https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page1/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Freely configurable safety module, with 20 safe inputs and 4 safe outputs, 4 signal, 2 clock, and 2 ground
switching outputs; can be extended via additional I/O modules, up to SILCL 3, Cat. 4/PL e, SIL 3, EN 50156,
plug-in spring-cage terminal block
The figure shows a version with a
screw connection
Your advantages
Freely configurable safety module for monitoring emergency stops, safety doors, light grids, etc.
With 20 safe inputs, 4 safe outputs, 4 alarm outputs, and 2 clock outputs on a design width of just 67.5 mm
Multifunctional use for a wide range of safety functions
Including IFS-CONFSTICK memory stick for easily storing and saving the configuration
Easy graphical configuration with the SAFECONF software
Easy graphical configuration instead of complex programming
Quick startup thanks to comprehensive simulation and test functions
Option for connecting fieldbus gateways for diagnostics and signaling functions
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
EN 50156
Safe and standard extension via INTERFACE DIN rail TBUS
Flexible extension with safe inputs and outputs
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4046356345897
Weight per Piece (excluding packing) 400.000 g
Custom tariff number 85371098
Country of origin Germany
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page2/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Technical data
Note
Utilization restriction EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 67.5 mm
Height 112 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 55 °C
Ambient temperature (storage/transport) -20 °C ... 70 °C
Max. permissible relative humidity (operation) 75 % (On average, 85 % occasionally)
Max. permissible humidity (storage/transport) 75 % (On average, 85 % occasionally)
Air pressure (operation) 70 kPa ... 108 kPa (up to 3000m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500m above sea level)
Maximum altitude max. 2000 m (SeeAppendix"Using PSR-TRISAFE
modulesataltitudesgreater than2000mabove sealevel")
Power supply
Rated control circuit supply voltage US24 V DC (A1/A2)
18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Rated control supply current IStyp. 110 mA
Limiting continuous current max. 6 A (For looped-through current paths A1/A1 and A2/A2)
Filter time typ. 20 ms (Load-dependent, in the event of voltage dips at US)
Status display 3x LED green,1x LED red
Protective circuit Yes, within the scope of the operating voltage limits
Digital inputs
Description of the input Digital, type HTL
Number of inputs 10 (Two-channel, up to SIL3)
20 (Single-channel, up to SIL2)
Input voltage range "0" signal 0 V DC ... 5 V DC (for safe Off)
Input voltage range "1" signal 11 V DC ... 30 V DC
Current consumption typ. 4 mA
Cable length max. 2000 m
Status display 20xLED green (1 LED per input)
Digital outputs
Number of outputs 4 (Safe semiconductor outputs, up to Cat.4 in accordance with
ENISO13849-1)
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page3/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Technical data
Digital outputs
2 (Ground switching outputs)
Nominal output voltage 24 V DC (Supplyvia24V/0V)
Nominal output voltage range 18 V DC ... 30 V DC (Incl. all tolerances, incl. residual ripple)
Limiting continuous current 2 A (Per channel, see Derating)
2 A (Total current of all outputs)
Output voltage < 5 V (Low state)
Leakage current max. 2 mA
Max. capacitive load max. 1 µF (Electroniccomponents)
Max. inductive load See "Protective circuit"
Test pulses < 1 ms
Note on protection circuit Yes,within thescopeofthe operating voltage limits
Short-circuit protection Yes
Status display 4xLED green (1LED per output)
Clock outputs
Output description Digital
Number of outputs 2
Voltage 24 V DC (Supplyvia24V/0V)
Limiting continuous current 100 mA
Test pulses < 1 ms
Short-circuit protection Yes
Alarm outputs
Output description Digital
Number of outputs 4
Voltage 24 V DC (Supplyvia24V/0V)
Limiting continuous current 100 mA
Short-circuit protection Yes
Times
Response time max. 30 ms (plusresponse timeofPSR-TS-SDOR4)
Recovery time < 10 s
General
Nominal operating mode 100% operating factor
Net weight 154 g
Mounting position On horizontal DIN rail
Mounting type DIN rail mounting
Degree of protection IP20
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page4/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Technical data
General
IP54
Min. degree of protection of inst. location IP54
Housing material Polyamide PA non-reinforced
Housing color yellow
Number of possible extension modules 1 (Max. continuous current via PSR-TBUS: 4A)
Number of possible safe extension modules 10 (Max. continuous current via PSR-TBUS: 4A)
Connection data
Connection method Spring-cage connection
pluggable Yes
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Safety-related characteristic data
Stop category 0
Designation IEC 61508 - High demand
Safety Integrity Level (SIL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation IEC 61508 - Low demand
Safety Integrity Level (SIL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation EN ISO 13849
Performance level (PL) d (1-channel parameterization)
e (2-channel parameterization)
Category 2 (1-channel parameterization)
4 (2-channel parameterization)
Designation EN 62061
Safety Integrity Level Claim Limit (SIL CL) 2 (1-channel parameterization)
3 (2-channel parameterization)
Designation EN50156
Safety Integrity Level (SIL) max. 3 (Reference IEC61508)
Standards and Regulations
Designation Air clearances and creepage distances between the power circuits
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page5/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Technical data
Standards and Regulations
Standards/regulations DIN EN 50178
Degree of pollution 2
Overvoltage category III
Vibration (operation) 2g
Shock (operation) 10g (Δt=11ms, threeshocksineach space direction)
10g (Δt=16ms, continuous shock, 1000 shocks in each space direction)
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
Connection diagram
INTERFACE-PSR
use only
PSR-TBUS
INTERFACE-PSR
use only
PSR-TBUS
INTERFACE-PSR
use only
PSR-TBUS
PSR-TBUS-
bus
connectors
PSR-TBUS-
bus
connectors
PSR-TBUS-
bus
connectors
PSR-TBUS DIN rail connectors are used for cross-wiring between the
modules.
Circuit diagram
A1 A2 T0
24V 0V O0 O1 O2 O3 O0- O1-
T0 T1 T1 I0 I1 I19 M0 M1 M2 M3
TBUS
NON-SAFE
PSR-TBUS
SAFE
POWER
24V DC
POWER
24V DC
TEST PULSE MONITORING
OUTPUT OUTPUTSAFE INPUT
LOGIC
SAFE OUTPUT USB
CONF
STICK
Diagram
0
2
1,5
1
0,5
0 25 30 35 40 45 50 55 60
Ambienttemperature[°C]
Totalcurrent
OutputOx[A]
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page6/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Application drawing
K1
K2
24V DC
0V
S1
S2
K2
K1
A1
I0
24V
I4
T0
I8
M0
I12
I16
O0
A1
I1
0V
I5
T0
I9
M1
I13
I17
O1
A2
I2
O0-
I6
T1
I10
M2
I14
I18
O2
A2
I3
O1-
I7
T1
I11
M3
I15
I19
O3
TRISAFE-M
TBUS
NON-SAFE
SAFE
PSR-TBUS
Classifications
eCl@ss
eCl@ss 4.0 27371102
eCl@ss 4.1 27371102
eCl@ss 5.0 27371901
eCl@ss 5.1 27371900
eCl@ss 6.0 27371800
eCl@ss 7.0 27371819
eCl@ss 8.0 27371819
eCl@ss 9.0 27371819
ETIM
ETIM 2.0 EC001449
ETIM 3.0 EC001449
ETIM 4.0 EC001449
ETIM 5.0 EC001449
ETIM 6.0 EC001449
UNSPSC
UNSPSC 6.01 30211901
UNSPSC 7.0901 39121501
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page7/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Classifications
UNSPSC
UNSPSC 11 39121501
UNSPSC 12.01 39121501
UNSPSC 13.2 39121501
Approvals
Approvals
Approvals
UL Listed / cUL Listed / Functional Safety / cULus Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 140324
Functional Safety 01/205/5151.03/17
cULus Listed
Accessories
Accessories
Device parameterization
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page8/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Accessories
Configuration package-SAFECONF-2986119
Configuration software for SafetyBridge technology and PSR-TRISAFE modules, connecting cable for PSR-TRISAFE
DIN rail connector
DIN rail bus connectors-ME 22,5 TBUS 1,5/ 5-ST-3,81 GN-2707437
DIN rail connector, nominal current (Ex): 8 A, nominal voltage (Ex): 125 V, number of positions: 5, pitch: 3.81 mm,
Articles with gold-plated contacts, bus connectors for connecting with electronic housings
DIN rail bus connectors-PSR-TBUS-2890425
DIN rail connector for safety switching devices, for supplying/controlling/monitoring (depending on the module)
Filter terminal block
Filter terminal block-PSR-FTB/20/86-2904477
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (20µF/86µF), as well
as for EMC filtering of 24V signals up to an amperage of 2A.
Filter terminal block-PSR-FTB/1.5/11.5-2904476
Terminal block for filtering test pulses from safe semiconductor outputs with adjustable filter values (1.5µF/11.5µF), as
well as for EMC filtering of 24V signals up to an amperage of 2A.
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page9/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Accessories
Gateways/Proxies
Data interface-EM-CAN-GATEWAY-IFS-2901504
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via CANopen®. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-MODBUS-GATEWAY-IFS-2901528
Gateway for the connection of up to 32 INTERFACE system devices via Modbus/TCP to a higher-level controller. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-DNET-GATEWAY-IFS-2901529
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via DeviceNet™. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-ETH-GATEWAY-IFS-2901988
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via EtherNet/IP™. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-PNET-GATEWAY-IFS-2904472
Gateway for the connection of up to 32 INTERFACE system devices via PROFINET to a higher-level controller. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page10/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Accessories
Data interface-EM-PB-GATEWAY-IFS-2297620
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via PROFIBUS DP. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-RS232-GATEWAY-IFS-2901526
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-232. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Data interface-EM-RS485-GATEWAY-IFS-2901527
Gateway for the connection of up to 32 INTERFACE system devices to a higher-level controller via Modbus/RS-485. The
INTERFACE system devices are connected to the Gateway via DIN rail connectors, the DIN rail connectors are provided.
Memory block
Memory block-IFS-CONFSTICK-2986122
Multi-functional memory block for the INTERFACE systemf for easy storage and backup of the configuration.
Copy and delete station-COPYSTATION - IFS-2901985
Copy and delete station for IFS-CONFSTICK memory modules for copying data from a master stick to up to four slave
sticks and for deleting data on one ore more slave sticks, connection via USB/mini USB cable.
https://www.phoenixcontact.com/us/products/2986025
04/02/2019Page11/11
Safety module-PSR-SPP- 24DC/TS/M-2986025
Accessories
Programming cable
USB cable-CABLE-USB/MINI-USB-3,0M-2986135
USB connecting cable: USB plug type A to USB plug type Mini-B; length: 3 m
Starter kit
Starter kit-PSR-TRISAFE STARTER KIT-2986300
STARTER kit for the PSR-TRISAFE safety module consisting of: PSR-TRISAFE demoboard (with inputs & outputs),
SAFECONF CD, Quick Start Guide, USB cable (3m) , voltage supply with international connector adapters and package
inserts.
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com