...............................2-31 Connections of MOD_1 / MOD_2.................2-39 Process Control System PCS 7, Driver Blocks A5E00127662-01 Connections of MOD_D1 / MOD_D2 ........... 2-51 Connections of OB_BEGIN............................ 2-5 Connections of OB_DIAG ............................ 2-14 Connections of OB_END ............................. 2-11 Connections of PA_AI.................................... 3-4 Connections of PA_AO.................................. 3-9 Connections of PA_DI ................................. 3-15 Connections of PA_DO................................ 3-20 Connections of PA_TOT .............................. 3-48 Connections of PADP_L00 / L01 / L02 ........ 3-38 Connections of RACK.................................. 2-24 Connections of SUBNET ............................. 2-19 CPU .............. 2-1, 2-2, 2-3, 2-4, 2-12, 2-13, 2-14 D Digital value input ............................... 2-70, 2-86 Discrete Input PROFIBUS PA...................... 3-13 Discrete Output PROFIBUS PA................... 3-17 DP Master........................................... 2-17, 2-18 DP/PA ........................................ 3-23, 3-27, 3-32 Monitoring .............................. 3-23, 3-27, 3-32 DP/PA-Link .................................................. 3-38 Monitoring ................................................ 3-38 DP-/PA-Slaves after....................................... A-9 Text Libraries ............................................. A-9 DPAY_V0................................... 3-39, 3-43, 3-44 Auxiliary process values .......................... 3-44 Connections............................................. 3-43 Message texts.......................................... 3-44 Message texts and auxiliary process values .................................................. 3-44 E Error information of the MSG_STAT output parameter .................................................. A-2 G General information on .................................. 1-2 block description ........................................ 1-2 General information on the block description. 1-2 I IM 153-2....................................................... 2-33 IM_DRV ..................................... 2-28, 2-29, 2-31 Auxiliary process values .......................... 2-31 Connections............................................. 2-31 Message texts.......................................... 2-31 Interface IM153-2......................................... 2-33 Index-1 09.10.2001 04.10.2001 Index M Message texts and auxiliary process values .............2-20, 2-24, 2-31, 2-40, .................... 2-52, 2-59, 3-6, 3-12, 3-17, 3-22, .............................3-27, 3-31, 3-36, 3-44, 3-50 DPAY_V0................................................. 3-44 MOD_1 / MOD_2 ..................................... 2-40 MOD_D1 .................................................. 2-52 MOD_D2 .................................................. 2-59 PA_AI......................................................... 3-6 PA_AO ..................................................... 3-12 PA_DI ...................................................... 3-17 PA_DO..................................................... 3-22 PA_TOT ................................................... 3-50 PADP_L00 ............................................... 3-27 PADP_L01 ............................................... 3-31 PADP_L02 ............................................... 3-36 RACK ....................................................... 2-25 SUBNET .................................................. 2-20 Message texts and auxiliary process values of DPAY_V0 .................... 3-44 Message texts and auxiliary process values of MOD_1 / MOD_2 ........ 2-40 Message texts and auxiliary process values of MOD_D1 ..................... 2-52 Message texts and auxiliary process values of MOD_D2 ..................... 2-59 Message texts and auxiliary process values of PA_AI............................ 3-6 Message texts and auxiliary process values of PA_AO ........................ 3-12 Message texts and auxiliary process values of PA_DI.......................... 3-17 Message texts and auxiliary process values of PA_DO ........................ 3-22 Message texts and auxiliary process values of PA_TOT ...................... 3-50 Message texts and auxiliary process values of PADP_L00 .................. 3-27 Message texts and auxiliary process values of PADP_L01 .................. 3-31 Message texts and auxiliary process values of PADP_L02 .................. 3-36 Message texts and auxiliary process values of RACK .......................... 2-24 Message texts and auxiliary process values of SUBNET...................... 2-20 Message texts and auxiliary process values of the IM_DRV................. 2-31 MOD_1 ....................2-36, 2-37, 2-39, 2-40, 2-41 Auxiliary process values .......................... 2-40 connections.............................................. 2-39 Message texts................................. 2-40, 2-41 MOD_1 / MOD_2 ................................ 2-39, 2-40 Connections ............................................. 2-39 Message texts and auxiliary process values ..................................... 2-40 MOD_2 .............................2-39, 2-40, 2-42, 2-45 Auxiliary process values .......................... 2-41 Connections ............................................. 2-39 Index-2 Message texts ..........................................2-40 MOD_D1 ................. 2-46, 2-48, 2-50, 2-51, 2-52 Auxiliary process values ...........................2-53 Connections .............................................2-51 Message texts ..........................................2-52 Message texts and auxiliary process values .....................................2-52 MOD_D1 / MOD_D2.....................................2-51 Connections .............................................2-51 MOD_D2 .......................... 2-51, 2-54, 2-58, 2-59 Auxiliary process values ...........................2-60 Connections .............................................2-51 Message texts ..........................................2-59 Message texts and auxiliary process values .....................................2-59 MODE............................................. A-2, A-6, A-7 MODE setting ................................................ A-7 PA.............................................................. A-7 MODE settings .......................................A-2, A-7 PA Devices................................................ A-7 Signal Modules.......................................... A-2 MODE settings for PA Devices...................... A-7 MODE settings for Signal Modules................ A-2 Monitoring............... 2-38, 2-43, 2-47, 2-48, 2-55, ..................................... 3-23, 3-27, 3-32, 3-38 DP/PA......... 3-23, 3-24, 3-28, 3-29, 3-32, 3-34 DP/PA-Link............................ 3-39, 3-40, 3-41 S7-300/400 SM............. 2-36, 2-41, 2-45, 2-53 MSG_STAT ................................................... A-2 N Notes on Using Driver Blocks.........................1-1 O OB ................................................................2-13 OB_BEGIN ......2-1, 2-2, 2-3, 2-5, 2-6, 2-10, 2-11 Connections ...............................................2-5 Control system messages .... 2-6, 2-7, 2-8, 2-9 OB_DIAG .................................. 2-12, 2-13, 2-14 Connections .............................................2-14 OB_END............................................. 2-10, 2-11 Connections .............................................2-11 P PA Devices.................................................... A-7 MODE settings .......................................... A-7 PA-/Y-LINK DP V0......................................... A-9 PA_AI .............................................. 3-1, 3-4, 3-6 Auxiliary process values .............................3-6 Connections ...............................................3-4 Message texts ............................................3-6 Message texts and auxiliary process values .......................................3-6 PA_AO .......................................... 3-6, 3-9, 3-12 Auxiliary process values ...........................3-12 Connections ...............................................3-9 Message texts ..........................................3-12 Process Control System PCS 7, Driver Blocks A5E00127662-01 09.10.2001 04.10.2001 Index Message texts and auxiliary process values .....................................3-12 PA_DI........................................ 3-13, 3-15, 3-17 Auxiliary process values...........................3-17 Connections .............................................3-15 Message texts ..........................................3-17 Message texts and auxiliary process values .....................................3-17 PA_DO ...................................... 3-17, 3-20, 3-22 Connections .............................................3-20 Message texts ..........................................3-22 Message texts and auxiliary process values .....................................3-22 PA_DO .....................................................3-22 PA_MODE..................................................... A-7 Setting ....................................................... A-7 PA_TOT .................................... 3-45, 3-48, 3-50 Auxiliary process values...........................3-50 Connections .............................................3-48 Message texts ..........................................3-50 Message texts and auxiliary process values .....................................3-50 PADP_L00 ................................ 3-23, 3-24, 3-27 Auxiliary process values...........................3-27 Message texts ..........................................3-27 Message texts and auxiliary process values .....................................3-27 PADP_L00/ L01/ L02....................................3-38 Connections .............................................3-38 PADP_L01 ..........................................3-28, 3-31 Auxiliary process values...........................3-32 Message texts ..........................................3-31 Message texts and auxiliary process values .....................................3-31 PADP_L02 ..........................................3-33, 3-36 Auxiliary process values...........................3-37 Message texts .................................3-36, 3-37 Message texts and auxiliary process values .....................................3-36 PADP_L0x....................................................3-38 Connections .............................................3-38 PO_UPDAT ..................................................2-25 Process Control System PCS 7, Driver Blocks A5E00127662-01 R RACK.......................2-20, 2-21, 2-22, 2-23, 2-24 Auxiliary process values .......................... 2-24 Connections............................................. 2-24 Message texts.......................................... 2-24 Message texts and auxiliary process values..................................... 2-24 S S7-300/400 SM.................2-36, 2-41, 2-45, 2-53 Monitoring .....................2-36, 2-41, 2-45, 2-53 Signal Modules ...................................... A-2, A-8 MODE settings........................................... A-2 Text Library................................................ A-8 SUBNET ...........................2-17, 2-18, 2-19, 2-20 Auxiliary process values .......................... 2-20 Connections............................................. 2-19 Message texts.......................................... 2-20 Message texts and auxiliary process values..................................... 2-20 T Technical data ............................................. A-10 Text library ..................................................... A-9 Text Library.................................................... A-8 Signal Modules .......................................... A-8 Text Library for Signal Modules ..................... A-8 Totalizer PROFIBUS PA .............................. 3-45 V V0 ................................................................ 3-39 Y Y-Link ................................................. 3-39, 3-41 Index-3 09.10.2001 04.10.2001 Index Index-4 Process Control System PCS 7, Driver Blocks A5E00127662-01